Altronix Maximal11DV Manual Download Page 6

 

- 6 - 

Maximal11DV / Maximal33DV / Maximal55DV / Maximal75DV / Maximal77DV  Access Power Controllers (PTC) Installation Guide

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

  FACP Supervision: 

To ensure proper connection and operation of the Fire Alarm disconnect 

   

hookup. Please follow the appropriate procedure below:

 

Normally Open Input:

 

Placing a short between terminals marked [T] and [+ INP] will trigger the 

   

Fire Alarm Disconnect. Remove the short to reset.

 

Normally Closed Input:

 

Remove the wire from terminal marked [INP –] will trigger the Fire Alarm 

   

Disconnect. Replace the wire to terminal marked [INP –] to reset.

 

FACP Signal Circuit Input:

 

It is necessary to trigger the Fire Alarm System.

   

In all of the above scenarios the green TRG LED of the ACM8CBs will 

   

illuminate. All outputs selected for Fire Alarm Disconnect will activate 

   

releasing locking devices.

  

Note:

 All outputs [OUT 1 - OUT 8] must be in a normal (de-energized) 

   

condition prior to testing. When the unit is configured for Normally Open 

  

(Fig. 13, pg. 18)

 or Normally Closed 

(Fig. 15, pg. 18)

 latching operation, 

   

it is necessary to reset the Fire Alarm Disconnect by activating the 

   

Normally Closed reset switch.

  Output Voltage Test:

 

Under normal load conditions, the DC output voltage should be checked 

   

for proper voltage level 

(Power Supply Board Stand-by Battery 

   

Specifications, pg. 8).

  Battery Test:

 

Under normal load conditions check that the battery is fully charged, check 

   

specified voltage at the battery terminals and at the board terminals marked 

   

[+ BAT –] to ensure that there is no break in the battery connection wires.

  

Note:

  AL400XB2V, AL600XB220, and AL1012XB220 Power Supply 

   

 

Board maximum charge current is 0.7A. AL1024XB2V Power 

   

 

Supply Board maximum charge current is 3.6A.

   

Expected battery life is 5 years; however, it is recommended to change 

   

batteries within 4 years or less if necessary.

Power Supply Board LED Diagnostics:

LED

Power Supply Status

Red (DC)

Green (AC)

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery supplying power.

OFF

ON

No DC output. Short circuit or thermal overload condition.

OFF

OFF

No DC output. Loss of AC. Discharged battery.

Red (Bat)

Battery Status

ON

Normal operating condition.

OFF

Battery fail/low battery.

Access Power Controller LED Diagnostics:

LED

ON

OFF

LED 1- LED 8 (Red) Output relay(s) energized.

Output relay(s) de-energized.

Trg (Green)

FACP input triggered (alarm condition).

FACP normal (non-alarm condition).

Summary of Contents for Maximal11DV

Page 1: ...C protected outputs Maximal75DV Power Supply 1 12VDC 9 5A Power Supply 2 24VDC 9 7A Sixteen 16 PTC protected outputs Maximal77DV Power Supply 1 24VDC 9 7A Power Supply 2 24VDC 9 7A Sixteen 16 PTC prot...

Page 2: ...by Battery Specifications pg 8 Power Supply Board Output Voltage Settings pg 9 Access Power Controller Typical Application Diagram for each ACM8 pg 9 Maximal11DV Maximal33DV Maximal55DV Battery Hookup...

Page 3: ...VDC 2 7A 24VDC 2 7A 5 4A 24VDC 3 5A 24VDC 2 7A 6 2A Maximal33DV AL600XB220 AL600XB220 2 5A 16 3A 5A 250V 12VDC 5 5A 12VDC 5 5A 11A 12VDC 5 7A 24VDC 5 7A 11 4A 24VDC 5 5A 24VDC 5 7A 11 2A Maximal55DV A...

Page 4: ...and predrill holes in the wall to line up with the top three key holes in the enclosure Install three upper fasteners and screws in the wall with the screw heads protruding Place the enclosure s upper...

Page 5: ...alarm condition Jumper located next to TRG LED must be cut Fig 2b pg 8 and Fig 8 pg 14 9 FACP Dry form C output Fig 2a pg 9 FACP form C contacts can be use to trigger reporting or signaling devices T...

Page 6: ...e Fire Alarm Disconnect by activating the Normally Closed reset switch Output Voltage Test Under normal load conditions the DC output voltage should be checked for proper voltage level Power Supply Bo...

Page 7: ...ked BAT for 12VDC operation Fig 3 pg 10 Fig 5 pg 12 Use two 2 12VDC batteries wired in series for 24VDC operation Figs 3 5 pgs 10 12 Access Power Controller Terminal Identification Terminal Legend Fun...

Page 8: ...d position 12VDC 40AH N A 3 5A 0 5A 24VDC 40AH N A 2 7A 0 7A Maximal33DV AL600XB220 Refer to Fig 1a pg 9 for Switch SW1 location and position 12VDC 40AH N A 5 5A 5 5A 24VDC 40AH N A 5 5A 0 7A Maximal5...

Page 9: ...NO C Access Control Panel Output Relay FACP Fire Alarm Control Panel NC C NO COM OUTPUT 1 LED1 F1 NC C NO COM OUTPUT 2 IN GND 1 IN GND 2 IN GND 3 IN GND 4 IN GND 5 IN GND 6 IN GND 7 MAIN IN GND 8 LED2...

Page 10: ...D IN GND 1 2 3 4 5 6 7 8 INPUT TRIGGER 10A 250V INP T RET NO C NC FACP INTERFACE Power Control F1 F2 F3 F4 F5 F6 F7 F8 MAIN TRG FACP 1 2 3 4 1 2 3 4 O N O N 1 2 3 4 1 2 3 4 O N O N Optional Rechargeab...

Page 11: ...IN GND IN GND 1 2 3 4 5 6 7 8 INPUT TRIGGER 10A 250V INP T RET NO C NC FACP INTERFACE Power Control F1 F2 F3 F4 F5 F6 F7 F8 MAIN TRG FACP 1 2 3 4 1 2 3 4 O N O N 1 2 3 4 1 2 3 4 O N O N Optional 12VDC...

Page 12: ...C NO COM NC C NO COM NC C NO COM NC C NO COM IN GND IN GND IN GND IN GND IN GND IN GND IN GND IN GND 1 2 3 4 5 6 7 8 INPUT TRIGGER 10A 250V INP T RET NO C NC FACP INTERFACE Power Control F1 F2 F3 F4...

Page 13: ...uire different conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gau...

Page 14: ...ow Your specific application may require different conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections...

Page 15: ...r limited circuit wiring must enter and exit the cabinet through different conduits One such example of this is shown below Your specific application may require different conduit knockouts to be used...

Page 16: ...uire different conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gau...

Page 17: ...ATED POWER INPUT 12 OR 24 VAC OR VDC ACM8 POWER Fig 10 Optional hook up using two 2 isolated power supply inputs Only applicable on Maximal11DV CUT JUMPER FROM FACP OUTPUT CIRCUIT FACP OUTPUT EOL TRG...

Page 18: ...cont d N C RESET SWITCH N O TRIGGER INPUT JUMPER TRG NO C NC FACP Fig 13 Normally Open FACP Latching trigger input with reset JUMPER N C DRY TRIGGER INPUT TRG NO C NC FACP INTERFACE FACP Fig 14 Norma...

Page 19: ...Maximal11DV Maximal33DV Maximal55DV Maximal75DV Maximal77DV Access Power Controllers PTC Installation Guide 19 Notes...

Page 20: ...www altronix com e mail info altronix com Lifetime Warranty Made in U S A IIMaximal11DV 33DV 55DV 75DV 77DV Series G27U MEMBER 4 101 6mm 19 482 6mm 2 50 8mm 2 50 8mm 4 101 6mm 4 101 6mm 7 177 8mm 6 2...

Reviews: