DSC
®
Power Series
™
Programming
Compatible Panels
• PC580 (Power 432)
• PC1555 (Power 632)
• PC1555MX (Power 632)
• PC5010 (Power 832)
• PC5020 (Power 864)
• PC5015 (Power 832)
• PC1616
•
PC1832
•
PC1864
1. Set up an account with your interactive services provider.
2. Add a contact that uses the system MASTER CODE to the account before connecting the IGM.
This is required for the IGM to be able to properly configure the system settings.
3. Program the DSC panel using an
INSTALLER CODE
.
Panel Programming
• Disable the IGM ([380]:[1])
• Disable the Telephone Line Monitor ([015]:[7])
• Delete Telephone Numbers (programming section 301-303)
• Verify Alt Comm ([351]:[5]) is enabled
• Verify T-Link is Disabled ([382]:[5])
• Verify Master Code Not Changeable is Disabled ([015]:[6])
• Verify Access Code Required for *1, *2, *3 menus is disabled ([022]:[1])
• Verify that keypad lockout is either zero (disabled) or higher than 6 ([012])
• If you have removed any bus devices, perform a Module Supervision Reset ([902])
4. Verify alarm report codes are setup properly for zones that are being used, 1-64 (programming
section 320-349). System will report as Burg (130) if programmed as FF.
5. If using Aux input (PGM2) verify Aux input report codes are setup properly (programming section
329:4). System will report as Fire (110) if programmed as FF.
6. To enable reporting of the Period Test Transmission, program the “Periodic Test Transmission”
([348]:[4]) and the “Periodic Test Transmission with Trouble” ([348]:[3]) reporting codes to “02”.
7. All other reports are hard coded in the IGM and cannot be changed regardless of what is entered
in the programmed location.
• Format and account number have no effect on reporting.
8. Disarm the system (all partitions).
9. Power down the DSC system.
10. Set IGM’s panel selector switch to
DSC/OTHER
.
11. Connect the DSC system and the IGM as shown in the wiring diagram below.
12. Power up to the DSC system.
•
The DSC control panel will begin automatic configuration. This can take up to 2 minutes.
13. Installation is complete.
Red
AUX+
Black
AUX-
Green
GRN
Yellow
YEL
DSC Panel
IGM