Overview:

The Altronix AL600ULADA is an extremely cost effective 6.5 amp voltage regulated remote power supply/battery charg-
er. The AL600ULADA may be connected to any 12 or 24 volt Fire Alarm Control Panel (FACP). Primary applica-
tions include Notification Appliance Circuit (NAC) expansion (supports ADA requirements) and will provide aux-
iliary power to support system accessories. The unit delivers regulated and filtered 24 or 12 volt power via four
(4) Class B, two (2) Class A or two (2) Class B and one (1) Class A  Notification Appliance Circuits.
Additionally, a separate 50mA auxiliary output with reset for four (4)-wire smoke detectors. The 6.5 amp continu-
ous supply current can be divided between the four (4) outputs for powering notification appliances. Each output is
rated at 2 amp max. An individual output of 4 amp is achieved by paralleling 2 outputs. The AL600ULADA in
non-alarm condition provides independent loop supervision for Class A and/or Class B FACP NAC circuits. In the event
of a loop trouble the FACP will be notified via the AL600ULADA’s steered input (input 1 or input 2). In addition, there
are common trouble output terminals (NC, C, NO) which are used to indicate general loop/system trouble. A common
trouble input is provided for optional NC (normally closed) devices to report trouble to the FACP. Two (2) FACP signaling
outputs can be connected to AL600ULADA’s inputs. These inputs can then be directed to control supervision and power
delivery to any combination of the four (4) outputs.

Specifications:

AL600ULADA - NAC Power Extender

Agency Listings:

• UL Listed for Control Units and Accessories for Fire 

Alarm Systems (UL 864) and UL Listed Standard for 
Safety for Fire Protective Signaling Systems (UL 1481).

• MEA - NYC Department of Buildings Approved.
• CSFM - California State Fire Marshal Approved.
• NFPA 72 Compliant.

Inputs:

• Power input 115VAC / 60 Hz, 3.2 amp.
• Two (2) Class A or two (2) Class B FACP inputs.
• Compatible with 12VDC or 24VDC fire panels.

Outputs:

• Class 2 Rated power limited outputs.
• Field selectable 24VDC or 12VDC voltage regulated 

power limited outputs.

• 24VDC or 12VDC rated @ 6.5 amp max.
• Separate 1 amp auxiliary output with built-in and 

remote reset capability.

• Two (2) outputs may be paralleled for more power on 

an indicating circuit.

• Programmable EOL resistor supervised indicating 

circuit outputs: 
Four (4) Class B or Two (2) Class A or One (1) Class A 
and Two (2) Class B.

• Filtered and electronically regulated output. 

Battery Backup:

• Built-in charger for sealed lead acid or 

gel type batteries. 

• Zero voltage drop when switching over to 

battery backup.

• Automatic switchover to stand-by battery when 

AC Fails. 

• PTC battery protection.

Supervision:

• AC fail supervision 

(form "C" contact, 1 amp / 28VDC).

• Battery presence and low battery supervision 

(form "C" contact, 1 amp / 28VDC).

Visual Indicators:

• Input and output status LED indicators.

Special Features:

• Output loop supervision steered to Input 1 or Input 2.
• Common trouble input and output.
• Ground fault detection. 

Added Features:

• Unit includes power supply, red enclosure, cam lock, 

open frame transformer and battery leads.

• Thermal and short circuit protection with auto reset.

Enclosure Dimensions:

15.5"H x 12"W x 4.5"D

Product Weight:

17 lbs.

- 2 -

Summary of Contents for AL600ULADA

Page 1: ...Rev 122000 AL600ULADA NAC Power Extender Installation Guide...

Page 2: ...4 outputs Specifications AL600ULADA NAC Power Extender Agency Listings UL Listed for Control Units and Accessories for Fire Alarm Systems UL 864 and UL Listed Standard for Safety for Fire Protective S...

Page 3: ...limited wiring separate from non power limited wiring 115VAC 60Hz Input Battery Wires Minimum 25 spacing must be provided 3 Set switch SW1 on Power Supply Board for desired output voltage Open for 24...

Page 4: ...Condition Memory Out 2 Normal Alarm Condition Trouble Condition Trouble Condition Memory Out 3 Normal Alarm Condition Trouble Condition Trouble Condition Memory Out 4 Normal Alarm Condition Trouble C...

Page 5: ...esignated input 1 IN1 or input 2 IN2 Input Output Selection Table pg 4 C FAULT N C An open circuit across this pair of terminals will cause IN1 and IN2 to simultaneously Common signal a trouble condit...

Page 6: ...ng output switches must be set to follow the same input Install two 2 2 2K ohm EOL resistors in parallel across the last notification appliance Note Paralleled output circuit configuration is non powe...

Page 7: ...W1 CLOSED 12V DC AC RL2 RL3 RLY1 PTC2 AC TROUBLE DELAY OPTION J2 IC3 IC2 AC FAIL NC C NO BAT FAIL NC C NO XFMR These circuits are used to monitor AC and Bat Fail and will cause a simultaneous trouble...

Page 8: ...t the battery is fully charged Check specified voltage both at battery terminal and at the board terminals marked BAT to insure there is no break in the battery connection wires Note Maximum charging...

Reviews: