eFlow104N Series Installation Guide

Overview:

Altronix eFlow104N power supply/chargers convert a 120VAC / 60Hz input to a 24VDC nominal output

(see Power Supply Configuration Reference Chart and Specifications)

.

eFlow104N Series Power Supply Configuration Reference Chart:

Altronix  Model Number

Nominal DC 

Outputs

Maximum Supply Current for  Main and Aux. Outputs (A)

Input Rating: 120VAC, 60Hz

Input Fuse Rating

Battery Fuse Rating

Ripple Voltage (mV)

Under low battery condition

Power Distribution Modiule

Number of Outputs

Fused Outputs Ratings

PTC Protected Class 2 Power-Limited  Auto-Resettable Outputs Ratings

Accommodates up to 7AH Batteries

Accommodates up to 12AH Batteries

[DC]

[AUX]

24VDC Output Range (V)

24VDC Output Range (V)

eFlow104N

20.17-

26.4

20.28-

26.4

10A

4.5A 6.3A/

250V

15A/

32V 700

N/A

1

P

eFlow104NX

P

eFlow104N8

20.17-

26.4

20.28-

26.4

10A

4.5A 6.3A/

250V

15A/

32V 700

PD8UL

8

2.5A

P

eFlow104NX8

2.5A

P

eFlow104N8D

20.0-

26.4

20.28-

26.4

10A

4.5A 6.3A/

250V

15A/

32V 700

PD8ULCB

8

2A

P

eFlow104NX8D

2A

P

eFlow104N16

20.17-

26.4

20.28-

26.4

10A

4.5A 6.3A/

250V

15A/

32V 700

PD16W

16

2.5A

P

eFlow104NX16

2 - PD8UL

2.5A

P

eFlow104N16D

20.0-

26.4

20.28-

26.4

10A

4.5A 6.3A/

250V

15A/

32V 700

PD16WCB

16

2A

P

eFlow104NX16D

2 - PD8ULCB

2A

P

The following units provide non power-limited outputs: eFlow104N, eFlow104NX, eFlow104N8, eFlow104NX8, eFlow104N16, 

and eFlow104NX16.

The following units provide Class 2 power-limited outputs: eFlow104N8D, eFlow104NX8D, eFlow104N16D, and eFlow104NX16D.

If a power-limited output is required in the end-product application, the DC output from the power supply must be connected to a 

separately Listed control unit or accessory board that provides power-limited outputs. The product(s) providing the power-limited 

output(s) must be listed as appropriate for the particular end-product application (fire alarm, burglar alarm, access control), and 

wired in accordance with the products installation instructions. Class 1 wiring methods, separation of circuits, and proper fire-

rated enclosures all must be considered when connecting the DC output of the power supply to the end-product devices. The 

auxiliary output of these units are power-limited.

UL Listings for US Installations:

UL 294, 7th edition

 - UL Listed for Access Control System Units.

 

Access Control Performance Levels: 

  Destructive Attack - I; Endurance - I; Line Security - I; 

  Stand-by Power: 7AH - I, 12AH - I, 40AH - III, 65AH - IV.

UL 603 - UL Listed for Power Supplies for Use with Burglar-Alarms Systems.

UL 1481 - UL Listed for Power Supplies for Fire Protective Signaling Systems.

UL Listings for Canadian Installations:

ULC-S318-96 - Power Supplies for Burglar Alarm Systems. Also suitable for Access Control.

California State Fire Marshal

 

European Conformity

Factory Mutual Approved (eFlow104N and eFlow104NX only)

Altronix Corp.

140 58th St. Brooklyn, NY

Summary of Contents for eFlow104N Series

Page 1: ...t 8 PTC Protected Class 2 Power Limited Outputs eFlow104N16D eFlow104NX16D 10A 24VDC Sixteen 16 PTC Protected Class 2 Power Limited Outputs eFlow104N Series Power Supply Chargers Models Include Rev 10...

Page 2: ...104NX eFlow104N8 eFlow104NX8 eFlow104N16 and eFlow104NX16 The following units provide Class 2 power limited outputs eFlow104N8D eFlow104NX8D eFlow104N16D and eFlow104NX16D If a power limited output is...

Page 3: ...60Hz Input Battery Wires Minimum 0 25 spacing must be provided CAUTION Do not touch exposed metal parts Shut branch circuit power before installing or servicing equipment There are no user serviceabl...

Page 4: ...position Fig 1c pg 5 9 Trigger terminals are end of a line resistor supervised 10k ohms Opening or shorting trigger terminals will cause DC output to shutdown Fig 1d pg 5 10 Place a jumper for non lat...

Page 5: ...power is present Contact rating 1A 30VDC A removed battery is reported within 5 minutes Battery reconnection is reported within 1 minute power limited Fig 1b pg 5 BAT Stand by battery connections Maxi...

Page 6: ...Power Limited Outputs N COMMON POWER OUTPUTS P FUSED POWER OUTPUTS 1 2 3 4 5 6 7 8 D1 INPUT R1 LED DC Output to devices 1P 8P Power Outputs 1N 8N Common Outputs From Power Supply Board Factory Install...

Page 7: ...294 Applications Note 12V batteries are required for UL603 UL1481 and Canadian installations CAUTION Power supply board is factory set for 24VDC Use two 2 12VDC stand by batteries Keep power limited w...

Page 8: ...employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods For Canadian ins...

Page 9: ...minimum 0 25 spacing 12AH Rechargeable batteries are the largest batteries that can fit in this enclosure A UL listed external battery enclosure must be used if using 40AH or 65AH batteries Optional...

Page 10: ...employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods For Canadian inst...

Page 11: ...x 82 6mm 1 40 35 6mm 1 40 35 6mm 1 40 35 6mm 4 85 123 2mm 4 85 123 2mm 3 25 82 6mm 0 75 19 1mm 0 75 19 1mm 11 0 279 4mm 12 5 317 5mm 1 20 30 5mm 1 20 30 5mm 0 9375 23 8mm 0 9375 23 8mm 5 10 129 5mm 1...

Page 12: ...25 28 6mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 4 5 114 3mm 4 5 114 3mm 1 25 31 8mm 1 25 31 8mm 0 79 20 1mm 0 91 23 1mm 0 91 23 1mm 15 5 393 7mm 1 1 27 9mm 1 1 27 9mm 1 1 27 9mm 12 23 310 6mm...

Page 13: ...ectric w 135o Thermal Supervisory Relay 15 45 2312 24TB Photoelectric 0 12 50 2412 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2451 Photoelectric 0 10 39 2451TH with B402B Base Photoelect...

Page 14: ...emote control of up to 2 two Altronix eFlow power output s via LAN and or WAN Monitor real time diagnostics DC output voltage output current AC battery status service input trigger state change output...

Page 15: ...ltronix is not responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8181 fax 718 567 9056 website www altronix com e mail info altronix com Lifetime Warra...

Page 16: ...5AH 6A 10A 1 5A 10A Over 4 Hours 10A Battery Backup Built in charger for sealed lead acid or gel type batteries Maximum charge current 1 0A Automatic switch over to stand by battery when AC fails Tran...