AL1024NK8QP Series Installation Guide

LED Diagnostics:

AL1024ULXB2 - Power Supply Board

Red (DC)

Green (AC)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery is supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

LINQ8PD and LINQ8PDCB Networkable Power Distribution Module

LED

Flash Codes Description

BAT LOCAL

ON

Charge/Discharge current working properly.

Blinking

Charge/Discharge current on the battery exceed limits.

FACP

ON

Fire Alarm Condition.

OFF

Normal.

AC

ON

AC trouble.

OFF

Normal.

BAT

ON

Battery trouble.

OFF

Normal.

OUT1-OUT8

ON

Output is ON.

OFF

Output is OFF.

Blinking

Output is ON and voltage and/or current exceeds limits.

Terminal Identification:

AL1024ULXB2 - Power Supply Board

Terminal Legend

Function/Description

L, N

Connect 115VAC to these terminals: L to hot, N to neutral 

(Fig. 2a, pg. 5)

.

+ DC –

Factory connected to LINQ8PD(CB) 

(Fig. 2d, pg. 5)

.

AC Fail

NC, C, NO

Used to notify loss of AC power, e.g.connect to audible device or alarm panel. 

Relay normally energized when AC power is present. Contact rating 1A @ 28VDC. 

AC or brownout fail is reported within 1 minute of event. 

To delay reporting for up to 6 hrs., cut “AC Delay” jumper and reset power to unit 

(Fig. 2f, pg. 5)

.

Bat Fail

NC, C, NO

Used to indicate low battery condition, e.g. connect to alarm panel. 

Relay normally energized when DC power is present. Contact rating 1A @ 28VDC. 

A removed battery is reported within 1 minute. 

Battery reconnection is reported within 1 minute.

Low battery threshold: approximately 21VDC 

(Fig. 2b, pg. 5)

.

– BAT +

Stand-by battery connections. Maximum charge current 3.6A 

(Fig. 2c, pg. 5)

.

Summary of Contents for AL1024NK8QP Series

Page 1: ...Eight 8 programmable Class 2 power limited PTC protected outputs Two 2 network controlled Form C relays Built in Charger for sealed lead acid or gel type batteries AL1024NK8QP Series Networkable Dual...

Page 2: ...reatly reducing system downtime and elimi nating unnecessary service calls Stand by Specifications total current shown Output 15 min of Stand by and 5 min of Alarm 4 hr of Stand by and 5 min of Alarm...

Page 3: ...y when AC fails Maximum charge current 3 6A Zero voltage drop when switched over to battery backup Fire Alarm Disconnect LINQ8PD CB Supervised FACP disconnect Latching or Non Latching FACP reset N C o...

Page 4: ...are not used a loss of AC will result in the loss of output voltage When the use of stand by batteries is desired they must be lead acid or gel type Power supply s battery charging circuit is factory...

Page 5: ...proper voltage level AL1024ULXB2 24VDC nominal rated 10A max Battery Test Under normal load conditions check that the battery is fully charged check specified voltage 24VDC 26 4 both at battery termin...

Page 6: ...its Terminal Identification AL1024ULXB2 Power Supply Board Terminal Legend Function Description L N Connect 115VAC to these terminals L to hot N to neutral Fig 2a pg 5 DC Factory connected to LINQ8PD...

Page 7: ...g or Tamper Contact rating 1A 30VDC L AC Fail NC C Relay3 Programmable for AC Fail or AC Fail Battery Fail reporting Contact rating 1A 30VDC power limited M OUT1 to OUT8 24VAC 28VAC or 12VDC 24VDC con...

Page 8: ...24ULXB2 12VDC from VR6 mounted under LINQ8PD CB Battery input factory wired Connect batteries Factory wired supervisory connections power limited Factory wired supervisory connections power limited FA...

Page 9: ...Click the button labeled Submit Network Settings A dialog box will display New network settings will take effect after the server is rebooted Click OK DHCP A After selecting DHCP in the IP Address Me...

Page 10: ...connected to any DC power supply ies or AL1024ULXB2 power supply ies being monitored prior to programing Factory Default settings IP Address 192 168 168 168 User Name admin Password admin 1 Set the st...

Page 11: ...n Alarm ________________ A G Alarm duration Hours 15 Min 0 25 Hour Alarm ________________ H H Battery capacity required for Alarm E F G ________________ AH I Total calculated battery capacity D H ____...

Page 12: ...1 8mm 1 25 31 8mm 0 79 20 1mm 0 91 23 1mm 0 91 23 1mm 15 5 393 7mm 1 1 27 9mm 1 1 27 9mm 1 1 27 9mm 12 23 310 6mm 2 0 50 8mm 2 0 50 8mm 1 25 31 8mm 1 25 31 8mm Enclosure Dimensions BC400 15 5 x 12 x 4...

Reviews: