- 4 -
MOM5C
Typical Application Diagrams:
Fig. 1
MOM5C module shown with wet and/or dry
normally closed trigger inputs
(Non-Latching):
TRIGGER
--
INPUT +
EOL 2.2K
(+)
(-)
DC VOLTAGE INPUT
FROM FACP SIGNALING
OUTPUT OR ACCESS
CONTROL DEVICE
NORMALLY CLOSED (NC)
INPUT FROM FACP
OR ACCESS CONTROL DEVICE
TRIGGER
--
INPUT +
EOL
2.2K
(+)
(-)
DC VOLTAGE INPUT
FROM FACP SIGNALING
OUTPUT OR ACCESS
CONTROL DEVICE
NORMALLY OPEN (NO)
INPUT FROM FACP
OR ACCESS CONTROL DEVICE
MOM5C module shown with wet and/or dry
normally open trigger inputs
(Non-Latching):
Fig. 2
Two (2) or more MOM5C modules shown with wet and/or dry normally closed trigger inputs
(Non-Latching):
TRIGGER
LED
POWER
ON LED
TRIGGER
--
INPUT +
EOL 2.2K
EOL 2.2K
NORMALLY CLOSED (NC)
INPUT FROM FACP OR
ACCESS CONTROL DEVICE
DC VOLTAGE INPUT FROM
FACP SIGNALING
OUTPUT OR ACCESS
CONTROL DEVICE
(+)
(--)
TO TRIGGER INPUT
OF NEXT MOM5
NC C NO
DRY OUTPUT
NC C NO
POWER FAIL
TRIGGER
LED
POWER
ON LED
TRIGGER
--
INPUT +
NC C NO
DRY OUTPUT
NC C NO
POWER FAIL
TRIGGER
LED
POWER
ON LED
TRIGGER
--
INPUT +
EOL 2.2K
NORMALLY OPEN (NO)
INPUT FROM FACP OR
ACCESS CONTROL DEVICE
DC VOLTAGE INPUT FROM
FACP SIGNALING
OUTPUT OR ACCESS
CONTROL DEVICE
(+)
(--)
TO TRIGGER INPUT
OF NEXT MOM5
NC C NO
DRY OUTPUT
NC C NO
POWER FAIL
TRIGGER
LED
POWER
ON LED
TRIGGER
--
INPUT +
NC C NO
DRY OUTPUT
NC C NO
POWER FAIL
EOL
2.2K
Fig. 3
Two (2) or more MOM5C modules shown with wet and/or dry normally open trigger inputs
(Non-Latching):
Summary of Contents for MOM5C