eFlow4NV Series Installation Guide 

- 3 -

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, The Canadian 

Electrical Code, Part 1 and with all local codes and authorities having jurisdiction. The product must be located 

indoors within the protected premises. 

1.  Mount unit in desired location. Mark and predrill holes in the wall to line up with the top two keyholes in 

 

the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the 

 

enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower two 

 

holes. Remove the enclosure. Drill the lower holes and install the two fasteners. Place the enclosure’s upper 

 

keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws 

 

(Enclosure Dimensions, pgs. 11-12)

. Secure enclosure to earth ground. 

2.  Set desired DC output voltage by setting SW1 to the appropriate position on the power supply board 

 

(Fig. 1i, pg. 5)

.

3.  Connect unswitched AC power (220VAC 50/60Hz) to terminals marked [L, N] 

(Fig. 1a, pg. 5)

 

Use 14 AWG or larger for all power connections. Secure green wire lead to earth ground lug. 

 

Keep power-limited wiring separate from non power-limited wiring (220VAC, 50/60Hz Input, 

 

Battery Wires). Minimum 0.25” spacing must be provided.

 

CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or 

 

servicing equipment. There are no user serviceable parts inside. Refer installation and servicing to 

 

qualified service personnel.

 

For Fire Alarm applications the outputs are “Special Applications” only, see list 

(refer to Appendix A, pg. 12)

4.  Measure output voltage before connecting devices. This helps avoiding potential damage.

5.  Connect devices to be powered:

 

a.  For eFlow4NV/eFlow4NXV connect devices to terminals marked [– DC +] (

Fig. 1h, pg. 5

). 

 

b.  For other Power Distribution Models connect devices to be powered to terminal pairs 1 to 8 marked  

 

  [1P & 1N] through [8P & 8N] (

Fig. 3a & 3b, pg. 6

) carefully observing correct polarity.

 

For auxiliary device connection this output will not be affected by Low Power Disconnect or Fire Alarm 

 

Interface. Connect device to terminals marked [+ AUX –] 

(Fig. 1f, pg. 5).

Input:

• 220VAC (working range 198VAC - 256VAC), 

 50/60Hz. 

Output:

•  For output voltage and supply current refer to

 

  eFlow4NV series Power Supply Configuration

  Reference Chart, pg. 2

.

•  Auxiliary output rated @ 1A (unswitched).

•  Overvoltage protection.

Fuse Ratings:

•  Refer to

 eFlow4NV Series Power Supply 

  Configuration Reference Chart, pg. 2.

Battery Backup:

•  Built-in charger for sealed lead acid or 

  gel type batteries.

•  Maximum charge current 1.54A.

•  Automatic switch over to stand-by battery when 

  AC fails. Transfer to stand-by battery power is 

  instantaneous with no interruption.

Fire Alarm Disconnect:

•  Supervised Fire Alarm disconnect (latching or non-

  latching) 10K EOL resistor. Operates on a normally

  open (NO) or normally closed (NC) trigger.

Supervision:

•  AC fail supervision (form “C” contacts).

•  Battery fail and presence supervision 

  (form “C” contacts).

•  Low power shutdown. Shuts down DC output 

  terminals if battery voltage drops below 71-73% for 

  12V units and 70-75% for 24V units (depending on 

  the power supply). Prevents deep battery discharge.

Visual Indicators:

•  Green AC Power LED indicates 220VAC present.

•  AC input and DC output LED indicators.

Additional Features:

•  Short circuit and overload protection.

•  Unit is complete with power supply, enclosure,

  battery leads, and cam lock. 

Enclosure Dimensions 

(approximate H x W x D)

:

eFlow4NV, eFlow4N8V, eFlow4N8DV:

  13.5” x 13” x 3.25”

  (342.9mm x 330.2mm x 82.6mm)

eFlow4NXV, eFlow4NX8V, eFlow4NX8DV:

  15.5” x 12” x 4.5”

  (393.7mm x 304.8mm x 114.3mm)

Specifications:

Summary of Contents for eFlow4N8D

Page 1: ...DC or 24VDC Eight 8 Fused Outputs eFlow4N8DV eFlow4NX8DV 4A 12VDC or 24VDC Eight 8 PTC Outputs Installation Guide Rev 4NVRP052213 More than just power TM Installing Company ________________ Service Re...

Page 2: ...C Output Range V 24VDC Output Range V eFlow4NV 10 1 13 2 20 28 26 4 10 05 13 2 20 2 26 4 4A 2 1A 5A 250V 7 5A 32V 730 N A 1 P eFlow4NXV P eFlow4N8V 10 1 13 2 20 28 26 4 10 05 13 2 20 2 26 4 4A 2 1A 5A...

Page 3: ...helps avoiding potential damage 5 Connect devices to be powered a For eFlow4NV eFlow4NXV connect devices to terminals marked DC Fig 1h pg 5 b For other Power Distribution Models connect devices to be...

Page 4: ...5 12 For Access Control Applications mount tamper switch Altronix Model TS112 or equivalent at the top of the enclosure Slide tamper switch bracket onto the edge or the enclosure approx 2 from the rig...

Page 5: ...energized when DC power is present Contact rating 1A 30VDC A removed battery is reported within 5 minutes Battery reconnection is reported within 1 minute power limited Fig 1b pg 5 BAT Stand by batte...

Page 6: ...CATING LAMP Power Distribution Module s Fig 3a PD8 Power Distribution Board Fig 3b PD8CB Power Distribution Board N COMMON POWER OUTPUTS P FUSED POWER OUTPUTS 1 2 3 4 5 6 7 8 D1 INPUT R1 LED DC Output...

Page 7: ...d Lug Optional Rechargeable Stand by Battery Optional Rechargeable Stand by Battery CAUTION When power supply board is set for 12VDC use only one 1 12VDC stand by battery Keep power limited wiring sep...

Page 8: ...use of conduit is optional All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional battery enclosure must be mounted adjacent to th...

Page 9: ...D8CB 220VAC power mains Ground Lug CAUTION When power supply board is set for 12VDC use only one 1 12VDC stand by battery Keep power limited wiring separate from non power limited Use minimum 0 25 spa...

Page 10: ...s use of conduit is optional All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional battery enclosure must be mounted adjacent to...

Page 11: ...35 6mm 1 40 35 6mm 1 40 35 6mm 4 85 123 2mm 4 85 123 2mm 3 25 82 6mm 0 75 19 1mm 0 75 19 1mm 11 0 279 4mm 12 5 317 5mm 1 20 30 5mm 1 20 30 5mm 0 9375 23 8mm 0 9375 23 8mm 5 10 129 5mm 1 40 35 6mm 5 10...

Page 12: ...4 615 117 2mm 4 615 117 2mm 1 5 38 1mm 1 5 38 1mm 4 615 117 2mm 4 615 117 2mm 1 75 44 5mm 1 75 44 5mm 1 375 34 9mm 1 125 28 6mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 4 5 114 3mm 4 5 114 3mm 1...

Page 13: ...TB Photoelectric 0 12 50 2412 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2451 Photoelectric 0 10 39 2451TH with B402B Base Photoelectric 0 10 39 2W MOD Loop Test Maintenance Mod 30 50 4W...

Page 14: ...emote control of up to 2 two Altronix eFlow power output s via LAN and or WAN Monitor real time diagnostics DC output voltage output current AC battery status service input trigger state change output...

Page 15: ...otes Altronix is not responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8181 fax 718 567 9056 website www altronix com e mail info altronix com Lifetime...

Page 16: ...4A Over 4 Hours 4A Battery Backup Built in charger for sealed lead acid or gel type batteries Maximum charge current 1 54A Automatic switch over to stand by battery when AC fails Transfer to stand by...