- 2 - 

WayPoint DC

Overview:

Altronix DC Outdoor Power Supply/Chargers provide 12VDC or 24VDC and are designed to be conveniently 
located where power is required.

WayPoint DC Reference Chart:

Altronix 
Model 
Number

Output

(VDC)

Supply

Current (A)

Input Rating:

120VAC, 60Hz

Input 

Fuse Rating

Battery Fuse

Rating

Ripple 

Voltage (mV)

Under low

battery 

condition

Accommodates

up to 7AH

Batteries

Waypoint102

12VDC

10

3.5A

5A/250V

15A/32V

760

3

Waypoint104

24VDC

10

4.5A

6.3A/250V

15A/32V

700

3

Specifications:

Installation Instructions:

Unit shall be installed in accordance with The National Electrical Code and all applicable Local Regulations.
1.  Remove backplane from enclosure prior to mounting (do not discard hardware).
2.  Mark and drill desired inlets on the enclosure to facilitate wiring (Fig. 2, pg. 4).
 

Note: Inlets for conduit fittings should only be made on the bottom of the enclosure. 

 

UL Listed NEMA type 4X rated conduit connector/hubs shall be used for the appropriate size inlets.

3.  Mount unit in the desired location. For wall mounting refer to Fig. 4, pg. 7.
 

For pole mounting installation refer to pg. 7 - Pole Mounting Using Optional Pole Mount Kit PMK1.

4.  Mount backplane to enclosure with hardware.
5.  To facilitate wire entry utilize weather-tight NEMA 4 rated connectors, bushings, and cable.
6.  Connect unswitched AC power (120VAC, 60 Hz) to terminals marked [L, N] (Fig. 3, pg. 5)
 

Green branch wire connects to earth (safety) ground lug      .

 

Wire gauge range of connectors is 14 AWG to 11 AWG (1.6mm to 2.5mm diameter).

7.  Measure output voltage before connecting devices. This helps avoiding potential damage.

Input:

•  Input: 120VAC, 60Hz.

Output:

• 

WayPoint102: 12VDC;

 

WayPoint104: 24VDC.

•  Auxiliary power-limited output rated @ 1A 
 (unswitched).
•  Filtered and electronically regulated output.
•  Thermal overload and short circuit protection.

Battery Backup:

•  Built-in charger for sealed lead acid or 
  gel type batteries. 
•  Maximum charge current 1.54A.
•  Automatic switch over to stand-by battery.

Output Disconnect:

•  Supervised output disconnect (latching or non-
  latching) 10K EOL resistor. Operates on a normally 
  open (NO) or normally closed (NC) trigger.

Supervision:

•  AC fail supervision (form “C” contacts).
•  Battery fail & presence supervision 
  (form “C” contacts).
•  Low power shutdown. Shuts down DC output 
  terminals if battery voltage drops below 71-73% for 
  12V units and 70-75% for 24V units (depending on 
  the power supply). Prevents deep battery discharge.

Visual Indicators:

•  Green AC Power LED indicates 120VAC present.
•  AC input and DC output LED indicators.

Environmental:

•  Operating Ambient Temperature:
   

– 40°C to 60°C (– 40°F to 140ºF). 

•  Relative Humidity: 85%, +/– 5%
•  Storage Temperature: 
  – 40ºC to 75ºC (– 40ºF to 167ºF).
•  Operating Altitude: – 304.8 to 2,000m.

Optional Accessories:

• 

PMK1 Pole Mount Kit 

  simplifies installation of outdoor units.
• 

LINQ2 Network Communication Module

  provides remote supervision, control, 
  and monitoring over LAN/WAN.

Enclosure:

•  NEMA 4/4X, IP66-11 Rated enclosure for 
  outdoor use.
•  Enclosure Dimensions (H x W x D approx.):
  13.31” x 11.31” x 5.59”  

 

  (338.1 mm x 287.3 mm x 142 mm).
•  Enclosure accommodates up to two (2)
  12VDC/7AH batteries.

CAUTION

HIGH VOLTAGE

L

G

N

NC  C  NO 

NC  C  NO

BAT FAIL

AC FAIL

--- 

 DC  

+

AC

AC1

DC

--- 

BA

+

+ AUX –

enable
disable

1 min.
2 hr.

AC DELAY   SHUTDOWN

TRIGGER EOL

SUPERVISED

NO          GND

RESET

O

N

5A 250V

Summary of Contents for WayPoint104

Page 1: ...Rev 062818 WPF More than just power TM DC Outdoor Power Supply Chargers Installation Guide Models Include WayPoint102 12VDC 10A WayPoint104 24VDC 10A...

Page 2: ...sure output voltage before connecting devices This helps avoiding potential damage Input Input 120VAC 60Hz Output WayPoint102 12VDC WayPoint104 24VDC Auxiliary power limited output rated 1A unswitched...

Page 3: ...secure enclosure door with latches and optional lock WARNING When installing in a non restricted service area use lock or other fastened means on door latches This installation should be made by quali...

Page 4: ...ing Inlets Fig 2 Fig 1 eFlow Board configuration L G N NC C NO NC C NO BAT FAIL AC FAIL DC AC AC1 DC BAT AUX TRIGGER EOL SUPERVISED Input Fuse Battery Fuse NO GND RESET OFF 24V ON 12V enable disable 1...

Page 5: ...user to the presence of an insulated DANGEROUS VOLTAGE within the product s enclosure that may be of sufficient magnitude to constitute an electric shock The exclamation point within an equilateral t...

Page 6: ...6 WayPoint DC Notes...

Page 7: ...ap through the locking mechanism on the strap then tighten the screw with flat head screwdriver or 5 16 hex socket driver Fig 6 pg 7 and Fig 8 pg 7 3 Attach the bottom bracket to the enclosure by inse...

Page 8: ...MEMBER Enclosure Dimensions H x W x D approx 13 31 x 11 31 x 5 59 338 1mm x 287 3mm x 142mm 1 61 40 9mm 3 96 100 6mm 5 59 142mm 10 32 X 0 375 9 6mm BRASS INSERT X4 STAINLESS STEEL PIANO HINGE 11 31 28...

Reviews: