Rev. 101413
More than just power.
TM
Altronix Corp.
140 58th St. Brooklyn, NY
AL1002ULADAJ
NAC Power Extender
Installation Guide
(see Application Guide for additional information)
Page 1: ...Rev 101413 More than just power TM Altronix Corp 140 58th St Brooklyn NY AL1002ULADAJ NAC Power Extender Installation Guide see Application Guide for additional information...
Page 2: ...nel and should conform to all local codes Agency Listings UL Listed Control Units for Fire Protective Signaling Systems UL 864 MEA NYC Department of Buildings Approved CSFM California State Fire Marsh...
Page 3: ...h the top two keyholes in the enclosure Install two upper fasteners and screws in the wall with the screw heads protruding Place the enclosure s upper keyholes over the two upper screws level and secu...
Page 4: ...h the Faraday series of horns strobes and horn strobes to provide a means of synchronizing the Temporal coded horns synchronizing the flash timing of the strobe and silencing the horns of the horn str...
Page 5: ...ugh OUT4 Output Programming Selection Table pg 4 Note these inputs are unidirectional and will not report a trouble condition to the FACP OUT1 OUT2 OUT3 OUT4 Supervised Notification appliances are con...
Page 6: ...will report at approximately 20VDC Battery presence detection will report with in 180 seconds after battery remains undetected missing or removed A restored battery will report within 30 seconds LED D...
Page 7: ...use of conduit is optional All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional battery enclosure must be mounted adjacent to t...
Page 8: ...pervised Input from Power Supply BAT FAIL AC FAIL DC AC NC C NO NC C NO AC LOCAL NC C NO L N 6 3A 250V Digital Communicator or Local Annunciator Dry output Contact Form C contacts Power Limited Output...
Page 9: ...nnunciation of the trouble condition Note If common trouble input terminals marked C FAULT NC are not used these terminals must be shorted connect jumper to remain inactive For optional hookups see Fi...
Page 10: ...0mA mA Alarm mA 0mA mA Alarm mA 0mA mA Alarm mA 0mA mA C Notification Appliances Current must not exceed 10A 10 000mA 0mA mA D Total alarm current mA mA E Total current ratings converted to amperes l...
Page 11: ...WGESG24 75PWLPR W UL SSPKA24 15 75PWW UL WGES24 75WRLP WWLP UL WGESR24 75PWLPR W UL SSPKA24 15 75AWR UL WGEC24 75WR WW UL WGECA24 75PWLPR W UL SSPKA24 15 75AWW UL WGEC24 75PWR PWW UL WGECB24 75PWLPR...
Page 12: ...UL P2WH SP UL PC2WH SP UL SCWHK UL SPSW ALERT UL SWH SP UL P2WHK UL PC2WHK UL SCWK UL SPSW CLR ALERT UL SWHK UL P2WHK P UL PC2WK UL SPSCR UL SPSW P UL SWHK P UL P2WK UL PC4R UL SPSCRH UL SPSWH UL SWK...
Page 13: ...CH90 24MCC FW UL cUL E90H 24MCCH FW UL cUL LHSW A UL cUL RSS 24MCWH FW UL cUL CH90 24MCCH FR UL cUL EET90 24MCCH FR UL cUL LHSW AL UL cUL RSSA 24MCC NW UL CH90 24MCCH FW UL cUL ET 1010 R UL LHSW N UL...
Page 14: ...oelectric 0 12 50 2412 12 volt Photoelectric 0 12 77 2412AT 12 volt Photoelectric 0 12 58 2412TH 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2424TH Photoelectric 0 10 41 2451 Photoelectri...
Page 15: ...AL1002ULADAJ 15 Notes...
Page 16: ...12R MEMBER 1 5 38 1mm 1 0 25 4mm 4 5 114 3mm 1 0 25 4mm 1 0 25 4mm 1 25 31 75mm 1 25 31 75mm 1 0 25 4mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 8 5 215 9mm 18 0 457 2mm 18 0 457 2mm 18 0 457 2mm 6...