Altronix MOM5C Installation Manual Download Page 3

 

MOM5C 

- 3 -

LED Diagnostic Table:

LED

ON

OFF

Power (Green)

Normal operating condition.

Power failure.

Trigger (Green)

Input is triggered (alarm condition).

MOM5 in stand-by (non-alarm condition).

Outputs (Red)

Output tripped due to a short circuit or 
overload condition.

Normal operation.

Terminal Identification:

Terminal Legend

Function/Description

– DC INPUT +

12VDC or 24VDC from power supply.

TRIGGER

Dry normally open [NO] or normally closed [NC] supervised (2.2K EOL resistor) 
input trigger. A short or open circuit will transfer power from terminals marked 
[POS. (+) DC OUTPUT (STAND-BY)] to terminals marked [POS (+) DC OUTPUT 
(ALARM)].

– INPUT +

Wet (5-30VDC) input trigger. Applying voltage to these terminals in the polarity 
shown will transfer power from terminals marked [POS. (+) DC OUTPUT (STAND-
BY)] to terminals marked [POS. (+) DC OUTPUT (ALARM)] (e.g. fire alarm con-
trol panel indications circuit).

NEG. 1
THROUGH NEG. 5

Supplies constant negative (–) voltage.

POS. (+) DC OUTPUT 
(ALARM) 1-5

Supplies positive (+) voltage when dry trigger input or fire alarm wet trigger 
input is applied.

POS. (+) DC OUTPUT
(STAND-BY) 6-10

Supplies positive (+) voltage in normal condition. Power is removed when dry trig-
ger input or fire alarm wet trigger input is applied.

NC, C, NO
DRY OUTPUT

When the MOM5 is triggered, the terminals marked [C and NO] will open and the 
terminals marked [C and NC] will close. This output is used to trigger auxiliary 
devices. (e.g. HVAC Shutdown, Elevator Recall etc.). Contact rating 1A @ 28VDC.

NC, C, NO
POWER FAIL

Form “C” contacts used for reporting no voltage is present at [– DC INPUT +] 
terminals. Under normal conditions terminals marked [NO and C] are open, 
[NC and C] are closed. A loss of power causes terminals marked [NO and C] to close 
and [NC and C] to open. Contact rating 1A @ 28VDC.

Summary of Contents for MOM5C

Page 1: ...Rev 012100 More than just power TM MOM5C Multi Output Power Distribution Module for Access Control Installation Guide Altronix Corp 140 58th St Brooklyn NY...

Page 2: ...the wall to line up with the top two keyholes in the enclosure Install two upper fasteners and screws in the wall with the screw heads protruding Place the enclosure s upper keyholes over the two uppe...

Page 3: ...BY to terminals marked POS DC OUTPUT ALARM e g fire alarm con trol panel indications circuit NEG 1 THROUGH NEG 5 Supplies constant negative voltage POS DC OUTPUT ALARM 1 5 Supplies positive voltage w...

Page 4: ...igger inputs Non Latching TRIGGER LED POWER ON LED TRIGGER INPUT EOL 2 2K EOL 2 2K NORMALLY CLOSED NC INPUT FROM FACP OR ACCESS CONTROL DEVICE DC VOLTAGE INPUT FROM FACP SIGNALING OUTPUT OR ACCESS CON...

Page 5: ...NPUT NORMALLY CLOSED NC INPUT FROM FACP OR ACCESS CONTROL DEVICE DC VOLTAGE INPUT FROM FACP SIGNALING OUTPUT OR ACCESS CONTROL DEVICE NC C NO DRY OUTPUT NC C NO POWER FAIL TRIGGER LED POWER ON LED TRI...

Page 6: ...STANDBY NC C NO POWER FAIL TRIGGER 1 2 3 4 5 POS DC OUTPUT ALARM NEG1 NEG2 NEG3 NEG4 NEG5 DC INPUT INPUT MOM5 TRIGGER 12VDC or 24VDC FROM POWER SUPPLY FROM FACP SIGNALING OUTPUT FACP EOL 2 2K EOL 2 2...

Page 7: ...MOM5C 7 Notes...

Page 8: ...Warranty Made in U S A IIMOM5C E22R MEMBER Enclosure Dimensions H x W x D 8 x 7 25 x 3 5 215 9mm x 190 5mm x 88 9mm 1 25 31 75mm 1 25 31 75mm 1 25 31 75mm 1 125 28 575mm 1 25 4mm 1 25 4mm 1 25 4mm 5 2...

Reviews: