eFlow4NV Series Installation Guide
- 5 -
Terminal Identification:
Power Supply/Charger
Terminal Legend
Function/Description
L, N
Connect 220VAC 50/60Hz to these terminals: L to hot, N to neutral (non power-limited)
(Fig. 1a, pg. 5)
.
– DC +
12VDC or 24VDC nominal @ 4A continuous output (power-limited output)
(Fig. 1h, pg. 5)
.
Trigger EOL
Supervised
Fire Alarm Interface trigger input from a short or FACP. Trigger inputs can be normally open,
normally closed from an FACP output circuit (power-limited input)
(Fig. 1d, pg. 5)
.
NO, GND RESET
FACP interface latching or non-latching (power-limited)
(Fig. 1e, pg. 5)
.
+ AUX –
Auxiliary Class 2 power-limited output rated @ 1A (unswitched)
(Fig. 1f, pg. 5)
.
AC Fail
NC, C, NO
Indicates loss of AC power, e.g. connect to audible device or alarm panel.
Relay normally energized when AC power is present.
Contact rating 1A @ 30VDC (power-limited)
(Fig. 1b, pg. 5)
.
Bat Fail
NC, C, NO
Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized
when DC power is present. Contact rating 1A @ 30VDC.
A removed battery is reported within 5 minutes.
Battery reconnection is reported within 1 minute (power-limited)
(Fig. 1b, pg. 5)
.
– BAT +
Stand-by battery connections. Maximum charge current 1.54A (non power-limited)
(Fig. 1g, pg. 5)
.
Power Distribution Module
Terminal Legend
PD8/PD8CB
Function/Description
1P to 8P
Positive DC power outputs.
1N to 8N
Negative DC power outputs.
Fig. 1 -
eFlow4NV Board configuration
L
G
N
NC C NO
NC C NO
BAT FAIL
AC FAIL
---
DC
+
AC
AC1
DC
---
BA
T
+
+ AUX –
TRIGGER EOL
SUPERVISED
5A 250V
5A 250V
7.5A 32V
7.5A
NO GND
RESET
enable
disable
1 min.
2 hr.
AC DELAY SHUTDOWN
O
N
1a
1b
1g
1h
1e 1f
1d
1c
1i
OFF
---
24V
ON
---
12
V
ON
––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
Trouble/Time Limited Warning of Stand-by Batteries:
Time Limited Warning circuit must be connected for local or remote annunciation with an Amber or Red LED to
indicate DC Trouble (low battery, loss of battery or when 95% of the stand-by battery has been depleted). Connect
the circuit to the Batt Fail relay contacts to an appropriate input of a Burglar Alarm or Access Control Panel. The
following figure shows the circuitry needed for local annunciation.