background image

 

- 2 -  

SMP1024Xseries

Overview:

These units convert a 115VAC 60Hz input into a regulated 24VDC @ 10 amp continuous supply current
(see specifications). 

SMP1024X Series Power Supply Configuration Reference Chart:

Altronix 

Model Number

Accessory Power Distribution Module(s)

Number of  Outputs

Fused Outputs

PTC Outputs

Individual  Output Rating

Supervised

115VAC / 60Hz Input Current  (amp)

24VDC Total  Output Current  (amp)

SMP10C24X

-

1

-

-

-

-

2.7 amp

10 amp

SMP10PMC24X

-

1

-

-

-

P

2.7 amp

10 amp

SMP10PM24P4

PD4

4

P

-

3.5 amp

P

2.7 amp

10 amp

SMP10PM24P4CB

PD4CB

4

-

P

2.5 amp

P

2.7 amp

10 amp

SMP10PM24P8

PD8

8

P

-

3.5 amp

P

2.7 amp

10 amp

SMP10PM24P8CB

PD8CB

8

-

P

2.5 amp

P

2.7 amp

10 amp

SMP10PM24P16

PD16W

16

P

-

3.5 amp

P

2.7 amp

10 amp

SMP10PM24P16CB

PD16WCB

16

-

P

2.5 amp

P

2.7 amp

10 amp

Specifications:

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local 
codes and authorities having jurisdiction. Product is intended for indoor use only. 
1.  Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the
  enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s 
  upper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes. Remove the 
  enclosure. Drill the lower holes and install three fasteners. Place the enclosure’s upper keyholes over the two
  upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pgs. 6).
  Secure enclosure to earth ground. 
2.  Connect AC power to the terminals marked [L & N], connect ground to the terminal marked [G] (if used), 
  (Fig. 1, pg. 4 or Fig. 4, pg. 5). Use 18 AWG or larger for all power connections (Battery, DC output).
  Keep power-limited wiring separate from non power-limited wiring (115VAC / 60Hz Input, Battery Wires).  

 

  Minimum 0.25” spacing must be provided.
  CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment. 
  There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.
3.  Measure output voltage before connecting devices. This helps avoiding potential damage.

Input:

•  Input 115VAC, 60Hz, 2.7 amp.

Output:

•  24VDC output. 
•  10 amp supply current. 
•  Filtered and electronically regulated outputs.
•  Short circuit and thermal overload protection.

Battery Backup:

•  Built-in charger for sealed lead acid or 
  gel type batteries.
•  Maximum charge current 0.7 amp. 
•  Zero voltage drop when switching over 
  to battery backup.

Supervision:

•  AC fail supervision (form “C” contacts).  
•  Battery presence and low battery supervision 
  (form “C” contacts).

Visual Indicators:

•  AC input and DC output LED indicators.

Electrical:

•  Operating temperature: 0º C to 49º C ambient.
•  BTU/Hr.: 122.84 BTU/Hr.
•  System AC input VA requirement: 310.5VA.

Mechanical:

•  Enclosure Dimensions (H x W x D approx.):
  13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm)
  -  Accommodates up to two (2)12VDC/7AH batteries.

Summary of Contents for SMP10PM24X Series

Page 1: ...ent with supervision with supervision Four 4 fuse protected outputs Four 4 PTC protected outputs SMP10PM24P8 SMP10PM24P8CB 24VDC 10 amp total supply current 24VDC 10 amp total supply current with supe...

Page 2: ...three fasteners Place the enclosure s upper keyholes over the two upper screws Install the two lower screws and make sure to tighten all screws Enclosure Dimensions pgs 6 Secure enclosure to earth gro...

Page 3: ...wer OFF ON No DC output OFF OFF Loss of AC Discharged or no stand by battery No DC output PD4 PD4CB PD8 PD8CB Power Distribution Module Green Power Distribution Module Status ON Normal operating condi...

Page 4: ...tional rechargeable stand by batteries must match the power supply output voltage setting INPUT LED 1P 2P 3P 4P FUSED OUTPUTS 1N 2N 3N 4N COMMON OUTPUTS F1 F1 F2 F3 F4 COMMON POWER OUTPUTS 1P 1N 2P 2N...

Page 5: ...ply output voltage setting Optional Rechargeable Stand by Battery Optional Rechargeable Stand by Battery Fig 4 Fig 4a LOW BAT NC C NO NC C NO OFF ON 5A 250V AC FAIL BAT DC 15 AC DC Power Distribution...

Page 6: ...two 2 12VDC 7AH batteries 1 40 36mm 1 40 36mm 4 85 123mm 4 85 123mm 1 40 36mm 1 40 36mm 5 10 130mm 5 10 130mm 13 0 330mm 5 10 130mm 6 5625 167mm 1 20 31mm 1 20 31mm 1 20 31mm 3 25 83mm 3 25 83mm 3 25...

Page 7: ...SMP1024Xseries 7 Notes...

Page 8: ...ographical errors Product specifications are subject to change without notice 140 58th Street Brooklyn New York 11220 USA 718 567 8181 fax 718 567 9056 web site www altronix com e mail info altronix c...

Reviews: