- 2 -
eFlow102NV Series
Overview:
Altronix eFlow102NV power supply/chargers convert a 220VAC (working range 198VAC - 256VAC), 50/60Hz
input to a 12VDC nominal output (see Power Supply Configuration Reference Chart and Specifications).
eFlow102NV Series Power Supply Configuration Reference Chart:
Altronix
Model Number
Nominal DC
Outputs
Maximum Supply Current for
Main and Aux. Outputs(A)
Input Rating:
220VAC 50/60Hz
Input Fuse Rating
Battery Fuse Rating
Ripple Voltage (mV)
Under low battery condition
Power Distribution
Modiule
Number of Outputs
Fused Outputs Ratings
Auto-Resettable
PTC Outputs Ratings
Accommodates up to
7AH Batteries
Accommodates up to
12AH Batteries
[DC]
[AUX]
12VDC Output
Range (V)
12VDC Output
Range (V)
eFlow102NV
10.03-
13.2
10.03-
13.2
10A 2.1A
5A/
250V
15A/
32V
760
N/A
1
–
–
P
–
eFlow102NXV
–
–
–
P
eFlow102N8V
10.03-
13.2
10.03-
13.2
10A 2.1A
5A/
250V
15A/
32V
760
PD8
8
2.5A
–
P
–
eFlow102NX8V
2.5A
–
–
P
eFlow102N8DV
9.78-
13.2
10.03-
13.2
10A 2.1A
5A/
250V
15A/
32V
760
PD8CB
8
–
2A
P
–
eFlow102NX8DV
–
2A
–
P
eFlow102N16V
10.03-
13.2
10.03-
13.2
10A 2.1A
5A/
250V
15A/
32V
760
PD16W
16
2.5A
–
P
–
eFlow102NX16V
2 - PD8
2.5A
–
–
P
eFlow102N16DV
9.78-
13.2
10.03-
13.2
10A 2.1A
5A/
250V
15A/
32V
760
PD16WCB
16
–
2A
P
–
eFlow102NX16DV
2 - PD8CB
–
2A
–
P
European Conformity
Stand-by Specifications:
Battery
Burg. Applications
4 hr. Stand-by/
15 min. Alarm
Fire Applications
24 hr. Stand-by/
5 min. Alarm
Access Control
Applications
Stand-by
7AH
0.4A/10A
N/A
5 Mins./10A
12AH
1A/10A
0.3A/10A
15 Mins./10A
40AH
(for eFlow102NXV refer to Fig. 8, pg. 10)
6A/10A
1.2A/10A
Over 2 Hours/10A
65AH
(for eFlow102NXV refer to Fig. 8, pg. 10)
6A/10A
1.5A/10A
Over 4 Hours/10A