- 2 -
WayPoint DC
Overview:
Altronix DC Outdoor Power Supply/Chargers provide 12VDC or 24VDC and are designed to be conveniently
located where power is required.
WayPoint DC Reference Chart:
Altronix
Model
Number
Output
(VDC)
Supply
Current (A)
Input Rating:
120VAC, 60Hz
Input
Fuse Rating
Battery Fuse
Rating
Ripple
Voltage (mV)
Under low
battery
condition
Accommodates
up to 7AH
Batteries
Waypoint102
12VDC
10
3.5A
5A/250V
15A/32V
760
3
Waypoint104
24VDC
10
4.5A
6.3A/250V
15A/32V
700
3
Specifications:
Installation Instructions:
Unit shall be installed in accordance with The National Electrical Code and all applicable Local Regulations.
1. Remove backplane from enclosure prior to mounting (do not discard hardware).
2. Mark and drill desired inlets on the enclosure to facilitate wiring (Fig. 2, pg. 4).
Note: Inlets for conduit fittings should only be made on the bottom of the enclosure.
UL Listed NEMA type 4X rated conduit connector/hubs shall be used for the appropriate size inlets.
3. Mount unit in the desired location. For wall mounting refer to Fig. 4, pg. 7.
For pole mounting installation refer to pg. 7 - Pole Mounting Using Optional Pole Mount Kit PMK1.
4. Mount backplane to enclosure with hardware.
5. To facilitate wire entry utilize weather-tight NEMA 4 rated connectors, bushings, and cable.
6. Connect unswitched AC power (120VAC, 60 Hz) to terminals marked [L, N] (Fig. 3, pg. 5).
Green branch wire connects to earth (safety) ground lug .
Wire gauge range of connectors is 14 AWG to 11 AWG (1.6mm to 2.5mm diameter).
7. Measure output voltage before connecting devices. This helps avoiding potential damage.
Input:
• Input: 120VAC, 60Hz.
Output:
•
WayPoint102: 12VDC;
WayPoint104: 24VDC.
• Auxiliary power-limited output rated @ 1A
(unswitched).
• Filtered and electronically regulated output.
• Thermal overload and short circuit protection.
Battery Backup:
• Built-in charger for sealed lead acid or
gel type batteries.
• Maximum charge current 1.54A.
• Automatic switch over to stand-by battery.
Output Disconnect:
• Supervised output disconnect (latching or non-
latching) 10K EOL resistor. Operates on a normally
open (NO) or normally closed (NC) trigger.
Supervision:
• AC fail supervision (form “C” contacts).
• Battery fail & presence supervision
(form “C” contacts).
• Low power shutdown. Shuts down DC output
terminals if battery voltage drops below 71-73% for
12V units and 70-75% for 24V units (depending on
the power supply). Prevents deep battery discharge.
Visual Indicators:
• Green AC Power LED indicates 120VAC present.
• AC input and DC output LED indicators.
Environmental:
• Operating Ambient Temperature:
– 40°C to 60°C (– 40°F to 140ºF).
• Relative Humidity: 85%, +/– 5%
• Storage Temperature:
– 40ºC to 75ºC (– 40ºF to 167ºF).
• Operating Altitude: – 304.8 to 2,000m.
Optional Accessories:
•
PMK1 Pole Mount Kit
simplifies installation of outdoor units.
•
LINQ2 Network Communication Module
provides remote supervision, control,
and monitoring over LAN/WAN.
Enclosure:
• NEMA 4/4X, IP66-11 Rated enclosure for
outdoor use.
• Enclosure Dimensions (H x W x D approx.):
13.31” x 11.31” x 5.59”
(338.1 mm x 287.3 mm x 142 mm).
• Enclosure accommodates up to two (2)
12VDC/7AH batteries.
CAUTION
HIGH VOLTAGE
L
G
N
NC C NO
NC C NO
BAT FAIL
AC FAIL
---
DC
+
AC
AC1
DC
---
BA
T
+
+ AUX –
enable
disable
1 min.
2 hr.
AC DELAY SHUTDOWN
TRIGGER EOL
SUPERVISED
NO GND
RESET
O
N
5A 250V
Summary of Contents for WayPoint104