AL400UL3 / AL400UL3X Installation Guide

LED Diagnostics:

AL400ULXB2 - Power Supply

Red (DC)

Green (AC)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery is supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Red (Bat)

Battery Status

ON

Normal operating condition.

OFF

Battery fail/low battery.

Terminal Identification:

AL400ULXB2 - Power Supply

Terminal Legend

Function/Description

L, N

115VAC, 60 Hz

+ DC –

24VDC @ 3A total continuous output (supplies power to ALX3B).

AC Fail

NC, C, NO

Indicates loss of AC power, e.g. connect to audible device or alarm panel. 

Relay normally energized when AC power is present. Contact rating 1A @ 28VDC.

Bat Fail

NC, C, NO

Indicates low battery condition, e.g. no battery presence. 

Relay normally energized when DC power is present. Contact rating 1A @ 28VDC. 

Low battery threshold: 24VDC. Output threshold is set approximately @ 21VDC

+ BAT –

Stand-by battery connections. Maximum charge current 0.7A.

ALX3B - Power Output Module

Terminal Legend

Function/Description

+ INPUT –

24VDC from power supply (AL400ULXB2).

+ 24VDC –

24VDC @ 1.5A continuous power-limited output

+ 12VDC –

12VDC @ 1.75A continuous power-limited output.

+ 5VDC –

5VDC @ 1.75A continuous power-limited output.

Summary of Contents for AL400UL3

Page 1: ...e g AL400UL3XR AL400UL3 AL400UL3X Triple Output Power Supply Charger Installation Guide Rev 030619 More than just power TM Installing Company ________________ Service Rep Name ________________________...

Page 2: ...use rated 15A 32V Filtered and electronically regulated output s Short circuit and thermal overload protection LED Indicators AC input DC output and Battery LED indicators Battery Backup Built in char...

Page 3: ...y see list refer to Appendix A pg 6 3 Measure output voltage before connecting devices This helps avoiding potential damage 4 Connect devices to be powered at 5VDC to the terminals marked 5VDC 5 Conne...

Page 4: ...plies power to ALX3B AC Fail NC C NO Indicates loss of AC power e g connect to audible device or alarm panel Relay normally energized when AC power is present Contact rating 1A 28VDC Bat Fail NC C NO...

Page 5: ...ace fuse with the same type and rating Do not expose to rain or moisture 24VDC ALX3B INPUT 12VDC 5VDC 12VDC 24VDC 5VDC 115VAC power mains non power limited Class 1 Battery connection non power limited...

Page 6: ...lectric w 135o Thermal Supervisory Relay 15 45 2312 24TB Photoelectric 0 12 50 2412 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2451 Photoelectric 0 10 39 2451TH with B402B Base Photoelec...

Page 7: ...40 35 6mm 1 40 35 6mm 4 85 123 2mm 4 85 123 2mm 3 25 82 6mm 0 75 19 1mm 0 75 19 1mm 11 0 279 4mm 12 5 317 5mm 1 20 30 5mm 1 20 30 5mm 0 9375 23 8mm 0 9375 23 8mm 5 10 129 5mm 1 40 35 6mm 5 10 129 5mm...

Page 8: ...5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 4 5 114 3mm 4 5 114 3mm 1 25 31 8mm 1 25 31 8mm 0 79 20 1mm 0 91 23 1mm 0 91 23 1mm 15 5 393 7mm 1 1 27 9mm 1 1 27 9mm 1 1 27 9mm 12 23 310 6mm 2 0 50 8mm...

Reviews: