Altronix AL1002ULADAJ Installation Manual Download Page 2

 

- 2 - 

AL1002ULADAJ

Overview:

Altronix AL1002ULADAJ is an extremely cost-effective 10A remote power supply/battery charger. It may be 
connected to any 12 or 24 volt Fire Alarm Control Panel (FACP). Primary applications include Notification 
Appliance Circuit (NAC such as strobes and horns) expansion support to meet ADA requirements. It also pro-
vides auxiliary power to support system accessories. The unit delivers electronically regulated and filtered 24 
volt power to Class B, Style W, Y or Class A, Style Z NAC loop circuits. Additionally, a separate 1.0A auxiliary 
output for four (4)-wire smoke detectors is available. The 10A max. alarm current can be divided between the 
four (4) outputs for powering NAC devices. Each output is rated at 2.5A max., and can be independently pro-
grammed for Steady, Temporal Code 3 or Strobe Synchronization. All outputs may be programmed for Input to 
Output Follower Mode (output will follow input). In non-alarm condition independent loop supervision for Class 
A, Style Z and/or Class B, Style W, Y FACP NAC circuits is provided. In the event of a loop trouble, the FACP 
will be notified via the steered input (Input 1 or Input 2). In addition, there are common trouble output terminals 
(NC, C, NO) which are used to indicate general loop/system trouble. A common trouble input is provided for 
optional NC (normally closed) devices to report trouble to the FACP. Two (2) FACP signaling outputs can be 
employed and directed to control supervision and power delivery to any combination of the four (4) outputs. 

Note: The information in this document is valid for models AL1002ULADAJ and AL1002UL2ADAJ. 
Model AL1002ULADAJ is equivalent to model AL1002UL2ADAJ.

Specifications:

WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture. 
This installation should be made by qualified service personnel and should conform to all local codes.

 Agency  Listings:

•  UL Listed Control Units for Fire Protective
  Signaling Systems (UL 864). 
•  MEA - NYC Department of Buildings Approved.
•  CSFM - California State Fire Marshal Approved.
•  FM - Factory Mutual Approved.
•  NFPA 72 Compliant.

Input:

•   Power input 120VAC 60Hz, 5.0A.
•  Two (2) Class A, Style Z or two (2) Class B,
  Style W, Y FACP inputs.
•  Two (2) NC dry contact trigger inputs.

Output:

•  Class 2 Rated power-limited outputs.
•  24VDC @10A max total alarm current.
•  2.5A max current per output.
•  Separate 1.0A auxiliary output.
•  Programmable supervised indicating circuit outputs:
  Four (4) Class B, Style W, Y or Two (2) Class A,
  Style Z or One (1) Class A, Style Z and Two (2) 
  Class B, Style W, Y (see Application Guide).
•    Thermal and short circuit protection with auto reset. 

Battery Backup:

•    Built-in charger for sealed lead acid or gel type 

batteries. 

•    Automatic switchover to stand-by battery when 
  AC Fails.
•  Zero voltage drop when switching over to 
  battery backup. 

Supervision: 

•   AC fail supervision (form “C” contact, 1A/28VDC). 
  Factory set for 2 hours with optional 1 minute  
  delay setting (field selectable).
•  Instant local AC trouble reporting relay
  (form “C” contact, 1A / 28VDC).
•   Battery presence and low battery supervision 
  (form “C” contact, 1A / 28VDC).

Visual Indicators: 

•   Input and output status LED indicators. 

Special Features: 

•  2-wire horn/strobe Sync mode allows audible 
  notification appliances (horns) to be silenced 
  while visual notification appliances (strobes) 
  continue to operate. 
•  Sync protocols include Potter/Amseco, Faraday,
 Gentex

®

, System Sensor

®

, and CooperWheelock

®

•  Temporal Code 3, Steady Mode, Input to Output  
  Follower Mode (maintains synchronization of 
  notification appliances circuit).
•  Compatible with 12VDC or 24VDC fire panels. 
•   Output loop supervision steered to Input 1 or Input 2.
•  Signal circuit trouble memory (helps identify 
  intermittent loop problems).
•  Common trouble input and output.
•  Ground fault detection. 
•   Unit includes power supply, red enclosure, 
  cam lock, and battery leads.

Enclosure Dimensions 

(approx. H x W x D)

:

  18” x 14.5” x 4.5” 
  (457.2mm x 368.3mm x 114.3mm).

Summary of Contents for AL1002ULADAJ

Page 1: ...Rev 101413 More than just power TM Altronix Corp 140 58th St Brooklyn NY AL1002ULADAJ NAC Power Extender Installation Guide see Application Guide for additional information...

Page 2: ...nel and should conform to all local codes Agency Listings UL Listed Control Units for Fire Protective Signaling Systems UL 864 MEA NYC Department of Buildings Approved CSFM California State Fire Marsh...

Page 3: ...h the top two keyholes in the enclosure Install two upper fasteners and screws in the wall with the screw heads protruding Place the enclosure s upper keyholes over the two upper screws level and secu...

Page 4: ...h the Faraday series of horns strobes and horn strobes to provide a means of synchronizing the Temporal coded horns synchronizing the flash timing of the strobe and silencing the horns of the horn str...

Page 5: ...ugh OUT4 Output Programming Selection Table pg 4 Note these inputs are unidirectional and will not report a trouble condition to the FACP OUT1 OUT2 OUT3 OUT4 Supervised Notification appliances are con...

Page 6: ...will report at approximately 20VDC Battery presence detection will report with in 180 seconds after battery remains undetected missing or removed A restored battery will report within 30 seconds LED D...

Page 7: ...use of conduit is optional All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional battery enclosure must be mounted adjacent to t...

Page 8: ...pervised Input from Power Supply BAT FAIL AC FAIL DC AC NC C NO NC C NO AC LOCAL NC C NO L N 6 3A 250V Digital Communicator or Local Annunciator Dry output Contact Form C contacts Power Limited Output...

Page 9: ...nnunciation of the trouble condition Note If common trouble input terminals marked C FAULT NC are not used these terminals must be shorted connect jumper to remain inactive For optional hookups see Fi...

Page 10: ...0mA mA Alarm mA 0mA mA Alarm mA 0mA mA Alarm mA 0mA mA C Notification Appliances Current must not exceed 10A 10 000mA 0mA mA D Total alarm current mA mA E Total current ratings converted to amperes l...

Page 11: ...WGESG24 75PWLPR W UL SSPKA24 15 75PWW UL WGES24 75WRLP WWLP UL WGESR24 75PWLPR W UL SSPKA24 15 75AWR UL WGEC24 75WR WW UL WGECA24 75PWLPR W UL SSPKA24 15 75AWW UL WGEC24 75PWR PWW UL WGECB24 75PWLPR...

Page 12: ...UL P2WH SP UL PC2WH SP UL SCWHK UL SPSW ALERT UL SWH SP UL P2WHK UL PC2WHK UL SCWK UL SPSW CLR ALERT UL SWHK UL P2WHK P UL PC2WK UL SPSCR UL SPSW P UL SWHK P UL P2WK UL PC4R UL SPSCRH UL SPSWH UL SWK...

Page 13: ...CH90 24MCC FW UL cUL E90H 24MCCH FW UL cUL LHSW A UL cUL RSS 24MCWH FW UL cUL CH90 24MCCH FR UL cUL EET90 24MCCH FR UL cUL LHSW AL UL cUL RSSA 24MCC NW UL CH90 24MCCH FW UL cUL ET 1010 R UL LHSW N UL...

Page 14: ...oelectric 0 12 50 2412 12 volt Photoelectric 0 12 77 2412AT 12 volt Photoelectric 0 12 58 2412TH 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2424TH Photoelectric 0 10 41 2451 Photoelectri...

Page 15: ...AL1002ULADAJ 15 Notes...

Page 16: ...12R MEMBER 1 5 38 1mm 1 0 25 4mm 4 5 114 3mm 1 0 25 4mm 1 0 25 4mm 1 25 31 75mm 1 25 31 75mm 1 0 25 4mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 8 5 215 9mm 18 0 457 2mm 18 0 457 2mm 18 0 457 2mm 6...