background image

 

eFlow104NV Series 

- 3 -

Specifications:

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, 
The Canadian Electrical Code, Part 1 and with all local codes and authorities having jurisdiction. 
Product is intended for indoor use only. 
1.  Mount unit in desired location. Mark and predrill holes in the wall to line up with the top two keyholes in 
 

the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the 

 

enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower two 

 

holes. Remove the enclosure. Drill the lower holes and install the two fasteners. Place the enclosure’s upper 

 

keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws 

 

(Enclosure Dimensions, pgs. 11-12). Secure enclosure to earth ground. 

2.  Connect unswitched AC power (220VAC, 50/60Hz) to terminals marked [L, N] (Fig. 1a, pg. 5)
 

Use 14 AWG or larger for all power connections. Secure green wire lead to earth ground lug. 

 

Keep power-limited wiring separate from non power-limited wiring (220VAC 50/60Hz Input, 

 

Battery Wires). Minimum 0.25” spacing must be provided.

 

CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or 

 

servicing equipment. There are no user serviceable parts inside. Refer installation and servicing to 

 

qualified service personnel. 

 

For Fire Alarm applications the outputs are “Special Applications” only, see list (refer to Appendix A, pg. 12)

3.  Measure output voltage before connecting devices. This helps avoiding potential damage.
4.  Connect devices to be powered:
 

a.  For eFlow104NV/eFlow104NXV connect devices to terminals marked [– DC +] (Fig. 1h, pg. 5). 

 

b.  For other Power Distribution Models connect devices to be powered to terminal pairs 1 to 8 marked

 

 

[1P & 1N] through [8P & 8N] (Fig. 3a & 3b, pg. 6) or 1 to 16 marked [1P & 1N] through [16P & 16N]

 

 

(Fig. 4a & 4b, pg. 6) carefully observing correct polarity.

 

For auxiliary device connection: this output will not be affected by Low Power Disconnect or Fire Alarm 

 

Interface. Connect device to terminals marked [+ AUX –] (Fig. 1f, pg. 5).

5.  For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result 
 

in the loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel 

 

type. Connect battery to terminals marked [– BAT + ] (Fig. 1g, pg. 5). Use two (2) 12VDC batteries 

 

connected in series for 24VDC operation (battery leads included). Use batteries - Casil CL1270 

 

(12V/7AH), CL12120 (12V/12AH), CL12400 (12V/40AH), CL12650 (12V/65AH) batteries or BAZR2 

 

batteries of an appropriate rating.

Input:

•  220VAC (working range 198VAC - 256VAC), 
 50/60Hz. 

Output:

•  For output voltage and supply current refer to 
  eFlow104NV Series Power Supply Configuration 
  Reference Chart, pg. 2
.
•  Auxiliary output rated @ 1A (unswitched).
•  Overvoltage protection.

Battery Backup:

•  Built-in charger for sealed lead acid or 
  gel type batteries.
•  Maximum charge current 1.54A.
•  Automatic switch over to stand-by battery 
  when AC fails. Transfer to stand-by battery power 
  is instantaneous with no interruption.

Fire Alarm Disconnect:

•  Supervised Fire Alarm disconnect (latching or non-
  latching) 10K EOL resistor. Operates on a normally
  open (NO) or normally closed (NC) trigger.

Supervision:

•  AC fail supervision (form “C” contacts).
•  Battery fail and presence supervision 
  (form “C” contacts).

Supervision 

(cont’d)

:

•  Low power shutdown. Shuts down DC output 
  terminals if battery voltage drops below 70-75% 
  (depending on the power supply). 
  Prevents deep battery discharge.

Fuse Ratings:

•  Refer to eFlow104NV Series Power Supply 
  Configuration Reference Chart, pg. 2.

Visual Indicators:

•  Green AC Power LED indicates 220VAC present.
•  AC input and DC output LED indicators.

Additional Features:

•  Short circuit and overload protection.
•  Unit is complete with power supply, enclosure,
  battery leads, and cam lock. 

Enclosure Dimensions 

(approximate H x W x D)

:

eFlow104NV, eFlow104N8V, eFlow104N8DV,
eFlow104N16V, eFlow104N16DV:
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.6mm)
eFlow104NXV, eFlow104NX8V, eFlow104NX8DV, 
eFlow104NX16V, eFlow104NX16DV:
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)

Summary of Contents for eFlow104N16DV

Page 1: ..._____ Address ____________________________________________________ Phone ______________________ eFlow104NV eFlow104NXV 10A 24VDC eFlow104N8V eFlow104NX8V 10A 24VDC Eight 8 Fused Outputs eFlow104N16V e...

Page 2: ...ange V eFlow104NV 20 17 26 4 20 28 26 4 10A 2 7A 6 3A 250V 15A 32V 700 N A 1 P eFlow104NXV P eFlow104N8V 20 17 26 4 20 28 26 4 10A 2 7A 6 3A 250V 15A 32V 700 PD8 8 2 5A P eFlow104NX8V 2 5A P eFlow104N...

Page 3: ...y For auxiliary device connection this output will not be affected by Low Power Disconnect or Fire Alarm Interface Connect device to terminals marked AUX Fig 1f pg 5 5 For Access Control applications...

Page 4: ...wiring to the Access Control Panel input or the appropriate reporting device Wiring Use 18 AWG or larger for all low voltage power connections Note Take care to keep power limited circuits separate f...

Page 5: ...is present Contact rating 1A 30VDC A removed battery is reported within 5 minutes Battery reconnection is reported within 1 minute power limited Fig 1b pg 5 BAT Stand by battery connections Maximum ch...

Page 6: ...2 3 4 5 6 7 8 D1 INPUT R1 LED From Power Supply Board Factory Installed Replace fuses with the same type and rating 3 5A 250V DC Output to devices 1P 8P Power Outputs 1N 8N Common Outputs N COMMON POW...

Page 7: ...AC Supervision Circuit Battery Connections Keep power limited wiring separate from non power limited Use minimum 0 25 spacing 7AH Rechargeable batteries are the largest batteries that can fit in this...

Page 8: ...ptional All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional battery enclosure must be mounted adjacent to the power supply Note...

Page 9: ...eries are the largest batteries that can fit in this enclosure An external battery enclosure must be used if using the 40AH or 65AH batteries DC Output to devices refer to Fig 3a 3b for board configur...

Page 10: ...tional All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional battery enclosure must be mounted adjacent to the power supply Note...

Page 11: ...342 9mm x 330 2mm x 82 6mm 1 40 36mm 1 40 36mm 4 85 123mm 4 85 123mm 1 40 36mm 1 40 36mm 5 10 130mm 5 10 130mm 13 0 330mm 5 10 130mm 6 5625 167mm 1 20 31mm 1 20 31mm 1 20 31mm 3 25 83mm 3 25 83mm 3 25...

Page 12: ...mm 1 25 31 75mm 1 25 31 75mm 1 1 27 94mm 1 1 27 94mm 0 79 20 06mm 1 1 27 94mm 0 91 23 114mm 0 91 23 114mm 1 375 34 925mm 1 125 28 575mm 15 5 393 7mm 4 615 117 22mm 12 23 310 64mm 4 615 117 22mm 1 5 38...

Page 13: ...Thermal Supervisory Relay 15 45 2312 24TB Photoelectric 0 12 50 2412 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2451 Photoelectric 0 10 39 2451TH with B402B Base Photoelectric 0 10 39 2...

Page 14: ...trol of up to 2 two Altronix eFlow power output s via LAN and or WAN Monitor real time diagnostics DC output voltage output current AC battery status service input trigger state change output state ch...

Page 15: ...sponsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8181 fax 718 567 9056 website www altronix com e mail info altronix com Lifetime Warranty Made in U S A...

Page 16: ...65AH 6A 10A 1 5A 10A Over 4 Hours 10A Battery Backup Built in charger for sealed lead acid or gel type batteries Maximum charge current 1 54A Automatic switch over to stand by battery when AC fails Tr...

Reviews: