background image

 

AL400UL3 / AL400UL3X Installation Guide 

- 3 -

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all 

local codes and authorities having jurisdiction. Product is intended for indoor use only. 

1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes 

  in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place 

  the enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower 

  two holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s 

  upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws 

 

(Enclosure Dimensions, pgs. 7-8)

. Secure enclosure to earth ground. 

  It is recommended to first review the following tables for screw terminals, switch selection and LED status 

  indications. This will greatly facilitate installation hook-up. 

  Carefully review:

  Stand-by Specifications 

(pg. 2)

  LED Diagnostics 

(pg. 4)

  Terminal Identification Table 

(pg. 4)

2. Connect AC power (115VAC 60Hz) to the terminals marked [L, N] 

(Fig. 1, pg. 5)

. Green “AC” LED on 

  power supply board will turn on. This light can be seen through the LED lens on the door of the 

  enclosure. Use 14 AWG or larger for all power connections. Secure green wire lead to earth ground.

  Use 18 AWG or larger for all power connections (Battery, DC output, AC input).

  Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/Low Battery reporting).

  Keep power-limited wiring separate from non power-limited wiring (115VAC / 60Hz Input, 

  Battery Wires). Minimum 0.25” spacing must be provided.

  For Fire Alarm applications the outputs are “Special Applications” only, see list 

(refer to Appendix A, pg. 6)

3. Measure output voltage before connecting devices. This helps avoiding potential damage.

4. Connect devices to be powered at 5VDC to the terminals marked [+ 5VDC –].

5. Connect devices to be powered at 12VDC to the terminals marked [+ 12VDC –]. 

6. Connect devices to be powered at 24VDC to the terminals marked [+ 24VDC –].

7. Connect two (2) 12V Stand-by batteries. 

 

Note:

 For Access Control applications batteries are optional. When batteries are not used, a loss of AC will 

  result in the loss of output voltage. Batteries must be lead acid or gel type if used. 

  Use two (2) 12V stand-by batteries connected in series to the terminals marked [+ BAT –] 

(Fig. 1 , pg. 5)

.

8. It is required to connect supervisory trouble reporting devices to outputs marked [AC FAIL, LOW BAT] 

 

(Fig. 1, pg. 5)

  Use 22 AWG to 18 AWG for AC Fail and Low Battery reporting. AC Failure will report in 5 minutes.

 

Note:

 When used in fire alarm, burglar alarm or access control applications, “AC Fail” relay should be

  utilized to visually indicate that AC power is on. To delay report for 6 hours cut “AC Delay” jumper 

 

(Fig. 1, pg. 5)

.

9. Please ensure that the cover is secured with the provided key lock.

Wiring:

Use 14 AWG or larger for all power connections.

Note:

 Take care to keep power-limited circuits separate from non power-limited wiring (115VAC, Battery).

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

Output Voltage Test:

 

Under normal load conditions, the DC output voltage should be checked for proper 

   

voltage level (

refer to Power Supply Voltage Output Specifications chart

).

Battery Test:

 

Under normal load conditions check that the battery is fully charged, check specified 

   

voltage both at the battery terminal and at the board terminals marked [+ BAT –] to 

   

ensure that there is no break in the battery connection wires.

  

Note:

 Maximum charging current under discharge is 0.7A.

  

Note:

 Expected battery life is 5 years, however it is recommended changing batteries 

   

in 4 years or less if needed.

Summary of Contents for AL400UL3

Page 1: ...e g AL400UL3XR AL400UL3 AL400UL3X Triple Output Power Supply Charger Installation Guide Rev 030619 More than just power TM Installing Company ________________ Service Rep Name ________________________...

Page 2: ...use rated 15A 32V Filtered and electronically regulated output s Short circuit and thermal overload protection LED Indicators AC input DC output and Battery LED indicators Battery Backup Built in char...

Page 3: ...y see list refer to Appendix A pg 6 3 Measure output voltage before connecting devices This helps avoiding potential damage 4 Connect devices to be powered at 5VDC to the terminals marked 5VDC 5 Conne...

Page 4: ...plies power to ALX3B AC Fail NC C NO Indicates loss of AC power e g connect to audible device or alarm panel Relay normally energized when AC power is present Contact rating 1A 28VDC Bat Fail NC C NO...

Page 5: ...ace fuse with the same type and rating Do not expose to rain or moisture 24VDC ALX3B INPUT 12VDC 5VDC 12VDC 24VDC 5VDC 115VAC power mains non power limited Class 1 Battery connection non power limited...

Page 6: ...lectric w 135o Thermal Supervisory Relay 15 45 2312 24TB Photoelectric 0 12 50 2412 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2451 Photoelectric 0 10 39 2451TH with B402B Base Photoelec...

Page 7: ...40 35 6mm 1 40 35 6mm 4 85 123 2mm 4 85 123 2mm 3 25 82 6mm 0 75 19 1mm 0 75 19 1mm 11 0 279 4mm 12 5 317 5mm 1 20 30 5mm 1 20 30 5mm 0 9375 23 8mm 0 9375 23 8mm 5 10 129 5mm 1 40 35 6mm 5 10 129 5mm...

Page 8: ...5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 4 5 114 3mm 4 5 114 3mm 1 25 31 8mm 1 25 31 8mm 0 79 20 1mm 0 91 23 1mm 0 91 23 1mm 15 5 393 7mm 1 1 27 9mm 1 1 27 9mm 1 1 27 9mm 12 23 310 6mm 2 0 50 8mm...

Reviews: