Communications Paramaters:

All communications are at 9600 baud, 8 Data bits, No Parity, 1 Stop bits. ( 9600 8N1 )

Overview:

The DE-1500 is compliant to the Modicon Modbus RTU standard. The DE-1500
supports 

DE-1500 Display Modbus Communications

Register reads and data is duplicated for the 30000’s & 40000’s address range.
Maximum number of registers that can be read at one time has been limited to 32.

Address List:

Decimal point location for Analog Channel 25;

40120

Decimal point location for Analog Channel 24;
range from 0-3

40119

Decimal point location for Analog Channel 23;
range from 0-3

40118

Decimal point location for Analog Channel 22;
range from 0-3

40117

Decimal point location for Analog Channel 21;
range from 0-3

40116

Decimal point location for Analog Channel 20;
range from 0-3. 0 = no decimal place, 1 = 1
decimal place etc.

40115

Current Channel 91; range from 0 to 100

40110

Current Channel 90; range from 0 to 100

40109

RPM Channel 30; range from 0 to 9999

40108

Analog Channel 27; range from -9999 to 9999

40107

Analog Channel 26; range from -9999 to 9999

40106

Analog Channel 25; range from -9999 to 9999

40105

Analog Channel 24; range from -9999 to 9999

40104

Analog Channel 23; range from -9999 to 9999

40103

Analog Channel 22; range from -9999 to 9999

40102

Analog Channel 21; range from -9999 to 9999

40101

Analog Channel 20; range from -9999 to 9999

40100

Bit 0 = Low fault shutdown.  Bit 1 = High fault
shutdown.  Only applicable when fault exists.

40009

Reserved 

40008

Reserved 

40007

Reserved 

40006

Reserved 

40005

Status (10-13, 20-27, 30) For a shutdown on that
channel.  00 = TIMERS ACTIVE, 
01 = RUNNING, 60=STOP.

40004

Null, will always read 0 

40003

Hourmeter; range from 0-65535

40002

Summary of Contents for DE-1500

Page 1: ...nsists of the node number associated with the particular DE 1500 The range is from 01 to 99 SPACE 4 7 ASCII value 20h COMMAND 5 6 The letters D and L which stand for data log REQUESTED RECORD NUMBER 8...

Page 2: ...L4 222 223 2 CR LF 202 221 20 EGT1 1022 F VIEW scn 1 L3 200 201 2 CR LF 180 199 20 MAT1 145 F VIEW scn 1 L2 178 179 2 CR LF 158 177 20 VAC1 67 9 PSIG VIEW scn 1 L1 156 157 2 CR LF 136 155 20 MAP1 12...

Page 3: ...on label name Location 12 16 occupy the analog value 100 4 Location 17 contains a space Location 18 20 contain the units of measure PSI TABLE II 203 204 2 CR LF 198 202 177 202 26 NOT USED SERV MSG 3...

Page 4: ...MSG 6 259 260 2 CR LF 254 258 233 258 26 NOT USED SERV MSG 5 231 232 2 CR LF 226 230 205 230 26 NOT USED SERV MSG 4 The CHARACTER LOCATION for the service messages consists of 20 characters which was...

Page 5: ...elow Key Press Table 0 NONE no keypress returns current display C CANCEL TIMERS T TEST R RESET S STOP P VIEW N NEXT U UP UNITS V VIEW CHAN 1 F1 A RIGHT TENS X ENTER L LEFT TENS 2 F2 M MENU D DOWN UNIT...

Page 6: ...point location for Analog Channel 20 range from 0 3 0 no decimal place 1 1 decimal place etc 40115 Current Channel 91 range from 0 to 100 40110 Current Channel 90 range from 0 to 100 40109 RPM Channel...

Page 7: ...two byte Modbus RTU CRC Response NN 17 07 D E 1 5 0 0 CRC CRC NN node number 17 ID fucntion code 07 number of bytes to follow DE 1500 seven byte ASCII ID string CRC CRC two byte Modbus RTU CRC Stop R...

Page 8: ...14 MENU 15 DOWN UNITS 16 ESC Response NN 20 88 20bytes 1st line of display CR LF 20 bytes 2nd line CR LF 20bytes 3rd line CR LF 20bytes 4th line CR LF CRC CRC NN node number 20 KP fucntion code 88 nu...

Reviews: