AL602ADA220 Installation Guide 

- 9 -

Optional Hookups:

1- Battery and AC monitoring: AC or Battery Fail condition will cause the common trouble input 

  [C “FAULT” NC] to report back to the FACP via Input 1 and Input 2. The common trouble input may also 

  be used for other optional supervisory monitoring. 

(see Power Board Parameter for use of AC Delay, pg. 6)

  To report AC and Battery Trouble connect the battery and AC Fail relay output shown in (

Fig. 2a

) to the 

  common trouble input.

2- Dry contact input (C “DRY1” NC) (C “DRY2” NC) can be used to alarm output from an 

  addressable module (these inputs are unidirection and cannot report back to trigger module).

 

Connection to triggering devices must be made within 20ft of distance and using conduit for wiring.

3- Auxiliary output [– AUX +] 24VDC at 1A max.

4- AC Local [NC, NO, C] should connect to the host control panel for local annunciation of the trouble condition.

 

Note: 

If common trouble input, terminals marked [C “FAULT” NC] are not used, these terminals must be

  shorted (connect jumper) to remain inactive. For optional hookups see 

Fig. 2b

.

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

Output Voltage Test:

  Under normal load conditions the DC output voltage should be checked for proper 

   

voltage level 

(26.2-26.4VDC recommended range).

Battery Test

Under normal load conditions check that the battery is fully charged. Check specified 

   

voltage both at the battery terminal and at the board terminals marked [+ BAT –] to 

   

ensure that there is no break in the battery connection wires.

Fuses:

  

Check input fuse on the power supply board, replace if necessary. 

   

Input fuse rating is 5A @ 250V.

Note:

  

Maximum charging current is 650mA.

Note:

  

Expected battery life is 5 years; however, it is recommended changing batteries in

   

4 years or less if needed.

Summary of Contents for AL602ADA220

Page 1: ...ee Application Guide for additional information Rev 030320 More than just power TM Installing Company ________________ Service Rep Name ___________________________________ Address ______________________________________________ Phone ___________________ ...

Page 2: ...ersonnel and should conform to all local codes Input Nominal 220VAC working range 198 256VAC 60Hz 1 2A Two 2 Class A or two 2 Class B FACP inputs Two 2 NC dry contact trigger inputs Output 24VDC 6 5A max total alarm current 2 5A max current per output Separate 1 0A auxiliary output Programmable supervised indicating circuit outputs Four 4 Class B or two 2 Class A or One 1 Class A and Two 2 Class B...

Page 3: ...02ADA220 AL1002ADA220 Power Supply Specifications pg 3 Stand by Specifications pg 3 Output Programming Selection Table pg 4 Sync Mode Selection Table pg 4 Terminal Identification Table pgs 5 6 LED Status Indication Table pg 6 1 Mount the unit in the desired location Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure Install two upper fasteners and screws in t...

Page 4: ...connected Sync Mode Selection Table Function Switch Positions Descriptions ON OFF Amseco Sync Mode 1 3 4 2 This mode is designed to work with the Amseco series of horns strobes and horn strobes to provide a means of synchronizing the Temporal coded horns synchronizing the flash timing of the strobe and silencing the horns of the horn strobe combination over a two wire circuit while leaving strobes...

Page 5: ...puts are set by output switches OUT1 through OUT4 Output Programming Selection Table pg 4 Note these inputs are unidirectional and will not report a trouble condition to the FACP OUT1 OUT2 OUT3 OUT4 Supervised Notification appliances are connected to these regulated outputs see 02 Application Guide pg 2 4 Each power limited output will supply 2 5A Total supply current is 6 5A see note below Output...

Page 6: ...s Low battery condition will report at approximately 21VDC Battery presence detection will report with in 180 seconds after battery remains undetected missing or removed A restored battery will report within 30 seconds LED Diagnostics AL600ADA Power Supply Board Red DC Green AC Power Supply Status ON ON Normal operating condition ON OFF Loss of AC Stand by battery is supplying power OFF ON No DC o...

Page 7: ...larm mA 0mA mA Alarm mA 0mA mA Alarm mA 0mA mA Alarm mA 0mA mA C Notification Appliances Current must not exceed 6 5A 6500mA 0mA mA D Total alarm current mA mA E Total current ratings converted to amperes line D x 0 001 A A F Number of standby hours 24 for NFPA 72 Chapter 1 1 5 2 5 H G Multiply lines E and F Total stand by AH AH H Alarm sounding period in hours For example 5 minutes 0 0833 hours H...

Page 8: ... a simultaneous trouble condition to the FACP s IN1 and IN2 Non Supervised Class E AC Local Power limited Fig 2a DC OUT1 OUT2 OUT3 OUT INP1 INP2 F OUT1 OUT3 OUT2 OUT4 INPUT SELECT TEMPORAL STROBE SYNC IN OUT SYNC INPUT SELECT TEMPORAL STROBE SYNC IN OUT SYNC AUX line neutral RESET Unswitched 220VAC power mains non power limited 5A 250V Use separate knockout Keep 0 25 spacin non power limited wirin...

Page 9: ... C should connect to the host control panel for local annunciation of the trouble condition Note If common trouble input terminals marked C FAULT NC are not used these terminals must be shorted connect jumper to remain inactive For optional hookups see Fig 2b Maintenance Unit should be tested at least once a year for the proper operation as follows Output Voltage Test Under normal load conditions ...

Page 10: ...ystem Sensor 2112 24AITR Photoelectric 0 50 60 70 System Sensor 2112 24 D Photoelectric 0 05 50 System Sensor 2112 24R Photoelectric 0 50 60 70 System Sensor 2112 24TR Photoelectric 0 50 60 70 System Sensor 2112 24T D Photoelectric w 135 o Thermal 0 05 50 System Sensor 2112 24TSRB Photoelectric w 135 o Thermal Supervisory Relay 15 45 System Sensor 2312 24TB Photoelectric 0 12 50 System Sensor 2412...

Page 11: ...ount 96 Rixon Firemark FM 980 Floor Mount single 68 Rixon Firemark FM 996 Surface Wiring 68 Rixon Firemark FM 998 Concealed Wiring 68 A 3 Relays Table A 3 below lists relays compatible with AL602ADA220 AUX output and Outputs 1 8 when programmed as AUX Manufacturer Model Current mA Manufacturer Model Current mA System Sensor PR 1 15 System Sensor R 20T 40 PR 2 30 R 24T 40 PR 3 30 R 10E 23 EOLR 1 30...

Page 12: ...25 31 8mm 1 25 31 8mm 0 79 20 1mm 0 91 23 1mm 0 91 23 1mm 15 5 393 7mm 1 1 27 9mm 1 1 27 9mm 1 1 27 9mm 12 23 310 6mm 2 0 50 8mm 2 0 50 8mm 1 25 31 8mm 1 25 31 8mm Enclosure Dimensions 15 5 x 12 x 4 5 393 7mm x 304 8mm x 114 3mm Altronix is not responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8181 fax 718 567 9056 website www altronix com e mail in...

Reviews: