Specifications:

Agency Listings:

•  UL 294 - 7th edition. Trove1R Power Controllers: Destructive Attack I.

•  This Class B digital apparatus complies with Canadian ICES-003. 

  Cet appareil numérique de la classe B est conforme á la norme NMB-003 du Canada.

•  CE European Conformity.

Environmental:

•  Humidity and Temperature conditions as tested by 

UL: (85%, +/-5% @ 30ºC +/-2ºC), 

   

ULC: 

(93%, +/-2% @ 32ºC +/-2ºC).

Battery Backup:

•  If batteries are being used in your installation do not fit into the Trove1R unit, it is required to install a separate 

  enclosure, UL Listed for appropriate application. Separate battery enclosure is required to have 50 cubic 

  inches of additional open space. All wiring methods shall be in accordance with the National Electrical Code 

  NFPA 70/NFPA 72/ANSI and with all local codes and authorities having jurisdiction. Battery circuits are not 

  power-limited; provide 0.25” spacing from power-limited circuits and use separate knockout. If additional 

  battery enclosure is required, it must be UL Listed for the application and mounted within 5’ of the Trove1R 

  enclosure in the same room; minimum 12 AWG wire in appropriate conduit is required for connection. When 

  using conduit, make sure it is installed in a matter where it can not turn.

Additional Features:

•  16 Gauge enclosure with ample knockouts for convenient access.