Altronix AL1002ULADAJ Installation Manual Download Page 4

 

- 4 - 

AL1002ULADAJ

6. Connect FACP output to the desired AL800LGK9E logic board inputs, and notification appliances to the 
  desired AL800LGK9E logic board outputs (see Application Guide).
 

Note: The 2-wire horn/strobe sync mode will only synchronize horns, horn/strobes, strobes with 

  synchronization capability.
7. For connection of smoke detectors, digital dialer see Optional Hookup Diagram, pg. 8.

Class A, Style Z Class B, Style W, X, Y, SW1 & SW2 Settings:

•  For all Class B, Style W, X, Y hookups SW1 and SW2 on the AL800LGK logic board must be turned OFF.
  For all Class A, Style Z hookups SW1 and SW2 on the AL800LGK logic board must be turned ON.

Output Programming Selection Table:

Outputs must be programmed independently (OUT1 - OUT4)

Function

Switch Positions

Descriptions

ON

OFF

Input to Output 
Follower Mode

1

2, 3

Output follows signal it receives from the corresponding 
input (i.e. FACP Sync module - maintains synchronization 
of notification appliance circuit).

Temporal Code 3 Mode

3

1, 2

Enables Temporal Code 3 signal generation output. 
This mode will accept a steady or a pulsing input.

Steady Mode

1, 2, 3

A steady output signal will be generated. 
This mode will accept steady or pulsing input.

For the above modes DIP Switch 4 determines which Input controls the
corresponding output:
Switch 4 in the ON position causes output(s) to be controlled by Input 1.
Switch 4 in the OFF position causes output(s) to be controlled by Input 2.

Sync Mode Selection Table:

Function

Switch Positions

Descriptions

ON

OFF

Amseco 
Sync Mode*

1, 3,

4

2

This mode is designed to work with the Amseco series of horns, 
strobes, and horn/strobes to provide a means of synchronizing 
the Temporal-coded horns, synchronizing the flash timing of the 
strobe, and silencing the horns of the horn/strobe combination over 
a two-wire circuit while leaving strobes active.

Faraday 
Sync Mode*

2, 4

1, 3

This mode is designed to work with the Faraday series of horns, 
strobes, and horn/strobes to provide a means of synchronizing the 
Temporal-coded horns, synchronizing the flash timing of the strobe, 
and silencing the horns of the horn/strobe combination over a two-
wire circuit while leaving strobes active.

Gentex

®

 

Sync Mode*

Gentex is a registered 
trademark of 
Gentex Corporation.

1, 2,

3, 4

This mode is designed to work with the Gentex

®

 series of horns, 

strobes, and horn/strobes to provide a means of synchronizing 
the Temporal-coded horns, synchronizing the flash timing of the 
strobe, and silencing the horns of the horn/strobe combination 
over a two-wire circuit while leaving strobes active.

System Sensor

®

Sync Mode*

System Sensor is a 
registered trademark of 
Honeywell.

1, 2, 4

3

This mode is designed to work with the System Sensor

®

 series of 

horns, strobes, and horn/strobes to provide a means of synchroniz-
ing the Temporal-coded horns, synchronizing the one-second flash 
timing of the strobe, and silencing the horns of the horn/strobe 
combination over a two-wire circuit while leaving strobes active.

CooperWheelock

®

Sync Mode*

CooperWheelock is a 
registered trademark of 
Cooper Wheelock.

2, 3, 4

1

This mode is designed to work with the CooperWheelock series of 
horns, strobes, and horn/strobes to provide a means of synchronizing 
the Temporal-coded horns, synchronizing the one-second flash tim-
ing of the strobe, and silencing the horns of the horn/strobe combina-
tion over a two-wire circuit while leaving strobes active.

*Note: The AL1002ULADAJ will only synchronize horns, horn/strobes and strobes that contain synchronization 
capability. Contact signal manufacturer for more detailed info. 
The same synchronization mode must be selected for all outputs

Note: It is required to control visual notification appliances (strobes) via Input 1 (IN1) and audible 
notification appliances (horns) via Input 2 (IN2). This allows audible notification appliances (horns) 
to be silenced while visual notification appliances (strobes) continue to operate. 

AL800LGK9E Board

Output DIP Switches

INPUT SELECT

TEMPORAL

STROBE SYNC

IN>OUT SYNC

Summary of Contents for AL1002ULADAJ

Page 1: ...Rev 101413 More than just power TM Altronix Corp 140 58th St Brooklyn NY AL1002ULADAJ NAC Power Extender Installation Guide see Application Guide for additional information...

Page 2: ...nel and should conform to all local codes Agency Listings UL Listed Control Units for Fire Protective Signaling Systems UL 864 MEA NYC Department of Buildings Approved CSFM California State Fire Marsh...

Page 3: ...h the top two keyholes in the enclosure Install two upper fasteners and screws in the wall with the screw heads protruding Place the enclosure s upper keyholes over the two upper screws level and secu...

Page 4: ...h the Faraday series of horns strobes and horn strobes to provide a means of synchronizing the Temporal coded horns synchronizing the flash timing of the strobe and silencing the horns of the horn str...

Page 5: ...ugh OUT4 Output Programming Selection Table pg 4 Note these inputs are unidirectional and will not report a trouble condition to the FACP OUT1 OUT2 OUT3 OUT4 Supervised Notification appliances are con...

Page 6: ...will report at approximately 20VDC Battery presence detection will report with in 180 seconds after battery remains undetected missing or removed A restored battery will report within 30 seconds LED D...

Page 7: ...use of conduit is optional All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional battery enclosure must be mounted adjacent to t...

Page 8: ...pervised Input from Power Supply BAT FAIL AC FAIL DC AC NC C NO NC C NO AC LOCAL NC C NO L N 6 3A 250V Digital Communicator or Local Annunciator Dry output Contact Form C contacts Power Limited Output...

Page 9: ...nnunciation of the trouble condition Note If common trouble input terminals marked C FAULT NC are not used these terminals must be shorted connect jumper to remain inactive For optional hookups see Fi...

Page 10: ...0mA mA Alarm mA 0mA mA Alarm mA 0mA mA Alarm mA 0mA mA C Notification Appliances Current must not exceed 10A 10 000mA 0mA mA D Total alarm current mA mA E Total current ratings converted to amperes l...

Page 11: ...WGESG24 75PWLPR W UL SSPKA24 15 75PWW UL WGES24 75WRLP WWLP UL WGESR24 75PWLPR W UL SSPKA24 15 75AWR UL WGEC24 75WR WW UL WGECA24 75PWLPR W UL SSPKA24 15 75AWW UL WGEC24 75PWR PWW UL WGECB24 75PWLPR...

Page 12: ...UL P2WH SP UL PC2WH SP UL SCWHK UL SPSW ALERT UL SWH SP UL P2WHK UL PC2WHK UL SCWK UL SPSW CLR ALERT UL SWHK UL P2WHK P UL PC2WK UL SPSCR UL SPSW P UL SWHK P UL P2WK UL PC4R UL SPSCRH UL SPSWH UL SWK...

Page 13: ...CH90 24MCC FW UL cUL E90H 24MCCH FW UL cUL LHSW A UL cUL RSS 24MCWH FW UL cUL CH90 24MCCH FR UL cUL EET90 24MCCH FR UL cUL LHSW AL UL cUL RSSA 24MCC NW UL CH90 24MCCH FW UL cUL ET 1010 R UL LHSW N UL...

Page 14: ...oelectric 0 12 50 2412 12 volt Photoelectric 0 12 77 2412AT 12 volt Photoelectric 0 12 58 2412TH 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2424TH Photoelectric 0 10 41 2451 Photoelectri...

Page 15: ...AL1002ULADAJ 15 Notes...

Page 16: ...12R MEMBER 1 5 38 1mm 1 0 25 4mm 4 5 114 3mm 1 0 25 4mm 1 0 25 4mm 1 25 31 75mm 1 25 31 75mm 1 0 25 4mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 8 5 215 9mm 18 0 457 2mm 18 0 457 2mm 18 0 457 2mm 6...

Reviews: