Altronix ACM220 Series Installation Manual Download Page 7

 

ACM220 Series Installation Guide 

- 7 -

Fig. 2 - ACM220 Series Configuration

L      G     N

AC

+BAT-

DC

+ DC 

-

BAT FAIL  NC    C   NO  NC   C    NO   AC  FAIL  

BAT

OFF - 24V

ON - 12

V

ON

OUTPUT 1     OUTPUT 2         OUTPUT 3         OUTPUT 4          OUTPUT 5        OUTPUT 6         OUTPUT 7        OUTPUT 8

NC  C  NO COM NC C NO COM  NC  C  NO COM NC C NO COM  NC  C  NO COM NC C NO COM  NC  C NO COM NC C NO COM

 IN  GND IN GND IN GND IN GND

IN  GND IN GND IN  GND IN GND

1            2           3          4

5           6           7           8

 INPUT

TRIGGER

10A 250V

+INP-  T + RET-

NO  C   NC

FACP            INTERFACE

Power   Control

-      +      -      

+

F1                   F2                  F3                   F4                   F5                   F6                   F7                   F8

MAIN

TRG

FACP

1     2     3     4

1     2     3     4

O N

O N

1     2     3     4

1     2     3     4

O N

O N

Fire Alarm

Interface

DC Output to Devices 

Battery and AC 

Supervision Circuit

Observe

Polarity

Inputs

Ground Lug

Unswitched

220VAC

power mains

CAUTION: De-energize unit prior to servicing. 
For continued protection against fire hazard replace fuse with the same type and rating.

CAUTION: Optional  rechargeable stand-by batteries must match
the power supply output voltage setting.

Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.

Power Supply Board

Optional Rechargeable

12VDC Stand-by Battery

Optional Rechargeable

12VDC Stand-by Battery

Summary of Contents for ACM220 Series

Page 1: ...______________ Phone ___________________ ACM220 Series Access Power Controllers with Power Supplies Models Include For a red enclosure add an R suffix to the part e g AL1024ACMR220 Installation Guide...

Page 2: ...Current is determined by the power supply connected not to exceed a maximum of 10A total Eight 8 Access Control System trigger inputs Input options a Eight 8 normally open NO inputs b Eight 8 open col...

Page 3: ...t 24VDC Output Voltage and Stand by Specification Charts below Output Voltage and Stand by Specification Charts AL400ACM220 Voltage Switch Position Stand by Battery 4 hr Stand by 5 mins Alarm 24 hr St...

Page 4: ...onding switch SW1 SW8 OFF To disable FACP disconnect for an output turn the corresponding switch SW1 SW8 ON a Normally Open NO input For non latching hook up Fig 5 pg 8 For latching hook up see Fig 6...

Page 5: ...it BAT FAIL NC C NO Used to indicate low battery condition e g connect to alarm panel Relay normally energized when DC power is present Contact rating 1A 28VDC A removed battery is reported within 5 m...

Page 6: ...Strike Electromagnetic Door Holders FACP Fire Alarm Control Panel UL Listed Power Supply For this application corresponding fuse F8 must be removed Keypad AC or DC Power Supply req d AC or DC Power Su...

Page 7: ...F1 F2 F3 F4 F5 F6 F7 F8 MAIN TRG FACP 1 2 3 4 1 2 3 4 O N O N 1 2 3 4 1 2 3 4 O N O N Fire Alarm Interface DC Output to Devices Battery and AC Supervision Circuit Observe Polarity Inputs Ground Lug U...

Page 8: ...olarity is referenced in alarm condition Fig 3 Optional hook up using two 2 isolated power supply inputs J2 J1 CUT JUMPERS J1 AND J2 ISOLATED POWER INPUT 12 OR 24 VAC OR VDC LOCK POWER ISOLATED POWER...

Page 9: ...RG FACP Fig 7 Normally Closed Non Latching FACP trigger input Fig 8 Normally Closed Latching FACP trigger input with reset This output has not been evaluated by UL Fig 6 Normally Open FACP Latching tr...

Page 10: ...nsumption Alarm __________ A G Alarm duration Hours example 15 Min 0 25 Hour Alarm __________ H H Battery capacity required for Alarm E F G __________ AH I Total calculated battery capacity D H ______...

Page 11: ...ACM220 Series Installation Guide 11 Notes...

Page 12: ...nclosure Dimensions H x W x D approximate 15 5 x 12 x 4 5 393 7mm x 304 8mm x 114 3mm 1 5 38 1mm 1 5 38 1mm 4 615 117 2mm 4 615 117 2mm 1 5 38 1mm 1 5 38 1mm 4 615 117 2mm 4 615 117 2mm 1 75 44 5mm 1...

Reviews: