background image

Typical Application Diagrams:

AL600LGK

ALTRONIX CORP.
BKLYN, NY 11220

SW1

SW2

+ OUT1 --

 

INP1  INP2  

FAULT

NC

C

NO

C

"

F

A

U

L

T

"

N

C

AUX
RESET

O

OPEN - INP2

OUT2

OUT4

CLOSED - INP1

OPEN - INP2

L OWER TERMIN ALS

IN1+

UPP ER TERM INALS

IN1--

IN2+

IN2--

RET1+ RET1-- RET2+ RET2--

From  FACP

NAC2

From

FACP

NAC1

To FACP NAC1

EOL or next

device

2.2K

EOL

2.2K

EOL

2.2K

EOL

2.2K

EOL

Optional paralleled

Class B output  

+ OUT2 --

+ OUT3 --

+ OUT4 --

To FACP

NAC2

EOL or next

device

Class B hookup:

• Switches SW1 & SW2 on AL600LGK logic board 

must be in the open position.

• It is recommended (not required) to control visual 

notification appliances (strobes) via Input 1 (IN1) &
to control audible notifcation appliances (horns) via 
Input 2 (IN2). 
This facilitates the ability to silence audible 
notification appliances (horns) independently 
of visual notification appliances (strobes) 
during certain operations.

Note: If common trouble input, terminals marked 
[C “FAULT” N.C.] are not used, these terminals must be 
shorted (connect jumper) to remain inactive.  For optional
hookups (Fig. 4D, pg. 7).

Two outputs may be connected in parallel for a maximum
NAC output capability of 4 amp. When paralleling two (2) 
outputs, bridge (pos +) to (pos +) and (neg -) to (neg -) of the
selected outputs (Fig. 2, pg. 6). Both of the corresponding 
output switches must be set to follow the same input. Install
two (2) 2.2K ohm EOL resistors in parallel across the last 
notification appliance.

Note: Paralleled output circuit configuration is 
non-power limited.

AL600LGK

ALTRONIX CORP.
BKLYN, NY 11220

SW1

--- DC 

 

 

+

SW2

+ OUT1 --

 

OUT1  OUT2  OUT3  OUT4

INP1  INP2  

FAULT

--- AUX  +

NO  REMOTE C

NC

C

NO

C

"FAULT"

NC

AUX
RESET

OUT1

OUT3

CLOSED - INP1

OPEN - INP2

OUT2

OUT4

CLOSED - INP1

OPEN - INP2

LOWER  TERMI NALS

IN1+

U PPER  TERMI NALS

IN1--

IN2+

IN2--

RET1+ RET1-- RET2+ RET2--

Return to

FACP NAC2

From

FACP

NAC1

+ OUT2 --

+ OUT3 --

+ OUT4 --

Return to

FACP NAC1

From

FACP NAC2

Class A hookup:

• Switches SW1 & SW2 on AL600LGK logic board 

must be in the closed position for proper
termination of NAC. Output 1 and output 3 must be 
wired in parallel (pos +) to (pos +) and (neg -) 
to (neg -). Output 2 and output 4 must be wired in 
parallel (pos + to pos + and neg - to neg -). Both of the 
corresponding output switches must be set to follow 
the same input.

Note: If common trouble input, terminals marked 
[C “FAULT” N.C.] are not used, these terminals must be 
shorted (connect jumper) to remain inactive.  For optional
hookups (Fig. 4D, pg. 7).

Note: Paralleled output circuit configuration is 
non-power limited.

Horn

Legend

Strobes

Horn Strobes

Fig. 2

Fig. 3

Note: The sync mode will only synchronize
notification appliances with synchronization
capability. Contact signal manufacturer for more
detailed info. The same synchronization mode
must be selected for all outputs.

- 6 -

Summary of Contents for AL600ULADA

Page 1: ...Rev 122000 AL600ULADA NAC Power Extender Installation Guide...

Page 2: ...4 outputs Specifications AL600ULADA NAC Power Extender Agency Listings UL Listed for Control Units and Accessories for Fire Alarm Systems UL 864 and UL Listed Standard for Safety for Fire Protective S...

Page 3: ...limited wiring separate from non power limited wiring 115VAC 60Hz Input Battery Wires Minimum 25 spacing must be provided 3 Set switch SW1 on Power Supply Board for desired output voltage Open for 24...

Page 4: ...Condition Memory Out 2 Normal Alarm Condition Trouble Condition Trouble Condition Memory Out 3 Normal Alarm Condition Trouble Condition Trouble Condition Memory Out 4 Normal Alarm Condition Trouble C...

Page 5: ...esignated input 1 IN1 or input 2 IN2 Input Output Selection Table pg 4 C FAULT N C An open circuit across this pair of terminals will cause IN1 and IN2 to simultaneously Common signal a trouble condit...

Page 6: ...ng output switches must be set to follow the same input Install two 2 2 2K ohm EOL resistors in parallel across the last notification appliance Note Paralleled output circuit configuration is non powe...

Page 7: ...W1 CLOSED 12V DC AC RL2 RL3 RLY1 PTC2 AC TROUBLE DELAY OPTION J2 IC3 IC2 AC FAIL NC C NO BAT FAIL NC C NO XFMR These circuits are used to monitor AC and Bat Fail and will cause a simultaneous trouble...

Page 8: ...t the battery is fully charged Check specified voltage both at battery terminal and at the board terminals marked BAT to insure there is no break in the battery connection wires Note Maximum charging...

Reviews: