background image

 

- 12 - 

AL1042ULADA / R1042ULADA Installation Guide

Optional Hookups:

1- Battery and AC monitoring: AC or Battery Fail condition will cause the common trouble input 

  [C “FAULT” NC] to report back to the FACP via input 1 and input 2. The common trouble input may also 

  be used for other optional supervisory monitoring.

  To report AC and Battery Trouble connect the battery and AC Fail relay output shown in 

Fig. 8a, pg. 11

 to 

  the common trouble input.

2- Dry contact input (C “DRY1” NC) (C “DRY2” NC) can be used to alarm output from an 

  addressable module (these inputs are unidirection and cannot report back to trigger module).

 

Connection to triggering devices must be made within 20 ft. of distance and using conduit for wiring.

3- Auxiliary output (– AUX +) 24VDC at 1A max.

4- AC Local [NC, NO, C] should connect to the host control panel for local annunciation of the trouble condition.

 Note: 

If common trouble input, terminals marked [C “FAULT” NC] are not used, these terminals must be

  shorted (connect jumper) to remain inactive. For optional hookups see 

Fig. 8b, pg. 11

.

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

Output Voltage Test:

 

Under normal load conditions, the DC output voltage should be checked for proper 

   

voltage level 

(26.2-26.4VDC recommended range).

Battery Test

Under normal load conditions check that the battery is fully charged. Check specified 

   

voltage both at battery terminal and at the board terminals marked [– BAT +] to 

   

ensure that there is no break in the battery connection wires.

Fuses:

 

Check input and output fuses on the power supply board, replace if necessary.

   

Input fuse rating is 6.3A @ 250V, Output fuse rating is 15A @ 32V.

Note:

 

Maximum charging current is 1.5A.

Note:

  

Expected battery life is 5 years; however, it is recommended changing batteries in 

   

4 years or less if needed.

Summary of Contents for AL1042ULADA

Page 1: ...r R1042ULADA Rack Mountable NAC Power Extender Installation Guide see Application Guide for additional information Rev 062320 More than just power TM Installing Company ________________ Service Rep Name ___________________________________ Address ______________________________________________ Phone ___________________ ...

Page 2: ...wo 2 Class B FACP inputs Two 2 NC dry contact trigger inputs Input Ratings INP1 and INP2 8 30VDC 6 5mA max from FACP 12V 6 5mA 24V 6 5mA from FACP Output Power limited outputs 24VDC voltage regulated power limited outputs 10A max total alarm current 2 5A max current per output Two auxiliary outputs rated at 1A each 1A continuous 1A AC disconnect Programmable supervised indicating circuit outputs F...

Page 3: ...t is intended for indoor use only Note First assemble and install Z Bracket Wire Management Accesory refer to Z Bracket Installation pg 4 Note Rack enclosure must be UL listed and hard wired to a branch electrical circuit via conduit 1 Remove backplane from enclosure prior to installing into rack cabinet do not discard hardware Grounding Connect both grounding lugs Fig 1 to earth ground using 12 A...

Page 4: ...5 Small terminal block wire gauges range from 16 AWG to 24 AWG all others range from 14 AWG to 24 AWG Z Bracket Installation for R1002ULADA Altronix R1002ULADA enclosure includes Z Bracket a convenient and reliable wire management accessory Hardware included Ten 10 bolts and eight 8 lock nuts 1 Carefully unpack Z Bracket Do not discard hardware included Fig 3 pg 4 2 Attach arms to each other using...

Page 5: ...hes of additional open space All wiring methods shall be in accordance with the National Electrical Code NFPA 70 NFPA 72 ANSI and with all local codes and authorities having jurisdiction Battery circuits are not power limited provide 0 25 spacing from power limited circuits and use separate knockout If additional battery enclosure is required it must be UL Listed for the application and mounted wi...

Page 6: ...s of synchronizing the Temporal coded horns synchronizing the flash timing of the strobe allowing audible notification appliances horns and visual notification appliances strobes to be silenced deactivated at the same time System Sensor Sync Mode System Sensor is a registered trademark of Honeywell 1 2 4 3 This mode is designed to work with the System Sensor series of horns strobes and horn strobe...

Page 7: ...l Legend Function Description L N Connect 120VAC to these terminals L to Hot N to Neutral DC 24VDC 10A continuous 10A in alarm non power limited output AC FAIL NO C NC Form C dry contacts indicate the loss of AC with AC present terminals marked NO and C are open NC and C are closed When loss of AC occurs terminals marked NO and C are closed NC and C are open AC LOCAL NC NO C Form C dry contacts us...

Page 8: ...te below Outputs are controlled by designated Input 1 IN1 or Input 2 IN2 Output Programming Selection Table pg 5 Maximum line loss or voltage drop tested with 2 5V Loop 1 Loop 2 Loop 3 Loop 4 Used for Class A hook ups to terminate loops originating on OUT1 OUT2 OUT3 and OUT4 respectively C FAULT NC Common trouble input An open circuit across this pair of terminals will cause INP1 and INP2 LEDs to ...

Page 9: ...t is optional All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods Note Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire Fig 6a Fig 6 120VAC 60Hz Input non power limited Supervisory Connection...

Page 10: ...ted wire or equivalent substitute Optional battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods Note Refer to wire handling drawing Fig 6a pg 9 for the proper way to install the CM or FPL jacketed wire Fig 7 AC L N DC BAT DC NC C NO NC C NO AC FAIL NC C NO BAT FAIL AC LOCAL OUT1 OUT2 OUT3 OUT4 INP2 INP1 FAULT RESET NC C NO C FAULT NC DC AUX2 LOOP4 OUT4 OUT3 LOO...

Page 11: ... Fig 8c INP2 INP1 FAULT OUT1 OUT3 IN OUT SYNC STROBE SYNC TEMPORAL NC C NO C FAULT NC AUX2 LOOP4 OUT4 OUT3 LOOP3 LOOP1 OUT1 OUT2 LOOP2 IN1 RET1 IN2 RET2 NC DRY1 C NC DRY2 C AUX1 Addressable control module trigger output These circuits are used to monitor AC and Bat Fail Factory Installed Board Interface Cable AC BAT FAIL AC FAIL DC AC NC C NO NC C NO AC LOCAL NC C NO L N Battery and AC Supervision...

Page 12: ...panel for local annunciation of the trouble condition Note If common trouble input terminals marked C FAULT NC are not used these terminals must be shorted connect jumper to remain inactive For optional hookups see Fig 8b pg 11 Maintenance Unit should be tested at least once a year for the proper operation as follows Output Voltage Test Under normal load conditions the DC output voltage should be ...

Page 13: ...current ratings Alarm mA 0mA mA Alarm mA 0mA mA Alarm mA 0mA mA Alarm mA 0mA mA C Notification Appliances Current must not exceed 10A 10 000mA 0mA mA D Total alarm current mA mA E Total current ratings converted to amperes line D x 001 A A F Number of standby hours 24 for NFPA 72 Chapter 1 1 5 2 5 H G Multiply lines E and F Total stand by AH AH H Alarm sounding period in hours For example 5 minute...

Page 14: ...RHK UL PC2R UL SCRH UL SPSCWVH P UL SRHK R UL P2RHK P UL PC2R P UL SCRH P UL SPSR UL SRK UL P2RHK R UL PC2RH UL SCRH SP UL SPSR P UL SRK P UL P2RK UL PC2RH P UL SCRHK UL SPSRH UL SRK R UL P2RK P UL PC2RH SP UL SCRK UL SPSRH P UL SW UL P2RK R UL PC2RHK UL SCW UL SPSRHK UL SW ALERT UL P2W UL PC2RK UL SCW CLR ALERT UL SPSRK UL SW CLR ALERT UL P2W P UL PC2W UL SCW P UL SPSRK P UL SW P UL P2W SP UL PC2...

Page 15: ...KA24 15 75PWR UL GECG24PWR W UL WSSPK24 15 75AWR AWW UL WSSPKA24 15 75PWW UL GECR24PWR W UL GES24 177WR UL WSSPKB24 15 75PWR UL GCSA24PCR W UL GES24 177WW UL WSSPKB24 15 75PWW UL GCSB24PCR W UL GES24 15 75WR UL WSSPKG24 15 75PWR UL GCSG24PCR W UL GES24 15 75WW UL WSSPKG24 15 75PWW UL GCSR24PCR W UL GEC24 177WR UL WSSPKR24 15 75PWR UL GCCA24PCR W UL GEC24 177WW UL WSSPKR24 15 75PWW UL Potter Amseco...

Page 16: ...S 24MCWH FR UL cUL CH90 24MCC FW UL cUL E90H 24MCCH FW UL cUL LHSW A UL cUL RSS 24MCWH FW UL cUL CH90 24MCCH FR UL cUL EET90 24MCCH FR UL cUL LHSW AL UL cUL RSSA 24MCC NW UL CH90 24MCCH FW UL cUL ET 1010 R UL LHSW N UL cUL RSSA 24MCCH NW UL E50 241575W FW UL cUL ET 1010 W UL LSPSTR UL cUL RSSB 24MCC NW UL E50 24MCWH FR UL cUL ET70 241575W FR UL cUL LSPSTR AL UL cUL RSSB 24MCCH NW UL E50 24MCWH FW ...

Page 17: ...e B 2 below lists relays compatible with AL1042 R1042ULADA AUX output and Outputs 1 8 when programmed as AUX Manufacturer Model Current mA Manufacturer Model Current mA System Sensor PR 1 15 System Sensor R 20T 40 PR 2 30 R 24T 40 PR 3 30 R 10E 23 EOLR 1 30 R 14E 23 R 10T 23 R 20E 40 R 14T 23 R 24E 40 ...

Page 18: ... 18 AL1042ULADA R1042ULADA Installation Guide Notes ...

Page 19: ...m 14 5 368 3mm 1 0 25 4mm 1 5 38 1mm 8 5 215 9mm 18 0 457 2mm 18 0 457 2mm 18 0 457 2mm 1 25 31 75mm 1 25 31 75mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 2 5 63 5mm 2 5 63 5mm 14 5 368 3mm 14 5 368 3mm 4 5 114 3mm 1 0 25 4mm 1 0 25 4mm 1 0 25 4mm 1 0 25 4mm AL1042ULADA Enclosure Dimensions 18 x 14 5 x 4 5 457 2mm x 368 3mm x 114 3mm ...

Page 20: ...9056 website www altronix com e mail info altronix com Lifetime Warranty Made in U S A IIAL1042ULADA R1042ULADA H09U MEMBER R1042ULADA Enclosure Dimensions H x W x D 3 375 x 19 0 x 26 5 85 8mm x 482 6mm x 673 1mm Shown with Z Bracket attached 0 1 2 5mm 1 5 38 1mm 11 175 283 8mm 2 4 61mm 4 57 116 1mm 3 375 85 8mm 26 5 673 1mm 19 482 6mm R 1 27 32 3mm 1 25 4mm 0 55 14mm 3 62 92mm ...

Reviews: