- 4 - 

MaxiFit11FE/13FE/33FE/35FE/37FE/55FE/75FE/77FE Expandable Power Systems Installation Guide

5.  Connect devices or Altronix sub-assembly modules to be powered to the terminals marked [– DC +] 

 

(Fig. 1h, pg. 5)

. For auxiliary device connection, this output will not be affected by

 

Low Power Disconnect or Fire Alarm Interface. Connect device to the terminals

 

marked [+ AUX –] 

(Fig. 1f, pg. 5). Refer to page 2 for non power-limited applications.

6.  For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result 

 in the loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel 

 

type. Connect battery to the terminals marked [– BAT + ] 

(Fig. 1g, pg. 5)

. Use two (2) 12VDC batteries

 

connected in series for 24VDC operation (battery leads included). Use batteries - Casil CL1270 (12V/7AH), 

 

CL12120 (12V/12AH), CL12400 (12V/40AH), CL12650 (12V/65AH) batteries or UL recognized BAZR2

 

batteries of an appropriate rating.

7.  Connect appropriate signaling notification devices to AC FAIL & BAT FAIL 

(Fig. 1b, pg. 5)

 supervisory

 

relay outputs.

8.  To delay AC reporting for 2 hrs., set DIP switch [AC Delay] to OFF position 

(Fig. 1c, pg. 5)

.

 

To delay AC reporting for 1 min., set DIP switch [AC Delay] to ON position 

(Fig. 1c, pg. 5)

.

 

Note: 

Must be set to ON position for Burglar Alarm Applications.

9.  To enable Fire Alarm Disconnect set DIP switch [Shutdown] to ON position. 

(Fig. 1c, pg. 5)

.

 

To disable Fire Alarm Disconnect set DIP switch [Shutdown] to OFF position. 

(Fig. 1c, pg. 5)

.

10.  Trigger terminals are end of a line resistor supervised (10k Ohms). Opening or shorting trigger terminals 

 

will cause [DC] output to shutdown 

(Fig. 1d, pg. 5)

.

11.  Place a jumper for non-latching FACP. A momentary short on these terminals resets FACP latching

 

[Trigger EOL Shutdown] 

(Fig. 1d, pg. 5)

.

12.  For Access Control Applications: mount UL Listed tamper switch (Altronix Model TS112 or equivalent) at 

 

the top of the enclosure. Slide tamper switch bracket onto the edge or the enclosure approx. 2” from the 

 

right side 

(Fig. 3a, pg. 7)

. Connect tamper switch wiring to the Access Control Panel input or the appropriate 

 

UL Listed reporting device.

13.  Please ensure that the cover is secured with the provided key lock.

Wiring:

Use 18 AWG or larger for all low voltage power connections.

Note:

 Take care to keep power-limited circuits separate from non power-limited wiring (120VAC, Battery).

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

Output Voltage Test:

  Under normal load conditions the DC output voltage should be checked for proper 

 

voltage level 

(MaxFitFE Configuration Chart, pg. 2).

Battery Test:

 

Under normal load conditions check that the battery is fully charged, check specified 

 

voltage at the battery terminals and at the board terminals marked [– BAT +] to 

 

ensure that there is no break in the battery connection wires.

Note:

 

Maximum charge current 1.54A.

Expected battery life is 5 years; however, it is recommended to change batteries within 4 years or less if necessary.

Summary of Contents for MAXIMAL FIT MaxFit11FE

Page 1: ...one ___________________ MaxFit FE Series Expandable Power Systems Models Include Installation Guide MaxFit11FE 12VDC 24VDC 4A 12VDC 24VDC 4A MaxFit13FE 12VDC 24VDC 4A 12VDC 24VDC 6A MaxFit33FE 12VDC 2...

Page 2: ...10 1 13 2 10 05 13 2 10 1 13 2 10 05 13 2 20 28 26 4 20 2 26 4 20 28 26 4 20 2 26 4 20 28 26 4 20 2 26 4 MaxFit13FE eFlow4NB eFlow6NB 4A 6A 1 1 2 7 5A 250V 7 5A 32V eFlow4NB 10A 32V eFlow6NB 730 eFlo...

Page 3: ...VAC present AC input and DC output LED indicators Short circuit and overload protection Enclosure accommodates up to four 4 12VDC 12AH batteries Enclosure dimensions H x W x D 20 5 x 16 5 x 6 25 520 7...

Page 4: ...5 To disable Fire Alarm Disconnect set DIP switch Shutdown to OFF position Fig 1c pg 5 10 Trigger terminals are end of a line resistor supervised 10k Ohms Opening or shorting trigger terminals will ca...

Page 5: ...Stand by battery is supplying power OFF ON No DC output OFF OFF Loss of AC Discharged or no stand by battery No DC output Red Bat Battery Status ON Normal operating condition OFF Battery fail low bat...

Page 6: ...ower limited Fig 1b pg 5 BAT FAIL NC C NO Indicates low battery condition e g connect to alarm panel Relay normally energized when DC power is present Contact rating 1A 30VDC A removed battery is repo...

Page 7: ...r Switch Optional Rechargeable Stand by Battery for UL294 Applications Note 12V batteries are required for ULC S319 installations Input 120VAC 60Hz non power limited Supervisory Connections Aux Output...

Page 8: ...5 31 8mm 8 75 222 3mm 8 75 222 3mm 1 50 38 1mm 1 50 38 1mm 6 25 158 8mm 1 25 31 8mm 1 25 31 8mm 7 00 177 8mm 7 00 177 8mm 7 00 177 8mm 7 00 177 8mm 1 25 31 8mm 1 25 31 8mm 16 50 419 1mm 1 25 31 8mm 0...

Reviews: