background image

 

- 4 - 

AL300ULXJ

LED Diagnostics:

Red (DC)

Green (AC)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Red (Bat)

Battery Status

ON

Normal operating condition.

OFF

Battery fail/low battery.

Terminal Identification:

Terminal Legend

Function/Description

L, G, N

Connect 115VAC 60 Hz. to these terminals: L to hot, N to Neutral.

+ DC –

12VDC or 24VDC @ 2.5A continuous power-limited output.

AC Fail
NC, C, NO

Indicates loss of AC power, e.g. connect to annunciator/alarm panel. Relay normally 
energized when AC power is present. Contact rating 1A @ 28VDC. AC Fail condition 
will report approximately within one (1) minute after loss of AC. To delay report for 
6 hours cut jumper J1 on the Power Supply Board (AC trouble output delay option). If 
this mode is selected the Power Supply Board must be reset by removing all power to it 
for 30 seconds.

Bat Fail
NC, C, NO

Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized 
when DC power is present. Contact rating 1A @ 28VDC. Low battery conditions will 
report approximately 21VDC (24VDC output setting) or approximately 10.5VDC 
(12VDC output setting). Battery presence detection will report approximately 1 minute 
after battery remains undetected (missing or removed). 

+ BAT –

Stand-by battery connections. Maximum charge current 0.7A.

Summary of Contents for AL300ULXJ

Page 1: ...More than just power TM Rev 102612 AL300ULXJ Power Supply Charger Installation Guide Altronix Corp 140 58th St Brooklyn NY For a grey enclosure add a G suffix to the part number...

Page 2: ...2V Filtered and electronically regulated output s Short circuit and thermal overload protection LED Indicators AC input DC output and Battery LED indicators Battery Backup Built in charger for sealed...

Page 3: ...his helps avoiding potential damage When servicing the unit AC mains should be removed 5 Connect devices to the terminals marked DC Fig 1 pg 5 6 For Access Control applications batteries are optional...

Page 4: ...lly energized when AC power is present Contact rating 1A 28VDC AC Fail condition will report approximately within one 1 minute after loss of AC To delay report for 6 hours cut jumper J1 on the Power S...

Page 5: ...ction against risk of electric shock and fire hazard replace fuse with the same type and rating Do not expose to rain or moisture CAUTION Optional rechargeable stand by batteries must match the power...

Page 6: ...Thermal Supervisory Relay 15 45 2312 24TB Photoelectric 0 12 50 2412 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2451 Photoelectric 0 10 39 2451TH with B402B Base Photoelectric 0 10 39 2...

Page 7: ...AL300ULXJ 7 Notes...

Page 8: ...MEMBER 4 5 114 3mm 1 25 31 75mm 1 25 31 8mm 1 0 25 4mm 1 0 25 4mm 1 0 25 4mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 8 5 215 9mm 18 0 457 2mm 18 0 457 2mm 18 0 457 2mm 6 0 152 4mm 2 75...

Reviews: