Function
Range
Description
R.INP
continued
NONE
,
P.HLd
d.HLd
Hi
,
Lo
,
HiLo
,
SP.Ac,
No.Ac,
CAL.S
,
duLL
or
A.cIr
SP.Ac
- setpoint access only. This blocks access to any functions except the
alarm setpoint functions unless the remote input pins are short circuited or
entry is made via
CAL
mode.
No.Ac
- no access. This blocks access to all functions unless the remote input
pins are short circuited or entry is made via
CAL
mode.
duLL
- display brightness control. The remote input can be used to change
the display brightness. When this mode is selected the display brightness can
be switched, via the remote input, between the brightness level set at the
brgt
function and the brightness level set at the
duLL
function.
A.cIr
- acknowledge or reset alarm, used when
A
x
Ltch
is set to
on
i.e.
when using latching alarm relays. The remote input can be used to
acknowledge an alarm condition or reset the alarm. If the remote input is
activated when there is still an alarm condition then the alarm will be
acknowledged and the relay will automatically reset when the input moves out
of alarm condition. If the remote input is activated when the input has been in
an alarm condition but is no longer in alarm condition then the relay will
immediately reset. See
A
x
Ltch
function for further description of latching
operation.
SPFN
chnI
SCAN,
HIGH,
Lo,
AUGE,
dIFF,
dIF1,
ch1,
ch2
to
ch8
Remote or
P
button function mode of operation. This function sets the
operation mode for the remote input (
R.INP
function) or
P
button (
P.but
function) operation. See
R.INP
function for a description of the operation of
the
SPFN chnI
functions.
ACCS
OFF
,
EASY,
NONE
or
ALL
Access mode - the access mode function
ACCS
has four possible settings
namely
OFF
,
EASY,
NONE
and
ALL
. If set to
OFF
the mode function has no
effect on alarm relay operation. If set to
EASY
the easy alarm access mode
will be activated, see details at the beginning of this chapter preceding the
A1Lo
function. If set to
NONE
there will be no access to any functions via
FUNC
mode, entry via
CAL
mode must be made to gain access to alarm and
calibration functions. If set to
ALL
then access to all functions, including
calibration functions, can be gained via
FUNC
mode.
SPAC
A1
,
A1-2
etc
Setpoint access - seen only if more than 1 relay fitted.
Sets the access to the alarm relay set points. The following choices are
available:
A1
- allows setpoint access to alarm 1 only.
A1-2
- allows access to alarms 1 and 2.
A1-3
- allows access to alarms 1,2 and 3.
A1-4
- allows access to alarms 1, 2, 3 and 4
The remote input function (
R.INP
) must be set to
SP.AC
for this function to
operate. Note: Only the setpoints which have been given a value will be
accessible e.g. if
A1Hi
is set to
OFF
then there will be no access to the
A1Hi
function when
SPAC
is used.
Page 20 of 27