DC Backup UPS

Application, Maintenance and Installation Manual

Revision 1

Calculation example: 

2 Amps backup is required for 8 hours.

a) Multiply Amp x Hours (8 x 2 = 16). This gives 16Ahrs. Nearest size DCUPS would be 17Ahrs.
b) Look at Figure 3.1. The discharge time, in this case 8 Hrs, shows that approx. 90% of the 17Ah will be 

available from a fully charged battery

c) Check: 17 * 0.9 = 16 approximately so this unit will just satisfy the load 

The curve above shows the probable available Ampere-hour capacity for varying time periods over which 
the battery is drained. This is fairly indicative of commercially available sealed lead acid batteries. 

Figure 3.1

4

Technical description

Model 7021 and 7025 is a 12volt (nominal) DC power-supply with battery backup. An AC rectifier supplies 
power to the load and doubles as a battery charger. There are 3 modes of operation:

AC power available.  In this mode, the load is supplied from the AC rectifier. The battery is charged at a 
constant voltage but with controlled current. Thermal compensation is provided to ensure that the battery 
receives optimum charge. 

AC fail condition. In this mode, the internal 12volt lead acid battery supplies the load. Battery voltage 
and unbalance are monitored. Low battery is flagged as an alarm. 

Over-current condition. In this mode, the internal battery can supply peak currents to the load for short 
periods. The battery fuse limits the amount of over-current. Sustained high current will cause the fuse to 
open.

Changeover from AC to DC is done electronically without break in supply to the load. In AC available 
mode, the battery is charged automatically. 

18/10/06

7021 and 7025_manual1.doc

Page 4 of 7

Summary of Contents for 7021 Series

Page 1: ...algen Model 7021 7025 DC Backup UPS Manual Revision 1 Model 7021 and 7025 Series Amalgen Technologies Pty Ltd 43 Anderson road Mortdale NSW 2223 Australia 18 10 06 7021 and 7025_manual1 doc Page 1 of...

Page 2: ...e of battery when AC returns Amalgen battery management system The above functions are provided in a single unit designed to fit in 19 inch equipment racks Importantly the unit forms a complete soluti...

Page 3: ...rly in the small price sensitive categories is not straightforward Then there are power spikes and load transients to consider A DC back up system is a good alternative The 7021 and 7025 back up syste...

Page 4: ...h battery backup An AC rectifier supplies power to the load and doubles as a battery charger There are 3 modes of operation AC power available In this mode the load is supplied from the AC rectifier T...

Page 5: ...motely via voltage free contacts The following table shows the details CONDITION LOCAL LEDs REMOTE RELAYs Charger OK Green light if OK N O contact closes if OK DC available Green light if Vload over 1...

Page 6: ...the batteries as follows 1 connect RED wire to ve terminal of battery 1 2 connect BLACK wire to ve terminal of battery 2 3 Fit fuse Replacement of batteries follows the same procedure Remote monitori...

Page 7: ...Fusing To be provided external to unit IP rating IP20 DC Voltage 12VDC Nominal 9V to 14 Output is floating from earth Current The current ratings of different models given below Charger Type Constant...

Reviews: