- 8 -
eFlow6N Series Installation Guide
Battery Connection
non power-limited
Battery & AC
Supervision Circuit
(power-limited)
J1
AC Delay
NC C NO NC
C NO
AC FAIL
BAT FAIL
TRIGGER
AC
DC
AC1
EOL
NO
GN
D
SUPERVISED
RESET
+AUX-
- BAT +
- DC +
L G
N
OFF - 24V
ON - 12V
ON
power-
limited
PD8UL/PD8ULCB
PD16W/
PD16WCB
Green
Lead
120VAC power mains
non power-limited
DC Output to Devices*
(refer to Fig. 3a, 3b, 4a, 4b
for board configuration, pg. 7)
Optional Rechargeable Stand-by
Battery for UL294 Applications.
Note: 12V batteries are required for UL603,
UL1481 and Canadian installations.
Optional Rechargeable Stand-by
Battery for UL294 Applications.
Note: 12V batteries are required for UL603,
UL1481 and Canadian installations.
CAUTION: When power supply board is set for 12VDC use only one (1) 12VDC stand-by battery.
Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.
7AH Rechargeable batteries are the largest batteries that can fit in this enclosure.
A UL Listed external battery enclosure must be used if using 12AH, 40AH or 65AH batteries.
Switch Detail
ON
1
Switch On - 12V
Switch Off - 24V
Fig. 5 -
eFlow6N Configuration
Tamper Switch
(included)
To Access Control Panel or
UL Listed Reporting Device
Edge of
Enclosure
Enclosure
* Outputs are non power-limited:
eFlow6N, eFlow6N8, eFlow6N16.
Outputs are Class 2 power-limited:
eFlow6N8D, eFlow6N16D.