background image

 

- 2 - 

eFlow6N Series Installation Guide

Overview:

Altronix eFlow6N power supply/chargers convert a 120VAC / 60Hz input to a 12VDC or 24VDC nominal output

(see Power Supply Configuration Reference Chart and Specifications)

.

eFlow6N Series Power Supply Configuration Reference Chart:

Altronix  Model Number

Nominal DC Outputs

Maximum Supply Current for Main and Aux. Outputs (A) Input Rating: 120VAC, 60Hz

Input Fuse Rating

Battery Fuse Rating

Ripple Voltage (mV)

Under low battery condition

Power Distribution Modiule

Number of Outputs

Fused Outputs Ratings

PTC Protected Class 2 Power-Limited  Auto-Resettable Outputs Ratings Accommodates up to 7AH Batteries Accommodates up to 12AH Batteries

[DC]

[AUX]

12VDC Output Range (V)

24VDC Output Range (V)

12VDC Output Range (V)

24VDC Output Range (V)

eFlow6N

10.0-

13.2

20.19-

26.4

10.03-

13.2

20.19-

26.4

6

3.5A

5A/

250V

10A/

32V

910

N/A

1

P

eFlow6NX

P

eFlow6N8

10.0-

13.2

20.19-

26.4

10.03-

13.2

20.19-

26.4

6

3.5A

5A/

250V

10A/

32V

910

PD8UL

8

2.5A

P

eFlow6NX8

2.5A

P

eFlow6N8D

9.78-

13.2

20.0-

26.4

10.03-

13.2

20.19-

26.4

6

3.5A

5A/

250V

10A/

32V

910

PD8ULCB

8

2A

P

eFlow6NX8D

2A

P

eFlow6N16

10.0-

13.2

20.19-

26.4

10.03-

13.2

20.19-

26.4

6

3.5A

5A/

250V

10A/

32V

910

PD16W

16

2.5A

P

eFlow6NX16

2 - PD8UL

2.5A

P

eFlow6N16D

9.78-

13.2

20.0-

26.4

10.03-

13.2

20.19-

26.4

6

3.5A

5A/

250V

10A/

32V

910

PD16WCB

16

2A

P

eFlow6NX16D

2 - PD8ULCB

2A

P

The following units provide non power-limited outputs: eFlow6N, eFlow6NX, eFlow6N8, eFlow6NX8, eFlow6N16, and eFlow6NX16.

The following units provide Class 2 power-limited outputs: eFlow6N8D, eFlow6NX8D, eFlow6N16D, and eFlow6NX16D.

If a power-limited output is required in the end-product application, the DC output from the power supply must be connected to a 

separately Listed control unit or accessory board that provides power-limited outputs. The product(s) providing the power-limited 

output(s) must be listed as appropriate for the particular end-product application (fire alarm, burglar alarm, access control), and 

wired in accordance with the products installation instructions. Class 1 wiring methods, separation of circuits, and proper fire-

rated enclosures all must be considered when connecting the DC output of the power supply to the end-product devices. The 

auxiliary output of these units are power-limited.

UL Listings for US Installations:

UL 294, 7th edition

 - UL Listed for Access Control System Units.

 

Access Control Performance Levels: 

  Destructive Attack - I; Endurance - I; Line Security - I; 

  Stand-by Power: 7AH - I, 12AH - I, 40AH/65AH - IV.

UL 603

 - UL Listed for Power Supplies for Use with Burglar-Alarms Systems.

UL 1481

 - UL Listed for Power Supplies for Fire Protective Signaling Systems.

UL Listings for Canadian Installations:

ULC-S318-96 - Power Supplies for Burglar Alarm Systems. Also suitable for Access Control.

California State Fire Marshal

 

European Conformity

Factory Mutual Approved (eFlow6N and eFlow6NX only).

Altronix Corp.

140 58th St. Brooklyn, NY

Summary of Contents for eFlow6N

Page 1: ...VDC Eight 8 PTC Protected Class 2 Power Limited Outputs eFlow6N16D eFlow6NX16D 6A 12VDC or 24VDC Sixteen 16 PTC Protected Class 2 Power Limited Outputs eFlow6N Series Power Supply Chargers Models Incl...

Page 2: ...The following units provide non power limited outputs eFlow6N eFlow6NX eFlow6N8 eFlow6NX8 eFlow6N16 and eFlow6NX16 The following units provide Class 2 power limited outputs eFlow6N8D eFlow6NX8D eFlow6...

Page 3: ...can be seen through the LED lens on the door of the enclosure Use 14 AWG or larger for all power connections Secure green wire lead to earth ground Keep power limited wiring separate from non power l...

Page 4: ...Delay to OFF position Fig 1c pg 6 To delay AC reporting for 1 min set DIP switch AC Delay to ON position Fig 1c pg 6 Note Must be set to ON position for Burglar Alarm Applications 9 To enable Fire Ala...

Page 5: ...mally closed from an FACP output circuit power limited input Fig 1d pg 6 NO GND RESET FACP interface latching or non latching power limited Fig 1e pg 6 AUX Auxiliary Class 2 power limited output rated...

Page 6: ...e input of a UL Listed Burglar Alarm or Access Control Panel The following figure shows the circuitry needed for local annunciation Fig 2 Battery trouble indication For Canadian use a red indicating l...

Page 7: ...ses with the same type and rating 3 5A 250V N COMMON POWER OUTPUTS P FUSED POWER OUTPUTS 1 2 3 4 5 6 7 8 D1 INPUT R1 LED DC Output to devices 1P 8P Power Outputs 1N 8N Common Outputs From Power Supply...

Page 8: ...argeable Stand by Battery for UL294 Applications Note 12V batteries are required for UL603 UL1481 and Canadian installations CAUTION When power supply board is set for 12VDC use only one 1 12VDC stand...

Page 9: ...ade employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods For Canadian...

Page 10: ...4 Applications Note 12V batteries required for ULC S319 installations CAUTION When power supply board is set for 12VDC use only one 1 12VDC stand by battery Keep power limited wiring separate from non...

Page 11: ...de employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods For Canadian i...

Page 12: ...electric 0 12 50 2412 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2451 Photoelectric 0 10 39 2451TH with B402B Base Photoelectric 0 10 39 2W MOD Loop Test Maintenance Mod 30 50 4W B 12 24...

Page 13: ...6mm 1 40 35 6mm 1 40 35 6mm 1 40 35 6mm 4 85 123 2mm 4 85 123 2mm 3 25 82 6mm 0 75 19 1mm 0 75 19 1mm 11 0 279 4mm 12 5 317 5mm 1 20 30 5mm 1 20 30 5mm 0 9375 23 8mm 0 9375 23 8mm 5 10 129 5mm 1 40 35...

Page 14: ...34 9mm 1 125 28 6mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 4 5 114 3mm 4 5 114 3mm 1 25 31 8mm 1 25 31 8mm 0 79 20 1mm 0 91 23 1mm 0 91 23 1mm 15 5 393 7mm 1 1 27 9mm 1 1 27 9mm 1 1 27 9mm 12...

Page 15: ...mote control of up to 2 two Altronix eFlow power output s via LAN and or WAN Monitor real time diagnostics DC output voltage output current AC battery status service input trigger state change output...

Page 16: ...6A 6A 1 5A 6A Over 4 Hours 6A Battery Backup Built in charger for sealed lead acid or gel type batteries Maximum charge current 1 54A Automatic switch over to stand by battery when AC fails Transfer...

Reviews: