AL602ADA220 Installation Guide

Overview:

Altronix AL602ADA220 is an extremely cost-effective 6.5A remote power supply/battery charger. It may be con-

nected to any 24 volt Fire Alarm Control Panel (FACP). Primary applications include Notification Appliance Circuit 

(NAC such as strobes and horns) expansion support to meet ADA requirements. It also provides auxiliary power 

to support system accessories. The unit delivers electronically regulated and filtered 24 volt power to Class B or 

Class A NAC loop circuits. The 6.5A max. alarm current can be divided between the four (4) outputs for powering 

NAC devices. Each output is rated at 2.5A max., and can be independently programmed for Steady, Temporal 

Code 3 or Strobe Synchronization. All outputs may be programmed for Input to Output Follower Mode (output will 

follow input). In non-alarm condition independent loop supervision for Class A and/or Class B FACP NAC circuits 

is provided. In the event of a loop trouble, the FACP will be notified via the steered input (Input 1 or Input 2). In 

addition, there are common trouble output terminals (NC, C, NO) which are used to indicate general loop/system 

trouble. A common trouble input is provided for optional NC (normally closed) devices to report trouble to the 

FACP. Two (2) FACP signaling outputs can be employed and directed to control supervision and power delivery to 

any combination of the four (4) outputs.

Specifications:

WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture. 
This installation should be made by qualified service personnel and should conform to all local codes.

Input:

•  Nominal 220VAC (working range 198 - 256VAC), 

60Hz, 1.2A.

•  Two (2) Class A or two (2) Class B FACP inputs.

•  Two (2) NC dry contact trigger inputs.

Output:

•  24VDC @ 6.5A max total alarm current.

•  2.5A max current per output.

•  Separate 1.0A auxiliary output.

•  Programmable supervised indicating circuit outputs:

  Four (4) Class B or two (2) Class A or 

  One (1) Class A and Two (2) Class B 

 

(see 02 Application Guide).

•   Thermal and short circuit protection with auto reset.

Battery Backup:

•   Built-in charger for sealed lead acid or 

  gel type batteries. 

•   Automatic switchover to stand-by battery when 

  AC Fails.

•  Zero voltage drop when switching over to 

  battery backup. 

Visual Indicators: 

•  Input and output status LED indicators. 

Supervision: 

•  AC fail supervision (form “C” contact, 1A / 28VDC). 

  Factory set for 30 seconds with optional 2.5 to 3 

  hour delay setting (field selectable).

•  Instant local AC trouble reporting relay

  (form “C” contact, 1A / 28VDC).

•  Battery presence and low battery supervision 

  (form “C” contact, 1A / 28VDC).

Special Features: 

•  2-wire horn/strobe Sync mode allows 

  audible notification appliances (horns) and 

  visual notification appliances (strobes) to be 

  silenced/deactivated at the same time.

•  Sync protocols include Potter/Amseco, Gentex

®

  System Sensor

®

, and CooperWheelock

®

•  Temporal Code 3, Steady Mode, Input to Output

  Follower Mode (maintains synchronization of 

  notification appliances circuit).

•  Compatible with 12VDC or 24VDC fire panels. 

•  Output loop supervision steered to Input 1 or Input 2.

•  Signal circuit trouble memory (helps identify 

  intermittent loop problems).

•  Common trouble input and output.

•  Ground fault detection. 

•  Unit includes power supply, red enclosure, cam 

  lock, and battery leads.

Enclosure Dimensions 

(H x W x D approximate)

:

15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm).

Summary of Contents for AL602ADA220

Page 1: ...ee Application Guide for additional information Rev 030320 More than just power TM Installing Company ________________ Service Rep Name ___________________________________ Address ______________________________________________ Phone ___________________ ...

Page 2: ...ersonnel and should conform to all local codes Input Nominal 220VAC working range 198 256VAC 60Hz 1 2A Two 2 Class A or two 2 Class B FACP inputs Two 2 NC dry contact trigger inputs Output 24VDC 6 5A max total alarm current 2 5A max current per output Separate 1 0A auxiliary output Programmable supervised indicating circuit outputs Four 4 Class B or two 2 Class A or One 1 Class A and Two 2 Class B...

Page 3: ...02ADA220 AL1002ADA220 Power Supply Specifications pg 3 Stand by Specifications pg 3 Output Programming Selection Table pg 4 Sync Mode Selection Table pg 4 Terminal Identification Table pgs 5 6 LED Status Indication Table pg 6 1 Mount the unit in the desired location Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure Install two upper fasteners and screws in t...

Page 4: ...connected Sync Mode Selection Table Function Switch Positions Descriptions ON OFF Amseco Sync Mode 1 3 4 2 This mode is designed to work with the Amseco series of horns strobes and horn strobes to provide a means of synchronizing the Temporal coded horns synchronizing the flash timing of the strobe and silencing the horns of the horn strobe combination over a two wire circuit while leaving strobes...

Page 5: ...puts are set by output switches OUT1 through OUT4 Output Programming Selection Table pg 4 Note these inputs are unidirectional and will not report a trouble condition to the FACP OUT1 OUT2 OUT3 OUT4 Supervised Notification appliances are connected to these regulated outputs see 02 Application Guide pg 2 4 Each power limited output will supply 2 5A Total supply current is 6 5A see note below Output...

Page 6: ...s Low battery condition will report at approximately 21VDC Battery presence detection will report with in 180 seconds after battery remains undetected missing or removed A restored battery will report within 30 seconds LED Diagnostics AL600ADA Power Supply Board Red DC Green AC Power Supply Status ON ON Normal operating condition ON OFF Loss of AC Stand by battery is supplying power OFF ON No DC o...

Page 7: ...larm mA 0mA mA Alarm mA 0mA mA Alarm mA 0mA mA Alarm mA 0mA mA C Notification Appliances Current must not exceed 6 5A 6500mA 0mA mA D Total alarm current mA mA E Total current ratings converted to amperes line D x 0 001 A A F Number of standby hours 24 for NFPA 72 Chapter 1 1 5 2 5 H G Multiply lines E and F Total stand by AH AH H Alarm sounding period in hours For example 5 minutes 0 0833 hours H...

Page 8: ... a simultaneous trouble condition to the FACP s IN1 and IN2 Non Supervised Class E AC Local Power limited Fig 2a DC OUT1 OUT2 OUT3 OUT INP1 INP2 F OUT1 OUT3 OUT2 OUT4 INPUT SELECT TEMPORAL STROBE SYNC IN OUT SYNC INPUT SELECT TEMPORAL STROBE SYNC IN OUT SYNC AUX line neutral RESET Unswitched 220VAC power mains non power limited 5A 250V Use separate knockout Keep 0 25 spacin non power limited wirin...

Page 9: ... C should connect to the host control panel for local annunciation of the trouble condition Note If common trouble input terminals marked C FAULT NC are not used these terminals must be shorted connect jumper to remain inactive For optional hookups see Fig 2b Maintenance Unit should be tested at least once a year for the proper operation as follows Output Voltage Test Under normal load conditions ...

Page 10: ...ystem Sensor 2112 24AITR Photoelectric 0 50 60 70 System Sensor 2112 24 D Photoelectric 0 05 50 System Sensor 2112 24R Photoelectric 0 50 60 70 System Sensor 2112 24TR Photoelectric 0 50 60 70 System Sensor 2112 24T D Photoelectric w 135 o Thermal 0 05 50 System Sensor 2112 24TSRB Photoelectric w 135 o Thermal Supervisory Relay 15 45 System Sensor 2312 24TB Photoelectric 0 12 50 System Sensor 2412...

Page 11: ...ount 96 Rixon Firemark FM 980 Floor Mount single 68 Rixon Firemark FM 996 Surface Wiring 68 Rixon Firemark FM 998 Concealed Wiring 68 A 3 Relays Table A 3 below lists relays compatible with AL602ADA220 AUX output and Outputs 1 8 when programmed as AUX Manufacturer Model Current mA Manufacturer Model Current mA System Sensor PR 1 15 System Sensor R 20T 40 PR 2 30 R 24T 40 PR 3 30 R 10E 23 EOLR 1 30...

Page 12: ...25 31 8mm 1 25 31 8mm 0 79 20 1mm 0 91 23 1mm 0 91 23 1mm 15 5 393 7mm 1 1 27 9mm 1 1 27 9mm 1 1 27 9mm 12 23 310 6mm 2 0 50 8mm 2 0 50 8mm 1 25 31 8mm 1 25 31 8mm Enclosure Dimensions 15 5 x 12 x 4 5 393 7mm x 304 8mm x 114 3mm Altronix is not responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8181 fax 718 567 9056 website www altronix com e mail in...

Reviews: