background image

 

- 8 - 

AL1042ULADA / R1042ULADA Installation Guide

Terminal Identification Table:

AL842LGK Logic Board

Terminal Legend

Function/Description

– IN1 +
– IN2 +
(Supervised)

These terminals connect to the 24VDC FACP notification appliance circuit outputs. (Class 

A or Class B) Input trigger voltage is 8-33VDC @ 6.5mA min. Terminal polarity is shown 

in alarm condition. During an alarm condition these inputs will cause the selected outputs 

chosen to drive notification appliances. The designated outputs are set by output switches 

[OUT1 through OUT4] 

(Output Programming Selection Table, pg. 5).

 A trouble condition on 

an output loop will cause the corresponding input to trip the FACP by opening the FACP 

loop. An alarm condition will always override trouble to drive notification appliances. Rated 

12V 6.5mA, 24V 6.5mA.

– RET1 +

– RET2 +

(Supervised)

For Class A hookups these terminal pairs return to FACP NAC1 and/or NAC2. 

For Class B hookups the FACP EOL resistor from the NAC1 and/or NAC2 outputs are 

terminated at these terminals. Optionally, other notification appliances or additional signaling 

circuit power supplies may be connected to these terminals. 

If this option is chosen, the EOL resistor must be terminated at the last device.

NC “DRY1” C 

NC “DRY2” C

(Dry input trigger)

An open across these inputs, will cause the selected outputs chosen to drive notification 

appliances. The designated outputs are set by output switches [OUT1 through OUT4] 

(Output Programming Selection Table, pg. 5).

 Note these inputs are unidirectional and 

will not report a trouble condition to the FACP.

– OUT1 +

– OUT2 +

– OUT3 +

– OUT4 + 

(Supervised)

Notification appliances are connected to these regulated outputs

 (see Application Guide 

pg. 2-4). 

Each power-limited output will supply 2.5A. Total supply current is 10A 

(see 

note below).

 Outputs are controlled by designated Input 1 [IN1] or Input 2 [IN2] 

(Output 

Programming Selection Table, pg. 5). 

Maximum    line loss or voltage drop (tested with 2.5V).

– Loop 1 +

– Loop 2 +

– Loop 3 +

– Loop 4 +

Used for Class A hook-ups to terminate loops originating on

[OUT1], [OUT2], [OUT3], and [OUT4] respectively.

C “FAULT” NC

(Common

trouble input)

An open circuit across this pair of terminals will cause [INP1 and INP2] LEDs

to simultaneously signal a trouble condition back to the FACP. Typically used

to report AC or BAT Fail. 

(Fig. 8b, pg. 11).

NC, C, NO

(Common

trouble output)

These are dry contact trouble outputs that report any general loop/system trouble 

conditions. Typically used to trigger a digital communicator or other reporting devices.

Form “C” contact 1A / 28VDC 0.35 Power Factor 

(Fig. 8, pg. 11)

.

– AUX1 +

This separate 1A max. auxiliary Special Application Power output circuit is disconnected 

from load during AC power failure. See attached list of devices 

(Appendix A, pgs. 14-17)

.

– AUX2 +

This separate auxiliary special application output supplies up to 1A during stand-by and 

alarm condition. Since this output is not disconnected from its load during AC power 

failure use the 

Battery Calculation Worksheet, pg. 12

 to determine battery size and/or 

allowable stand-by and alarm current.

+ DC –

24VDC from power supply.

Note: Unit is equipped with two (2) 1A max. auxiliary outputs: “AUX1” will automatically disconnect when 

AC is lost. “AUX2” will remain battery backed up during power outage. For loads connected to “AUX2” 

please, refer to Battery Stand-by Specifications, pg. 3 for ratings. When loads are connected to the 

“AUX1” and or “AUX2” outputs during alarm condition, the remaining outputs may not exceed 10A total 

alarm current. Example: AUX1 = 1A, AUX2 = 1A, outputs up to 8A. 

  To reset the memory depress the reset button located on the AL842LGK logic board 

(Fig. 8c, pg. 11)

.

  The LED(s) will extinguish.

Note: 

When indicating circuits have restored, trouble memory reset is not required for normal operation.

Summary of Contents for AL1042ULADA

Page 1: ...r R1042ULADA Rack Mountable NAC Power Extender Installation Guide see Application Guide for additional information Rev 062320 More than just power TM Installing Company ________________ Service Rep Name ___________________________________ Address ______________________________________________ Phone ___________________ ...

Page 2: ...wo 2 Class B FACP inputs Two 2 NC dry contact trigger inputs Input Ratings INP1 and INP2 8 30VDC 6 5mA max from FACP 12V 6 5mA 24V 6 5mA from FACP Output Power limited outputs 24VDC voltage regulated power limited outputs 10A max total alarm current 2 5A max current per output Two auxiliary outputs rated at 1A each 1A continuous 1A AC disconnect Programmable supervised indicating circuit outputs F...

Page 3: ...t is intended for indoor use only Note First assemble and install Z Bracket Wire Management Accesory refer to Z Bracket Installation pg 4 Note Rack enclosure must be UL listed and hard wired to a branch electrical circuit via conduit 1 Remove backplane from enclosure prior to installing into rack cabinet do not discard hardware Grounding Connect both grounding lugs Fig 1 to earth ground using 12 A...

Page 4: ...5 Small terminal block wire gauges range from 16 AWG to 24 AWG all others range from 14 AWG to 24 AWG Z Bracket Installation for R1002ULADA Altronix R1002ULADA enclosure includes Z Bracket a convenient and reliable wire management accessory Hardware included Ten 10 bolts and eight 8 lock nuts 1 Carefully unpack Z Bracket Do not discard hardware included Fig 3 pg 4 2 Attach arms to each other using...

Page 5: ...hes of additional open space All wiring methods shall be in accordance with the National Electrical Code NFPA 70 NFPA 72 ANSI and with all local codes and authorities having jurisdiction Battery circuits are not power limited provide 0 25 spacing from power limited circuits and use separate knockout If additional battery enclosure is required it must be UL Listed for the application and mounted wi...

Page 6: ...s of synchronizing the Temporal coded horns synchronizing the flash timing of the strobe allowing audible notification appliances horns and visual notification appliances strobes to be silenced deactivated at the same time System Sensor Sync Mode System Sensor is a registered trademark of Honeywell 1 2 4 3 This mode is designed to work with the System Sensor series of horns strobes and horn strobe...

Page 7: ...l Legend Function Description L N Connect 120VAC to these terminals L to Hot N to Neutral DC 24VDC 10A continuous 10A in alarm non power limited output AC FAIL NO C NC Form C dry contacts indicate the loss of AC with AC present terminals marked NO and C are open NC and C are closed When loss of AC occurs terminals marked NO and C are closed NC and C are open AC LOCAL NC NO C Form C dry contacts us...

Page 8: ...te below Outputs are controlled by designated Input 1 IN1 or Input 2 IN2 Output Programming Selection Table pg 5 Maximum line loss or voltage drop tested with 2 5V Loop 1 Loop 2 Loop 3 Loop 4 Used for Class A hook ups to terminate loops originating on OUT1 OUT2 OUT3 and OUT4 respectively C FAULT NC Common trouble input An open circuit across this pair of terminals will cause INP1 and INP2 LEDs to ...

Page 9: ...t is optional All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods Note Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire Fig 6a Fig 6 120VAC 60Hz Input non power limited Supervisory Connection...

Page 10: ...ted wire or equivalent substitute Optional battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods Note Refer to wire handling drawing Fig 6a pg 9 for the proper way to install the CM or FPL jacketed wire Fig 7 AC L N DC BAT DC NC C NO NC C NO AC FAIL NC C NO BAT FAIL AC LOCAL OUT1 OUT2 OUT3 OUT4 INP2 INP1 FAULT RESET NC C NO C FAULT NC DC AUX2 LOOP4 OUT4 OUT3 LOO...

Page 11: ... Fig 8c INP2 INP1 FAULT OUT1 OUT3 IN OUT SYNC STROBE SYNC TEMPORAL NC C NO C FAULT NC AUX2 LOOP4 OUT4 OUT3 LOOP3 LOOP1 OUT1 OUT2 LOOP2 IN1 RET1 IN2 RET2 NC DRY1 C NC DRY2 C AUX1 Addressable control module trigger output These circuits are used to monitor AC and Bat Fail Factory Installed Board Interface Cable AC BAT FAIL AC FAIL DC AC NC C NO NC C NO AC LOCAL NC C NO L N Battery and AC Supervision...

Page 12: ...panel for local annunciation of the trouble condition Note If common trouble input terminals marked C FAULT NC are not used these terminals must be shorted connect jumper to remain inactive For optional hookups see Fig 8b pg 11 Maintenance Unit should be tested at least once a year for the proper operation as follows Output Voltage Test Under normal load conditions the DC output voltage should be ...

Page 13: ...current ratings Alarm mA 0mA mA Alarm mA 0mA mA Alarm mA 0mA mA Alarm mA 0mA mA C Notification Appliances Current must not exceed 10A 10 000mA 0mA mA D Total alarm current mA mA E Total current ratings converted to amperes line D x 001 A A F Number of standby hours 24 for NFPA 72 Chapter 1 1 5 2 5 H G Multiply lines E and F Total stand by AH AH H Alarm sounding period in hours For example 5 minute...

Page 14: ...RHK UL PC2R UL SCRH UL SPSCWVH P UL SRHK R UL P2RHK P UL PC2R P UL SCRH P UL SPSR UL SRK UL P2RHK R UL PC2RH UL SCRH SP UL SPSR P UL SRK P UL P2RK UL PC2RH P UL SCRHK UL SPSRH UL SRK R UL P2RK P UL PC2RH SP UL SCRK UL SPSRH P UL SW UL P2RK R UL PC2RHK UL SCW UL SPSRHK UL SW ALERT UL P2W UL PC2RK UL SCW CLR ALERT UL SPSRK UL SW CLR ALERT UL P2W P UL PC2W UL SCW P UL SPSRK P UL SW P UL P2W SP UL PC2...

Page 15: ...KA24 15 75PWR UL GECG24PWR W UL WSSPK24 15 75AWR AWW UL WSSPKA24 15 75PWW UL GECR24PWR W UL GES24 177WR UL WSSPKB24 15 75PWR UL GCSA24PCR W UL GES24 177WW UL WSSPKB24 15 75PWW UL GCSB24PCR W UL GES24 15 75WR UL WSSPKG24 15 75PWR UL GCSG24PCR W UL GES24 15 75WW UL WSSPKG24 15 75PWW UL GCSR24PCR W UL GEC24 177WR UL WSSPKR24 15 75PWR UL GCCA24PCR W UL GEC24 177WW UL WSSPKR24 15 75PWW UL Potter Amseco...

Page 16: ...S 24MCWH FR UL cUL CH90 24MCC FW UL cUL E90H 24MCCH FW UL cUL LHSW A UL cUL RSS 24MCWH FW UL cUL CH90 24MCCH FR UL cUL EET90 24MCCH FR UL cUL LHSW AL UL cUL RSSA 24MCC NW UL CH90 24MCCH FW UL cUL ET 1010 R UL LHSW N UL cUL RSSA 24MCCH NW UL E50 241575W FW UL cUL ET 1010 W UL LSPSTR UL cUL RSSB 24MCC NW UL E50 24MCWH FR UL cUL ET70 241575W FR UL cUL LSPSTR AL UL cUL RSSB 24MCCH NW UL E50 24MCWH FW ...

Page 17: ...e B 2 below lists relays compatible with AL1042 R1042ULADA AUX output and Outputs 1 8 when programmed as AUX Manufacturer Model Current mA Manufacturer Model Current mA System Sensor PR 1 15 System Sensor R 20T 40 PR 2 30 R 24T 40 PR 3 30 R 10E 23 EOLR 1 30 R 14E 23 R 10T 23 R 20E 40 R 14T 23 R 24E 40 ...

Page 18: ... 18 AL1042ULADA R1042ULADA Installation Guide Notes ...

Page 19: ...m 14 5 368 3mm 1 0 25 4mm 1 5 38 1mm 8 5 215 9mm 18 0 457 2mm 18 0 457 2mm 18 0 457 2mm 1 25 31 75mm 1 25 31 75mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 2 5 63 5mm 2 5 63 5mm 14 5 368 3mm 14 5 368 3mm 4 5 114 3mm 1 0 25 4mm 1 0 25 4mm 1 0 25 4mm 1 0 25 4mm AL1042ULADA Enclosure Dimensions 18 x 14 5 x 4 5 457 2mm x 368 3mm x 114 3mm ...

Page 20: ...9056 website www altronix com e mail info altronix com Lifetime Warranty Made in U S A IIAL1042ULADA R1042ULADA H09U MEMBER R1042ULADA Enclosure Dimensions H x W x D 3 375 x 19 0 x 26 5 85 8mm x 482 6mm x 673 1mm Shown with Z Bracket attached 0 1 2 5mm 1 5 38 1mm 11 175 283 8mm 2 4 61mm 4 57 116 1mm 3 375 85 8mm 26 5 673 1mm 19 482 6mm R 1 27 32 3mm 1 25 4mm 0 55 14mm 3 62 92mm ...

Reviews: