Altronix Maximal11DV Manual Download Page 5

 

Maximal11DV / Maximal33DV / Maximal55DV / Maximal75DV / Maximal77DV  Access Power Controllers (PTC) Installation Guide 

- 5 -

 

(b)  Fail-Secure Switched Power outputs:

 

 

For Fail-Secure operation connect the positive (+) input of the access control devices to terminal marked 

 

 

[NO]. Connect the negative (–) input of the access control devices to terminal marked [COM].

6. 

Auxiliary Power outputs (unswitched):

 

Connect access control devices that require constant power to terminals marked [C] positive (+) and 

 

[COM] negative (–).

7. 

Input trigger options 

(Fig. 2, pg. 9)

:

 

(a)  Normally Open [NO] input trigger:

 

 

Inputs 1-8 are activated by normally open or open collector sink inputs. Connect access control panel 

 

 

outputs, keypads, push buttons, REX PIRs, etc. to terminals marked [IN] and [GND]. 

 

(b)  Open Collector Sink inputs:

 

 

Connect the access control panel open collector sink positive (+) to terminals marked [IN] and the 

 

 

negative (–) to terminals marked [GND].

8. 

Fire Alarm Interface options 

(Figs. 10-15, pg. 17-18)

 

A normally closed [NC] or normally open [NO] input trigger from a fire alarm control panel or a polarity 

 

reversal input from an FACP signaling circuit will affect selected outputs. To enable FACP Disconnect for 

 

an output turn the corresponding switch(es) [SW1-SW8] on each ACM8CB board OFF. To disable FACP 

 

disconnect for an output turn the corresponding switch(es) [SW1-SW8] on each ACM8CB board ON.

 

(a)  Normally Open [NO] input:

 

 

For non-latching hook-up refer to 

Fig. 12, pg. 17

. For latching hook-up refer to 

Fig. 13, pg. 18

.

 

(b)  Normally Closed [NC] input:

 

 

For non-latching hook-up refer to 

Fig. 14, pg. 18

. For latching hook-up refer to 

Fig. 15, pg. 18

.

 

(c)  FACP Signaling Circuit input trigger:

 

 

Connect the positive (+) and negative (–) from the FACP signaling circuit output to the terminals marked 

 

 

[+ INP –]. Connect the FACP EOL to the terminals marked [+ RET –] (polarity is referenced in an alarm 

 

 

condition). Jumper located next to TRG LED must be cut 

(Fig. 2b, pg. 8 and Fig. 8, pg. 14)

9. 

FACP Dry form “C” output 

(Fig. 2a, pg. 9)

:

 

FACP form “C” contacts can be use to trigger reporting or signaling devices. These contact switch

 

upon a fire alarm input trigger to the ACM8CB boards.

10. 

Stand-by Battery Connections

 

(Figs. 3-5, pgs. 10-12)

:

 

For Access Control applications batteries are optional. If batteries are not used a loss of AC will result in 

 

the loss of output voltage. Batteries must be lead acid or gel type. Connect one (1) 12VDC battery to the 

 

terminals marked [+ BAT –] for 12VDC operation 

(Figs. 3, 5, pgs. 10, 12)

. Use two (2) 12VDC batteries 

 

wired in series for 24VDC operation 

(Figs. 3-5, pgs. 10-12)

11. 

Battery and AC Supervision outputs 

(Figs. 3-5, pgs. 10-12)

:

 

It is required to connect supervisory trouble reporting devices to outputs marked [AC Fail, BAT FAIL] 

 

supervisory relay outputs marked [NC, C, NO] to appropriate visual notification devices. Use 22 AWG to 

 

18 AWG for AC Fail & Low/No Battery reporting. 

12. 

Installation of tamper switch (Not Included) 

(Figs. 3a, 4a, 5a, pgs. 10-12)

:

 

Mount UL Listed tamper switch (Honeywell Model 112 or equivalent) at the top of the enclosure. Slide 

 

the tamper switch bracket onto the edge of the enclosure approximately 2” from the right side. Connect 

 

tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting device. 

 

To activate alarm signal open the door of the enclosure.

13. 

Multiple power supply inputs

 (Fig. 2, pg. 9)

:

 

When using an additional external power supply, jumpers J1 and J2 located on corresponding ACM8CB 

 

boards must be cut 

(Fig. 2c, 2d, pg. 9, Fig. 10, pg. 17)

. Connect external access control power supply to 

 

the terminals marked [– C] 

(only applicable on Maximal11DV)

 

When using DC power supplies polarity must be observed. 

 

When using AC power supplies polarity needs not to be observed. 

(Fig. 2d, pg. 9). 

 

All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or 

 

equivalent substitute 

(Fig. 6a-9a, pgs. 13-16).

Summary of Contents for Maximal11DV

Page 1: ...C protected outputs Maximal75DV Power Supply 1 12VDC 9 5A Power Supply 2 24VDC 9 7A Sixteen 16 PTC protected outputs Maximal77DV Power Supply 1 24VDC 9 7A Power Supply 2 24VDC 9 7A Sixteen 16 PTC prot...

Page 2: ...by Battery Specifications pg 8 Power Supply Board Output Voltage Settings pg 9 Access Power Controller Typical Application Diagram for each ACM8 pg 9 Maximal11DV Maximal33DV Maximal55DV Battery Hookup...

Page 3: ...VDC 2 7A 24VDC 2 7A 5 4A 24VDC 3 5A 24VDC 2 7A 6 2A Maximal33DV AL600XB220 AL600XB220 2 5A 16 3A 5A 250V 12VDC 5 5A 12VDC 5 5A 11A 12VDC 5 7A 24VDC 5 7A 11 4A 24VDC 5 5A 24VDC 5 7A 11 2A Maximal55DV A...

Page 4: ...and predrill holes in the wall to line up with the top three key holes in the enclosure Install three upper fasteners and screws in the wall with the screw heads protruding Place the enclosure s upper...

Page 5: ...alarm condition Jumper located next to TRG LED must be cut Fig 2b pg 8 and Fig 8 pg 14 9 FACP Dry form C output Fig 2a pg 9 FACP form C contacts can be use to trigger reporting or signaling devices T...

Page 6: ...e Fire Alarm Disconnect by activating the Normally Closed reset switch Output Voltage Test Under normal load conditions the DC output voltage should be checked for proper voltage level Power Supply Bo...

Page 7: ...ked BAT for 12VDC operation Fig 3 pg 10 Fig 5 pg 12 Use two 2 12VDC batteries wired in series for 24VDC operation Figs 3 5 pgs 10 12 Access Power Controller Terminal Identification Terminal Legend Fun...

Page 8: ...d position 12VDC 40AH N A 3 5A 0 5A 24VDC 40AH N A 2 7A 0 7A Maximal33DV AL600XB220 Refer to Fig 1a pg 9 for Switch SW1 location and position 12VDC 40AH N A 5 5A 5 5A 24VDC 40AH N A 5 5A 0 7A Maximal5...

Page 9: ...NO C Access Control Panel Output Relay FACP Fire Alarm Control Panel NC C NO COM OUTPUT 1 LED1 F1 NC C NO COM OUTPUT 2 IN GND 1 IN GND 2 IN GND 3 IN GND 4 IN GND 5 IN GND 6 IN GND 7 MAIN IN GND 8 LED2...

Page 10: ...D IN GND 1 2 3 4 5 6 7 8 INPUT TRIGGER 10A 250V INP T RET NO C NC FACP INTERFACE Power Control F1 F2 F3 F4 F5 F6 F7 F8 MAIN TRG FACP 1 2 3 4 1 2 3 4 O N O N 1 2 3 4 1 2 3 4 O N O N Optional Rechargeab...

Page 11: ...IN GND IN GND 1 2 3 4 5 6 7 8 INPUT TRIGGER 10A 250V INP T RET NO C NC FACP INTERFACE Power Control F1 F2 F3 F4 F5 F6 F7 F8 MAIN TRG FACP 1 2 3 4 1 2 3 4 O N O N 1 2 3 4 1 2 3 4 O N O N Optional 12VDC...

Page 12: ...C NO COM NC C NO COM NC C NO COM NC C NO COM IN GND IN GND IN GND IN GND IN GND IN GND IN GND IN GND 1 2 3 4 5 6 7 8 INPUT TRIGGER 10A 250V INP T RET NO C NC FACP INTERFACE Power Control F1 F2 F3 F4...

Page 13: ...uire different conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gau...

Page 14: ...ow Your specific application may require different conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections...

Page 15: ...r limited circuit wiring must enter and exit the cabinet through different conduits One such example of this is shown below Your specific application may require different conduit knockouts to be used...

Page 16: ...uire different conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gau...

Page 17: ...ATED POWER INPUT 12 OR 24 VAC OR VDC ACM8 POWER Fig 10 Optional hook up using two 2 isolated power supply inputs Only applicable on Maximal11DV CUT JUMPER FROM FACP OUTPUT CIRCUIT FACP OUTPUT EOL TRG...

Page 18: ...cont d N C RESET SWITCH N O TRIGGER INPUT JUMPER TRG NO C NC FACP Fig 13 Normally Open FACP Latching trigger input with reset JUMPER N C DRY TRIGGER INPUT TRG NO C NC FACP INTERFACE FACP Fig 14 Norma...

Page 19: ...Maximal11DV Maximal33DV Maximal55DV Maximal75DV Maximal77DV Access Power Controllers PTC Installation Guide 19 Notes...

Page 20: ...www altronix com e mail info altronix com Lifetime Warranty Made in U S A IIMaximal11DV 33DV 55DV 75DV 77DV Series G27U MEMBER 4 101 6mm 19 482 6mm 2 50 8mm 2 50 8mm 4 101 6mm 4 101 6mm 7 177 8mm 6 2...