Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

Output Voltage Test:

  Under normal load conditions, the DC output voltage should be checked for proper 

 

 

voltage level 

(Output Voltage and Stand-by Specification Charts, pg. 3).

Battery Test:

 

Under normal load conditions check that the battery is fully charged, check specified 

 

 

voltage at the battery terminals and at the board terminals marked [+ BAT –] to 

 

 

ensure that there is no break in the battery connection wires.

Note:

  AL400XB2V, AL600XB220, AL1012XB220 (Power Supply Board) maximum charge current is 0.7A. 

 AL1024XB2V 

(Power Supply Board) maximum charge current is 3.6A.

Expected battery life is 5 years, however it is recommended to change batteries within 4 years or less if necessary.

Terminal Identification Tables:

Power Supply Board

Terminal Legend

Function/Description

L, N

Connect 220VAC, 50/60Hz to these terminals: L to hot, N to neutral.

+ DC –

AL400ACM220 - 12VDC @ 4A or 24VDC @ 3A to ACM8 board. 

AL600ACM220 - 12VDC/24VDC @ 6A to ACM8 board.

AL1012ACM220 - 12VDC @ 10A to ACM8 board.

AL1024ACM220 - 24VDC @ 10A to ACM8 board.

AC FAIL

NC, C, NO

Used to notify loss of AC power, e.g. connect to audible device or alarm panel. 

Relay normally energized when AC power is present. Contact rating 1A @ 28VDC. 

AC or brownout fail is reported within 1 minute of event. 

To delay reporting of up to 6 hrs. cut “AC delay” jumper and reset power to unit.

BAT FAIL

NC, C, NO

Used to indicate low battery condition, e.g. connect to alarm panel. Relay normally 

energized when DC power is present. Contact rating 1A @ 28VDC. A removed battery is 

reported within 5 minutes. Battery reconnection is reported within 1 minute.

Low battery threshold:

12VDC output threshold set @ approximately 10.5VDC (N/A for AL1024ACM220), 

24VDC output threshold set @ approximately 21VDC (N/A for AL1012ACM220).

+ BAT –

Stand-by battery connections. AL400XB2V, AL600XB220 and AL1012XB220

(Power Supply Board) maximum charge current is 0.7A. 

AL1024XB2V (Power Supply Board) maximum charge current is 3.6A.

ACM8 Access Power Controller

Terminal Legend

Function/Description

– Power +

12VDC or 24VDC input from power supply board.

– C

These terminals can be connected to a separate power supply to provide isolated 

operating power for the ACM8 (jumpers J1and J2 must be removed).

TRIGGER INPUT 1 - 

INPUT 8 IN, GND

From normally open and/or open collector sink trigger inputs

(request to exit buttons, exit pir’s, etc.).

OUTPUT 1 -

OUTPUT 8

NC, C, NO, COM

12 to 24 volts AC/DC trigger controlled outputs:

Fail-Safe [NC positive (+) & COM Negative (–)],

Fail-Secure [NO positive (+) & COM Negative (–)],

Auxiliary output [C positive (+) & COM Negative (–)]

(When using AC power supplies polarity need not be observed),

NC, C, NO become form “C” 5A 24VAC/VDC rated dry outputs when fuses are removed. 

Contacts shown in a non-triggered state.

FACP INTERFACE

T, + INPUT –

Fire Alarm Interface trigger input from FACP. Trigger inputs can be normally open,

normally closed from an FACP output circuit 

(Fig. 4 through 8, pgs. 8-9)

.

FACP INTERFACE

NC, C, NO

Form “C” relay contact rated @ 1A 28VDC for alarm reporting.

Summary of Contents for ACM220 Series

Page 1: ...______________ Phone ___________________ ACM220 Series Access Power Controllers with Power Supplies Models Include For a red enclosure add an R suffix to the part e g AL1024ACMR220 Installation Guide...

Page 2: ...Current is determined by the power supply connected not to exceed a maximum of 10A total Eight 8 Access Control System trigger inputs Input options a Eight 8 normally open NO inputs b Eight 8 open col...

Page 3: ...t 24VDC Output Voltage and Stand by Specification Charts below Output Voltage and Stand by Specification Charts AL400ACM220 Voltage Switch Position Stand by Battery 4 hr Stand by 5 mins Alarm 24 hr St...

Page 4: ...onding switch SW1 SW8 OFF To disable FACP disconnect for an output turn the corresponding switch SW1 SW8 ON a Normally Open NO input For non latching hook up Fig 5 pg 8 For latching hook up see Fig 6...

Page 5: ...it BAT FAIL NC C NO Used to indicate low battery condition e g connect to alarm panel Relay normally energized when DC power is present Contact rating 1A 28VDC A removed battery is reported within 5 m...

Page 6: ...Strike Electromagnetic Door Holders FACP Fire Alarm Control Panel UL Listed Power Supply For this application corresponding fuse F8 must be removed Keypad AC or DC Power Supply req d AC or DC Power Su...

Page 7: ...F1 F2 F3 F4 F5 F6 F7 F8 MAIN TRG FACP 1 2 3 4 1 2 3 4 O N O N 1 2 3 4 1 2 3 4 O N O N Fire Alarm Interface DC Output to Devices Battery and AC Supervision Circuit Observe Polarity Inputs Ground Lug U...

Page 8: ...olarity is referenced in alarm condition Fig 3 Optional hook up using two 2 isolated power supply inputs J2 J1 CUT JUMPERS J1 AND J2 ISOLATED POWER INPUT 12 OR 24 VAC OR VDC LOCK POWER ISOLATED POWER...

Page 9: ...RG FACP Fig 7 Normally Closed Non Latching FACP trigger input Fig 8 Normally Closed Latching FACP trigger input with reset This output has not been evaluated by UL Fig 6 Normally Open FACP Latching tr...

Page 10: ...nsumption Alarm __________ A G Alarm duration Hours example 15 Min 0 25 Hour Alarm __________ H H Battery capacity required for Alarm E F G __________ AH I Total calculated battery capacity D H ______...

Page 11: ...ACM220 Series Installation Guide 11 Notes...

Page 12: ...nclosure Dimensions H x W x D approximate 15 5 x 12 x 4 5 393 7mm x 304 8mm x 114 3mm 1 5 38 1mm 1 5 38 1mm 4 615 117 2mm 4 615 117 2mm 1 5 38 1mm 1 5 38 1mm 4 615 117 2mm 4 615 117 2mm 1 75 44 5mm 1...

Reviews: