Overview:

Altronix MOM5C multi-output power distribution module converts one (1) non power-limited DC voltage input 
to five (5) power-limited outputs. Each output will route power to a variety of access control hardware and 
devices which includes Mag Locks, Electric Strikes, Magnetic Door Holders, etc. These outputs will operate in 
both fail-safe and fail-secure modes. Controlled trigger input is achieved through normally open (NO) or nor-
mally closed (NC) supervised input or the polarity reversal from an FACP (Fire Alarm Control Panel). A form 
“C” dry output relay will enable HVAC Shutdown, Elevator Recall or trigger auxiliary devices. 

Specifications:

Agency Listings:

• 

UL294 

Access Control System Units.

 

UL1481  

Standard for Safety for Fire Protective

   

Signaling Systems.

• 

MEA  

NYC Department of Buildings 

  

Approved.

• 

CSFM  

California State Fire Marshal 

  

Approved.

•  NFPA72 compliant.

Input:

•  12VDC or 24VDC from power supply.

Output:

•  12VDC or 24VDC selectable outputs.
•  Five (5) individual power-limited Class 2 outputs.
•  Current limit is 2A @ 12VDC or 24VDC per output.

Visual Indicators:

•  Red LED’s indicate condition of each power output.
•  Power and input trigger LEDs. 

Supervision:

•  Fire Alarm Panel or Access Control System trigger
  inputs. (NO or NC supervised trigger input and
  polarity reversal trigger input).
•  Output relay indicates that unit is triggered.
   (Form “C” contact rated 1A @ 28VDC).
•  Power fail supervision relay 
  (Form “C” contact rated 1A @ 28VDC).

Special Features:

•  Will interface with most UL Listed Power Supplies

Enclosure Dimensions:

  8” x 7.25” x 3.5” (215.9mm x 190.5mm x 88.9mm)

Current Draw:

Input Voltage

Stand-by

Alarm

12VDC

0.024A

0.066A

24VDC

0.026A

0.074A

Installation Instructions:

1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes 
  in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place 
  the enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower 
  two holes. Remove the enclosure. Drill the lower holes and install the two fasteners. Place the enclosure’s 
  upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws 
  (Enclosure Dimensions, pg. 8).
2. Connect the DC of the power supply to the terminals marked [– DC Input +] carefully observing polarity.
3. Connect door strikes (fail-secure) positive to terminals marked [1 through 5 Pos. (+) DC Output (Alarm)] 
  and negative to [NEG1] through [NEG5] (Fig. 7, pg. 6).
4. Connect mag locks, door holders (fail-safe) positive to terminals marked [6 through 10 Pos. (+) DC Output
  (Stand-by)] and negative to [NEG1] through [NEG5] (Fig. 7, pg. 6).
5. To trigger the MOM5C from a FACP connect signaling circuit of FACP to terminals marked [– INPUT +].
  Polarity is shown in alarm condition. Connect the wires on opposite sides of the screw.
6. To trigger the MOM5C using a supervised dry contact connect a 2.2K resistor in series to terminals marked
  [TRIGGER] for a NC (Normally Closed) trigger input or connect a 2.2K resistor in parallel to terminals 
  marked [TRIGGER] for NO (Normally Open) trigger input (Fig. 7, pg. 6).
7. Connect the auxiliary devices that are to be triggered by the MOM5 to terminals marked [Dry Output]:
  For Normally Open operation connect wires to the terminals marked [NO & C].
  For Normally Closed operation connect wires to the terminals marked [NC & C].
 

Note: This relay will energize when the MOM5C is triggered.

8. Connect trouble reporting device to the terminals marked [Power Fail]. 
  For Normally Open operation connect wires to the terminals marked [NO & C].
  For Normally Closed operation connect wires to the terminals marked [NC & C].
 

Note: This relay will switch when power is lost to the MOM5C.

Summary of Contents for MOM5C

Page 1: ...Rev 012100 More than just power TM MOM5C Multi Output Power Distribution Module for Access Control Installation Guide Altronix Corp 140 58th St Brooklyn NY...

Page 2: ...the wall to line up with the top two keyholes in the enclosure Install two upper fasteners and screws in the wall with the screw heads protruding Place the enclosure s upper keyholes over the two uppe...

Page 3: ...BY to terminals marked POS DC OUTPUT ALARM e g fire alarm con trol panel indications circuit NEG 1 THROUGH NEG 5 Supplies constant negative voltage POS DC OUTPUT ALARM 1 5 Supplies positive voltage w...

Page 4: ...igger inputs Non Latching TRIGGER LED POWER ON LED TRIGGER INPUT EOL 2 2K EOL 2 2K NORMALLY CLOSED NC INPUT FROM FACP OR ACCESS CONTROL DEVICE DC VOLTAGE INPUT FROM FACP SIGNALING OUTPUT OR ACCESS CON...

Page 5: ...NPUT NORMALLY CLOSED NC INPUT FROM FACP OR ACCESS CONTROL DEVICE DC VOLTAGE INPUT FROM FACP SIGNALING OUTPUT OR ACCESS CONTROL DEVICE NC C NO DRY OUTPUT NC C NO POWER FAIL TRIGGER LED POWER ON LED TRI...

Page 6: ...STANDBY NC C NO POWER FAIL TRIGGER 1 2 3 4 5 POS DC OUTPUT ALARM NEG1 NEG2 NEG3 NEG4 NEG5 DC INPUT INPUT MOM5 TRIGGER 12VDC or 24VDC FROM POWER SUPPLY FROM FACP SIGNALING OUTPUT FACP EOL 2 2K EOL 2 2...

Page 7: ...MOM5C 7 Notes...

Page 8: ...Warranty Made in U S A IIMOM5C E22R MEMBER Enclosure Dimensions H x W x D 8 x 7 25 x 3 5 215 9mm x 190 5mm x 88 9mm 1 25 31 75mm 1 25 31 75mm 1 25 31 75mm 1 125 28 575mm 1 25 4mm 1 25 4mm 1 25 4mm 5 2...

Reviews: