9. Green power LEDs on faceplate will illuminate when AC power is present. When an output is in a trouble
condition (blown fuse or tripped PTC) the corresponding LED will not be illuminated (Fig. 1, pg. 3).
a. Blown fuse (R248220, R248300220, and R248600220) - set power switch on the back of the unit to the
OFF position (Fig. 1c, pg. 3). Remove front faceplate to access fuses.
Replace with fuses rated @ 3.5A/250VA (R248220 and R248300220).
Replace with fuses rated @ 5A/32VA (R248600220).
b. Tripped PTC (R248CB220, R248300CB220, and R248600220) - to reset PTC, set power switch on the
back of the unit to the OFF position. After approximately 30 secs. set power switch to the ON (RESET)
position
(Fig. 1c, pg. 3).
10. Power switch with built-in circuit breaker:
OFF position - Switch not illuminated. Outputs not powered.
RESET (ON) position - Switch illuminated. Outputs powered.
Circuit breaker tripped - Switch not illuminated. Power LEDs on faceplate are not illuminated.
Outputs not powered. To reset circuit breaker set power switch to the ON (RESET) position (Fig. 1c, pg. 3).
Note: Do not exceed units electrical load ratings as indicated in reference chart (pg. 2).
Do not place mechanical load on unit. Data racks should always be properly ventilated.
Unit is designed optimally for normal data room office installations.
CAUTION:
Equipment to be installed / serviced by authorized / trained personnel only.
Shut branch circuit power before installing / servicing equipment.
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture.
This installation should be made by qualified service personnel and should conform to
the National Electrical Code and all local codes.
P
N
N
P
Illuminated
Power Disconnect
Circuit Breaker
with manual reset
Strain Relief
Line Cord
Removable
Terminal
Block
PTC1
Used
on PTC
Models
AC Power
LEDs
AC Power
LEDs
XFMR
XFMR
Green Wire
Earth GND
S P N S P N
24VAC Output
(Factory Set) 28VAC Output
28VAC (Black)
24VAC (Yellow)
COM (Brown)
28VAC (Black)
24VAC (Yellow)
COM (Brown)
Fig. 1
Fig. 1a
Fig. 1b
Fig. 1c
Fig. 1d