7. Connect appropriate signaling notification devices to AC FAIL & BAT FAIL
(Fig. 2, pg. 2)
supervisory relay outputs.
Note:
When used in fire alarm, burglar alarm or access control applications, “AC Fail” relay should be
utilized to visually indicate that AC power is on. To delay report 6 hours cut “AC Delay” jumper
(Fig. 2a, pg. 2)
.
Maintenance:
Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test:
Under normal load conditions, the DC output voltage should be checked for proper voltage level
(
refer to Power Supply Voltage Output Specifications chart
).
Battery Test:
Under normal load conditions check that the battery is fully charged, check specified voltage both at
battery terminal and at the board terminals marked [ + BAT --- ] to insure there is no break in the battery
connection wires.
Note:
Maximum charging current under discharge is .7 amp.
Note:
Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if needed.
LED Diagnostics:
Terminal Identification:
Altronix is not responsible for any typographical errors.
---
D
C
+
L
G
N
PTC3
NC C NO NC C NO
+
B
AT
---
DC
24V - OPEN
12V - CLOSED
AC FAIL
RL2
BAT FAIL
RL1
RL3
J1
SW1
3
.5
A
2
5
0
V
Fuse
Cover
AC
De
la
y
Fig. 2
Altronix Corp.
140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
website: www.altronix.com, e-mail: [email protected], Lifetime Warranty, Made in U.S.A.
IIAL400ULXB - Rev. 120600
B04J
MEMBER
Fig. 2a
G
N
PTC
NC C NO NC C NO
DC
24V - OPEN
12V - CLOSED
AC FAIL
RL2
BAT FAIL
RL1
RL3
J1
SW1
Fuse
Cover
AC
De
la
y
Terminal
Legend
Function/Description
L, G, N
Connect 115VAC 60 Hz. to these terminals: L to hot, N to Neutral, G to ground.
– DC +
12VDC @ 4 amp or 24VDC @ 3 amp continuous power limited output.
AC Fail
NC, NC, NO
Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay normally energized
when AC power is present. Contact rating 1 amp @ 28VDC.
BAT Fail
NC, C, NO
Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when DC power
is present. Contact rating 1 amp @ 28VDC.
+ BAT –
Stand-by battery connections. Maximum charge current 1.2 amp.
Red (DC)
Green (AC) Power Supply Status
ON
ON
Normal operating condition.
ON
OFF
Loss of AC, Stand-by battery supplying power.
OFF
ON
No DC output.
OFF
OFF
Loss of AC. Discharged or no stand-by battery. No Dc output.