AL1024ACM220 Battery Size Calculation Worksheet:

A. AL1024ACM220 internal current consumption 

(stand-by) 

__________ 0.35A

B. Load current consumption 

(stand-by) 

__________ A

C. Stand-by time required (Hours) 

 

__________ H

D. Battery capacity required for stand-by 

(A+B)*C 

__________ AH

E. AL1024ACM220 internal power consumption 

(Alarm) 

__________ 0.35A

F. Load current consumption 

(Alarm) 

__________ A

G. Alarm duration (Hours, example: 15 Min. = 0.25 Hour) 

(Alarm) 

__________ H

H. Battery capacity required for Alarm 

(E+F)*G 

__________ AH

I.  Total calculated battery capacity 

D+H 

__________ AH

J. Battery capacity required 

I*1.8 (safety factor)  __________ AH

Note:

  AL1024ACM220 power supply is designed to work with batteries up to 65AH. Please note, line [I] 

   

must not exceed 36AH. You have to reduce either stand-by current consumption or stand-by time in

   

order to comply with requirement.

To determine actual battery size please round line [J] to the nearest larger standard battery size.

Summary of Contents for ACM220 Series

Page 1: ...______________ Phone ___________________ ACM220 Series Access Power Controllers with Power Supplies Models Include For a red enclosure add an R suffix to the part e g AL1024ACMR220 Installation Guide...

Page 2: ...Current is determined by the power supply connected not to exceed a maximum of 10A total Eight 8 Access Control System trigger inputs Input options a Eight 8 normally open NO inputs b Eight 8 open col...

Page 3: ...t 24VDC Output Voltage and Stand by Specification Charts below Output Voltage and Stand by Specification Charts AL400ACM220 Voltage Switch Position Stand by Battery 4 hr Stand by 5 mins Alarm 24 hr St...

Page 4: ...onding switch SW1 SW8 OFF To disable FACP disconnect for an output turn the corresponding switch SW1 SW8 ON a Normally Open NO input For non latching hook up Fig 5 pg 8 For latching hook up see Fig 6...

Page 5: ...it BAT FAIL NC C NO Used to indicate low battery condition e g connect to alarm panel Relay normally energized when DC power is present Contact rating 1A 28VDC A removed battery is reported within 5 m...

Page 6: ...Strike Electromagnetic Door Holders FACP Fire Alarm Control Panel UL Listed Power Supply For this application corresponding fuse F8 must be removed Keypad AC or DC Power Supply req d AC or DC Power Su...

Page 7: ...F1 F2 F3 F4 F5 F6 F7 F8 MAIN TRG FACP 1 2 3 4 1 2 3 4 O N O N 1 2 3 4 1 2 3 4 O N O N Fire Alarm Interface DC Output to Devices Battery and AC Supervision Circuit Observe Polarity Inputs Ground Lug U...

Page 8: ...olarity is referenced in alarm condition Fig 3 Optional hook up using two 2 isolated power supply inputs J2 J1 CUT JUMPERS J1 AND J2 ISOLATED POWER INPUT 12 OR 24 VAC OR VDC LOCK POWER ISOLATED POWER...

Page 9: ...RG FACP Fig 7 Normally Closed Non Latching FACP trigger input Fig 8 Normally Closed Latching FACP trigger input with reset This output has not been evaluated by UL Fig 6 Normally Open FACP Latching tr...

Page 10: ...nsumption Alarm __________ A G Alarm duration Hours example 15 Min 0 25 Hour Alarm __________ H H Battery capacity required for Alarm E F G __________ AH I Total calculated battery capacity D H ______...

Page 11: ...ACM220 Series Installation Guide 11 Notes...

Page 12: ...nclosure Dimensions H x W x D approximate 15 5 x 12 x 4 5 393 7mm x 304 8mm x 114 3mm 1 5 38 1mm 1 5 38 1mm 4 615 117 2mm 4 615 117 2mm 1 5 38 1mm 1 5 38 1mm 4 615 117 2mm 4 615 117 2mm 1 75 44 5mm 1...

Reviews: