Altronix LINQ8ACM Installation And Programming Manual Download Page 8

 

- 8 - 

LINQ8ACM(CB)

Tango1B - PoE Driven Power Supply with Lithium Battery Backup

Overview: 

Altronix Tango1B Voltage Regulator converts an IEEE802.3bt PoE input into a regulated 24VDC and/or 12VDC 

output up to 65W. It eliminates the need for a high voltage power supply inside of an enclosure. The Tango 8-pin 
connector allows for stacking with LINQ8ACM(CB), saving valuable enclosure space. Tango1B is designed to 
support a single 12V LiFePO4 (Lithium Iron Phosphate) battery for high storage and charge/discharge cycle 

life reliability. Refer to Tango1B Installation Guide Rev. TANGO-071119.

Specifications:

Connecting LINQ8ACM(CB) to Tango1B:

1. Mount Tango1B in the desired location/enclosure. 
2. Plug-in male 8-pin connector to female 8-pin receptacle on Tango1B board. 
3. Fasten standoffs. Use metal standoff over mounting hole with star pattern. 
4. Align 8-pin male connector with female receptacle of LINQ8ACM(CB), then mount. 
5. Connect 24VDC power supply to terminal marked [+ PWR1 –] of LINQ8ACM(CB). 
  Thus Input 1 of LINQ8ACM(CB) is 24VDC from power supply and Input 2 is determined by 
  Tango1B’s settings (12VDC or 12VDC). 
6. Complete steps 4-10 (pgs. 3-4).

LINQ8ACM/

LINQ8ACMCB

Tango1B

Tango1B

Fig. 4

Ethernet Input:

•  802.3bt PoE up to 90W or 802.3at up to 30W

  or 802.3af up to 15W.

Power Output 

(when using 802.3bt 90W)

:

•  12VDC up to 5.4A (65W)

  and/or 24VDC up to 2.7A (65W).

  Combined output not to exceed 65W.

• 

When charging batteries:

  12VDC up to 4.6A (55W) and/or

  24VDC up to 2.3A (55W)

  Combined output not to exceed 55W.

Ethernet Output:

• Pass-through Ethernet Port (data only).

• 100/1G

Battery:

•  12VDC battery charger for Lithium Iron

  Phosphate Battery (LiFeP04 only) .

•  Unique technology allows for single battery

  to backup 12VDC and/or 24VDC systems.

Battery 

(cont’d)

:

•  Low power shutdown. Shuts down DC output 

  terminals if battery voltage drops below 80% of 

  nominal. Prevents deep battery discharge. 

Supervision:

•  Loss of PoE Input.

•  Battery Supervision.

Visual Indicators:

•  Input indicates input voltage is present.

•  Battery status indicates battery trouble condition.

•  PoE Class indicator.

•  Supervision PoE Fail or BAT Fail.

Additional Features:

•  Short circuit and overload protection.

Board Dimensions 

(approximate L x W x H)

:

  7.625” x 4.125” x 1.25”

  (193.7mm x 104.8mm x 32.0mm)

Summary of Contents for LINQ8ACM

Page 1: ...r Controllers Installation and Programming Manual Models include LINQ8ACM Network Access Power Controller Eight 8 Fused Outputs LINQ8ACMCB Network Access Power Controller Eight 8 PTC Outputs Please be...

Page 2: ...1 12 or 24 VDC from eFlow series power supply Input 2 a 12 or 24 VDC from eFlow series power supply b 5 or 12 VDC from VR6 voltage regulator Dual Input Option 2 24 and 12 VDC from Tango1B PoE Driven P...

Page 3: ...connect is triggered Flashing Blue Heartbeat LED indicates network connection Individual OUT1 OUT8 Red LEDs indicate outputs are triggered Individual Voltage LEDs indicate 12VDC Green or 24VDC Red Env...

Page 4: ...arity connect the voltage input trigger wires and the supplied 10K resistor to terminals marked INP1 to INP8 9 Fire Alarm Interface Options program fire alarm interface options via LINQ software A nor...

Page 5: ...lly Closed NC Open Collector Sink or Wet Input Triggers Tamper Tamper Switch Input AC NC C Connect appropriate signaling notification devices to the terminals to report AC fail BAT NC C Connect approp...

Page 6: ...Ratings Input Voltage and Source Output Voltage Rating 5VDC from VR6 regulator 5VDC 12V from VR6 regulator 12VDC 12VDC from external power supply 11 7 12VDC 24VDC from external power supply 23 7 24VD...

Page 7: ...over mounting hole with star pattern 4 Align 8 pin male connector with female receptacle of LINQ8ACM CB then mount 5 Connect 24VDC power supply to terminal marked PWR1 of LINQ8ACM CB Thus Input 1 of L...

Page 8: ...ACM CB is 24VDC from power supply and Input 2 is determined by Tango1B s settings 12VDC or 12VDC 6 Complete steps 4 10 pgs 3 4 LINQ8ACM LINQ8ACMCB Tango1B Tango1B Fig 4 Ethernet Input 802 3bt PoE up t...

Page 9: ...PWR1 PWR2 PWR1 PWR2 PWR1 PWR2 PWR1 OUT1 OUT7 OUT2 OUT3 OUT4 OUT5 OUT6 OUT8 NC C NO BAT AC Tamper NC C NO INP1 INP2 INP3 INP4 INP5 INP6 INP7 INP8 A C B A T F A C P B e a t O u t1 O u t2 O u t3 O u t4...

Page 10: ...e effect after the server is rebooted Click OK DHCP a After selecting DHCP in the IP Address Method field click the button labeled Submit Network Settings A dialog box will display New network setting...

Page 11: ...stamp the system log and email alerts 1 Click on the Status tab to access the status page 2 Click the time and date in the upper left a dialog box will open 3 Click on SYNC DATE AND TIME A Hardware Se...

Page 12: ...either of these limits are exceeded an alert message and or email notification will be generated 4 Click on the button labeled Submit to save the settings Output Current Calibration During the initial...

Page 13: ...remote access and monitoring The default inbound port setting is 80 HTTP is not encrypted and unsecure Even though HTTP can be used for remote access it is recommended primarily for use with LAN conne...

Page 14: ...2 Locate the new certificate file 3 Upload the certificate file 4 Under Key upload click on Select Key File 5 Locate the new certificate file 6 Upload the Key file 7 Click on the button labeled Submit...

Page 15: ...he EOL position Latching Single Reset COM F R GND GND C F R EOL RST NC FACP COM F R GND GND C F R EOL RST NC FACP Jumper Jumper COM F R GND GND C F R EOL RST NC FACP COM F R GND GND C F R EOL RST NC F...

Page 16: ...Jumper EOL Fig 10 Polarity reversal input from FACP signaling circuit output polarity is referenced in alarm condition Latching COM F R GND GND C F R EOL RST NC FACP EOL N O Switch Hook Up Diagrams CO...

Reviews: