Altherma EKHBHE008AA3V3 Operation Manual Download Page 6

Operation manual

5

EKHBH/XE008AA3V3

Indoor unit for air to water heat pump system and options

4PW48442-1B

Description of the operation modes

Space heating operation (

h

)

In this mode, heating will be activated as required by the water
temperature set point. The set point can be set manually (refer to

"Manual operation" on page 5

) or weather dependent (refer to

"Selecting weather dependent set point operation (only in heating
mode)" on page 6

).

Startup (

d

)

At the start of a heating operation, the pump is not started until a
certain refrigerant heat exchanger temperature is reached. This
guarantees correct startup of the heat pump. During startup, icon

d

 is displayed.

Defrost (

d

)

In space heating operation or domestic water heating operation,
freezing of the outdoor heat exchanger may occur due to low outdoor
temperature. If this risk occurs, the system goes into defrost
operation. It reverses the cycle and takes heat from the indoor
system to prevent freezing of the outdoor system. After a maximum
of 8 minutes of defrost operation, the system returns to space
heating operation.

Space cooling operation (

c

)

In this mode, cooling will be activated as required by the water
temperature set point.

Domestic water heating operation (

w

)

In this mode, the indoor unit will deliver hot water to the domestic hot
water tank when the space heating or space cooling operation has
reached its temperature set point. 

Quiet mode operation (

s

)

Quiet mode operation means that the outdoor unit works at reduced
capacity so that the noise produced by the outdoor unit drops. This
implies that the indoor heating and cooling capacity will also drop.
Beware of this when a certain level of heating is required indoors.

Controller operations

Manual operation

In manual operation, the user manually controls the settings of the
installation. The last setting remains active until the user changes it or
until the schedule timer forces another setting (refer to 

"Schedule

timer operation" on page 6

).

As the controller can be used for a wide variety of installations, it is
possible to select a function which is not available on your
installation. In that case the message 

n

 will appear.

Switching on and setting space cooling (

c

) and heating (

h

)

1

Use the 

=

 button to select space cooling (

c

) or space heating

(

h

).

Icon 

c

 or 

h

 appears on the display as well as the corresponding

water temperature set point.

2

Use the 

bi

  and 

bj

  buttons to set the desired water

temperature.

Temperature range for heating: 25°C to 55°C
The temperature for heating can be set as low as 15°C (see

"Field settings" on page 11

). However, the temperature for

heating should only be set lower than 25°C during
commissioning of the installation. When set lower than 25°C,
only the backup heater will operate.
In order to avoid overheating, space heating is not operable
when the outdoor ambient temperature rises above a certain
temperature (as set through field setting [4-02], refer to 

"Field

settings" on page 11

).

Temperature range for cooling: 5°C to 22°C

3

Switch on the unit by pushing the 

y

 button.

The operation LED 

0

 lights up.

Selection and setting of domestic water heating (

w

)

1

Use the 

v

 button to activate domestic water heating (

w

).

Icon 

w

 appears on the display.

2

Use the 

wi

  or 

wj

  button to display the actual

temperature set point and subsequently, to set the correct
temperature.

The actual temperature set point only appears on the display
after pressing one of the buttons 

wi

 or 

wj

. If no button is

pressed for 5 seconds, the temperature set point will
automatically disappear from the display again.
Temperature range for domestic water heating: 30°C to 80°C

3

Press the 

v

 button to deactivate domestic water heating (

w

).

Icon 

w

 disappears from the display.

NOTE

The space cooling temperature set point can only
be set manually (refer to 

"Manual operation" on

page 5

).

Switching between space heating and space
cooling operation can only be done by pressing
the 

=

 button or by an external room thermostat.

Space cooling operation is not possible if the
installation is a heating only installation.

NOTE

Refer to the warning mentioned in the chapter

"Introduction" on page 

2

  concerning domestic

water heating.

The domestic hot water temperature set point can
only be set manually (refer to 

"Manual operation"

on page 5

).

Any domestic water heating operation is
impossible when the domestic hot water tank is
not installed.

When the 

w

  icon is blinking, hot water is

delivered to the domestic hot water tank by the
solar kit option and not by the

AD

 

indoor unit. Refer to

installation manual of the EKSOLHW solar kit.

NOTE

In heating mode (

h

), the water temperature set point

can also be weather dependent (icon 

a

 is shown).

This means that the controller calculates the water
temperature set point based on the outdoor
temperature.

In this case, instead of showing the water temperature
set point, the controller shows the "shift value" which
can be set by the user. This shift value is the
temperature difference between the temperature set
point calculated by the controller and the real set point.
E.g. a positive shift value means that the real
temperature set point will be higher than the calculated
set point.

NOTE

When the unit is connected to an external room
thermostat, buttons 

=

 and 

y

 are not operable and

the icon 

e

  is shown. In this case, the external room

thermostat switches the unit on or off and determines
the operation mode (space cooling or space heating).

Summary of Contents for EKHBHE008AA3V3

Page 1: ...OPERATION MANUAL EKHBHE008AA3V3 EKHBXE008AA3V3 Indoor unit for air to water heat pump system and options For installation WITH restricted power supply condition 6 kW ...

Page 2: ...an coil units floor heating low temperature radiators the Daikin domestic hot water tanks and the solar option kit The AD indoor unit range consists of two main versions a heating cooling EKHBX version and a heating only EKHBH version Both versions are delivered with an integrated backup heater The backup heater only serves as a backup in case of malfunctioning of the outdoor unit or when the unit...

Page 3: ...l start up for example Refer to Initial start up at low outdoor ambient temperatures and Re start at low outdoor ambient temperatures in the installation manual During heating operation the water temperature becomes too low and drops ot of the operation range Refer to Checking the water volume and expansion vessel pre pressure in the installation manual to minimize the backup heater operation Malf...

Page 4: ...on will never be displayed If the solar option is installed and active the w icon will be blinking 4 EXTERNAL CONTROL ICON e This icon indicates that an external room thermostat with higher priority is controlling your installation This external room thermostat can start and stop the space heating cooling operation and change the operation mode cooling heating When an external room thermostat with...

Page 5: ...able the schedule timer The button is also used to program the controller The function of the button depends on the actual status of the controller or on previous actions carried out by the operator If the controller is set in permission level 3 refer to Field settings on page 11 the schedule timer button will not be operable 31 TIME ADJUST BUTTON pi and pj These multi purpose buttons are used to ...

Page 6: ...ating should only be set lower than 25 C during commissioning of the installation When set lower than 25 C only the backup heater will operate In order to avoid overheating space heating is not operable when the outdoor ambient temperature rises above a certain temperature as set through field setting 4 02 refer to Field settings on page 11 Temperature range for cooling 5 C to 22 C 3 Switch on the...

Page 7: ...t a scheduled time Five actions can be programmed per mode These actions are repeated daily 3 Booster heating refer to Programming quiet mode booster heating or domestic water heating on page 9 Allow or disallow booster heating at a scheduled time Five actions can be programmed per mode These actions are repeated daily 4 Domestic water heating refer to Programming quiet mode booster heating or dom...

Page 8: ...er If 2 or more actions are programmed for the same day and at the same time only the action with the highest action number will be executed You can always alter add or remove the programmed actions later When programming heating actions time and set point cooling actions are added automatically at the same time but with the predefined default cooling set point Conversely when programming cooling ...

Page 9: ... to select x to switch cooling or heating and the controller off 9 set the temperature by means of the bi and bj buttons a to select automatic temperature calculation only in heating mode 10 Use the pi and pj buttons to set the correct action time 11 Repeat steps 8 to 10 to program the other actions of the selected day When all actions have been programmed make sure that the display shows the high...

Page 10: ...ulting space cooling or space heating is carried out as follows 1 Use the button to select the operation mode cooling or heating you want to consult 2 Press the button The actual mode is blinking 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to consult by means of the pi and pj buttons The selected day is blinking 5 Press the button to c...

Page 11: ...y will show the next day e g 2 if 1 was selected first This indicates that the day has been copied You can return to step 2 by pressing the pr button Deleting one or more programmed actions Deleting one or more programmed actions is done at the same time as storing the programmed actions When all actions for one day have been programmed make sure that the display shows the highest action number yo...

Page 12: ...seconds in normal mode Note that no indication on the user interface is given When level 2 3 is selected the actual permission level either level 2 or level 3 is determined by the field setting 0 00 1 Weather dependent set point heating operation only The weather dependent set point field settings define the parameters for the weather dependent operation of the unit When weather dependent operatio...

Page 13: ...erature Shift value The disinfection function field settings must be configured by the installer according to national and local regulations TDHW Domestic hot water temperature TU User set point temperature as set on the user interface TH High set point temperature 2 03 t Time Space cooling heating always has priority over the disinfection function The disinfection function is only possible when t...

Page 14: ...revents the booster heater from repeatedly turning on and off i e chattering to maintain the domestic hot water set point temperature Note the booster heater will turn back on when the domestic hot water temperature drops 2 C fixed value below the booster heater OFF temperature 7 00 Domestic hot water step length temperature difference above the domestic hot water set point temperature before the ...

Page 15: ...aving water temperature for cooling operation 9 03 Cooling set point lower limit minimum leaving water temperature for cooling operation 9 04 Overshoot setting defines how much the water temperature may rise above the setpoint before the compressor stops This function is only applicable in heating mode C Solar priority mode C 00 For information concerning the EKSOLHW solar kit refer to the install...

Page 16: ...rity temperature 00 Not applicable Do not change the default value 1 01 Not applicable Do not change the default value 0 02 Not applicable Do not change the default value 0 03 Not applicable Do not change the default value 0 04 Not applicable Do not change the default value 10 6 DT for domestic water heating 00 Start 5 1 20 1 C 01 Stop 2 2 10 1 C 7 Domestic hot water step length 00 Domestic hot wa...

Page 17: ... readout 00 Software version Read only 01 EEPROM version Read only 02 Unit model identification Read only 03 Liquid refrigerant temperature Read only C 04 Inlet water temperature Read only C First code Second code Setting name Installer setting at variance with default value Default value Range Step Unit Date Value Date Value ...

Page 18: ...eck if the clock and the day of the week are set correctly correct if necessary DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done in accordance with relevant local and national legislation Do not try to dismantle the system yourself the dismantling of the system treatment of the refrigerant of oil and other parts must be done by a qua...

Page 19: ......