background image

Terminal Identification Table:

AL600LGK Logic Board

Terminal

Function/Description

Legend

IN1+, IN1-

These terminals connect to the 12 or 24VDC FACP  notification appliance circuit outputs.

IN2+, IN2-

(Class A or Class B) Input trigger voltage is 9-30VDC @ 5mA min. Terminal polarity is 
shown in alarm condition. During an alarm condition these inputs will cause the selected 
outputs chosen to drive notification appliances. The designated outputs are set by output 
switches OUT1 through OUT4 (Input/Output Selection Table pg. 4). A trouble condition 
on an output loop will cause the corresponding input to trip the FACP by opening the FACP 
loop. An alarm condition will always override trouble to drive notification appliances. 

RET1+, RET1-

For Class A hookups these terminal pairs return to FACP NAC1 and/or NAC2. For Class B 

RET2+, RET2-

hookups the FACP EOL resistor from the NAC1 and/or NAC2 outputs are terminated
at these terminals. Optionally, other notification appliances or additional signaling circuit 
power supplies may be connected to these terminals. If this option is chosen the EOL 
resistor must be terminated at the last device.

+ OUT1 --

Notification appliances are connected to these outputs (Typical Application

+ OUT2 --

Diagrams pg. 6). Each power limited output will supply 2 amp. Two (2) outputs may 

+ OUT3 --

be connected in parallel for a maximum NAC output capability of 4 amp. Total supply 

+ OUT4 --

current is 6.5 amp. Outputs are controlled by designated input 1 (IN1) or input 2 (IN2)
(Input/Output Selection Table pg. 4).

C “FAULT” N.C.

An open circuit across this pair of terminals will cause IN1 and IN2 to simultaneously 

(Common

signal a trouble condition back to the FACP (Typically used to report AC or BAT Fail)

trouble input)

(Fig. 4D, pg. 7).

N.C., C, N.O.

These are dry contact trouble outputs that follow any general loop/system trouble conditions.

(Common

(Typically used to trigger a digital communicator or other reporting device).

trouble output)

(Fig. 4D, pg. 7).

-- AUX+

This separate 1 amp auxiliary output is typically used to power 4-wire smoke detectors. 
It can be reset (voltage drops out) by pressing the momentary aux reset switch on
the AL600LGK logic board or via the N.O. “REMOTE” C terminals  (Fig. 4, pg. 7).

N.O.            C

A momentary dry contact closure across these terminals interrupts the [ -- AUX + ] 

“REMOTE”

power output to reset 4-wire smoke detectors

Power Supply Board

Terminal

Function/Description

Legend

AC/AC

Low voltage AC input.

-- DC  +

12VDC or 24VDC @ 6.5 amp continuous non-power limited output. 

AC FAIL

Form “C” dry contacts used to signal the loss of AC, with AC present terminals  

C, N.C., N.O.

N.O. and C are open, N.C. and C are closed. When loss of AC occurs terminals
N.O. and C close, N.C. and C are open (Fig. 4, pg. 7).

BAT FAIL

Form “C” dry contacts used to signal low battery voltage or loss of battery voltage.

N.O., N.C., C

Under normal conditions terminals NO and C are open, NC and C are closed. 
During a trouble condition terminals NO and C are closed, and NC and C are open
(Fig. 4, pg. 7).

BAT+, BAT-

Stand-by battery input (leads provided). Use two (2) 12VDC batteries wired in series
for 24VDC operation (Fig. 4, pg. 7)

- 5 -

Summary of Contents for AL600ULADA

Page 1: ...Rev 122000 AL600ULADA NAC Power Extender Installation Guide...

Page 2: ...4 outputs Specifications AL600ULADA NAC Power Extender Agency Listings UL Listed for Control Units and Accessories for Fire Alarm Systems UL 864 and UL Listed Standard for Safety for Fire Protective S...

Page 3: ...limited wiring separate from non power limited wiring 115VAC 60Hz Input Battery Wires Minimum 25 spacing must be provided 3 Set switch SW1 on Power Supply Board for desired output voltage Open for 24...

Page 4: ...Condition Memory Out 2 Normal Alarm Condition Trouble Condition Trouble Condition Memory Out 3 Normal Alarm Condition Trouble Condition Trouble Condition Memory Out 4 Normal Alarm Condition Trouble C...

Page 5: ...esignated input 1 IN1 or input 2 IN2 Input Output Selection Table pg 4 C FAULT N C An open circuit across this pair of terminals will cause IN1 and IN2 to simultaneously Common signal a trouble condit...

Page 6: ...ng output switches must be set to follow the same input Install two 2 2 2K ohm EOL resistors in parallel across the last notification appliance Note Paralleled output circuit configuration is non powe...

Page 7: ...W1 CLOSED 12V DC AC RL2 RL3 RLY1 PTC2 AC TROUBLE DELAY OPTION J2 IC3 IC2 AC FAIL NC C NO BAT FAIL NC C NO XFMR These circuits are used to monitor AC and Bat Fail and will cause a simultaneous trouble...

Page 8: ...t the battery is fully charged Check specified voltage both at battery terminal and at the board terminals marked BAT to insure there is no break in the battery connection wires Note Maximum charging...

Reviews: