- 6 -
AL1002ULADAJ
Terminal Identification Table:
Power Supply Board*
Terminal
Legend
Function/Description
L, N
Connect 120VAC to these terminals: L to hot, N to neutral (Fig. 3, pg. 8).
+ DC –
24VDC @ 10A in alarm non power-limited output (Fig. 3, pg. 8).
AC FAIL
NO, C, NC
Form “C” dry contacts used to instantaneously signal the loss AC to local annunciation devices,
with AC present terminals marked NO and C are open, NC and C are closed. When loss of AC
occurs terminals marked NO and C are closed, NC and C are open.
AC LOCAL
NC, NO, C
Form “C” dry contacts used to instantaneously signal the loss AC to local annunciation devices,
with AC present terminals marked NO and C are open, NC and C are closed. When loss of AC
occurs terminals marked NO and C are closed, NC and C are open.
BAT FAIL
NO, C, NC
Form “C” dry contacts used to signal low battery voltage or loss of battery voltage. Under nor-
mal conditions terminals marked NO and C are open, NC and C are closed. During a trouble
condition terminals marked NO and C are closed, and NC and C are open (Fig. 3, pg. 8).
– BAT +
Stand-by battery input (leads provided) (Fig. 3, pg. 8).
*Power Board Parameter Specifications:
• AC Fail condition will report approximately 2 hours after loss of AC. To set AC Delay to 1 minute power
the unit down (AC supply and Battery) prior to changing switch position.
Turn “AC Delay” switch ON for 1 minute or OFF for 2 hours, respectively.
• Low battery condition will report at approximately 20VDC.
• Battery presence detection will report with in 180 seconds after battery remains undetected (missing or
removed). A restored battery will report within 30 seconds.
LED Diagnostics:
Power Supply Board
Red (DC)
Green (AC)
Power Supply Status
ON
ON
Normal operating condition.
ON
OFF
Loss of AC. Stand-by battery is supplying power.
OFF
ON
No DC output.
OFF
OFF
Loss of AC. Discharged or no stand-by battery. No DC output.
AL800LGK9E - Logic Board
LED
OFF
ON
BLINK (LONG)*
BLINK (SHORT)**
Output 1
Normal
Alarm Condition
Trouble Condition
Trouble Condition Memory
Output 2
Normal
Alarm Condition
Trouble Condition
Trouble Condition Memory
Output 3
Normal
Alarm Condition
Trouble Condition
Trouble Condition Memory
Output 4
Normal
Alarm Condition
Trouble Condition
Trouble Condition Memory
Input 1
Normal
Alarm Condition
Trouble Condition
–
Input 2
Normal
Alarm Condition
Trouble Condition
–
Fault
Normal
Alarm Condition
–
–
* Indicates current trouble condition. When trouble (open, short or ground) occurs on a specific output, the
corresponding red output LED, [OUT1-OUT4] will blink. The corresponding green input LED will
blink as well. Loop trouble will report within 30 seconds.
** Indicates trouble condition memory. When a trouble condition restores, the units red output LED,
[OUT1-OUT4] will blink with a shorter and distinctly a different duration.
The green input LEDs will be off (normal condition).
To reset the memory depress the reset button (Fig. 3c, pg. 8). The LED(s) will extinguish.
Note: If indicating circuits have been restored, memory reset is not required for normal operation of the unit.