Altherma EKHBHE008AA3V3 Operation Manual Download Page 5

EKHBH/XE008AA3V3

Indoor unit for air to water heat pump system and options

4PW48442-1B

Operation manual

4

17. BOOSTER HEATER ICON 

m

This icon indicates that the booster heater is active. The booster
heater provides auxiliary heating for the domestic hot water
tank.

The booster heater is located in the domestic hot water tank.

The icon is not used when the domestic hot water tank is not
installed.

18. PUMP ICON 

é

This icon indicates that the circulation pump is active.

19. OUTDOOR TEMPERATURE DISPLAY 

u

When this icon is flashing, the outdoor ambient temperature is
displayed.

20. WEATHER DEPENDENT SET POINT ICON 

a

This icon indicates that the controller will adapt the temperature
set point automatically, based on the outdoor ambient
temperature.

21. TEMPERATURE ICON 

b

This icon is displayed when the water outlet temperature of the
indoor unit, the outdoor ambient temperature and the domestic
hot water tank temperature are shown.

The icon is also displayed when the temperature set point is set
in schedule timer programming mode.

22. TEST OPERATION ICON 

t

This icon indicates that the unit runs in test mode. Refer to the
installation manual.

23. FIELD SET CODE 

;

This code represents the code from the field set list. Refer to the
installation manual.

24. ERROR CODE 

:

This code refers to the error code list and is for service purposes
only. Refer to the installation manual.

25. SPACE HEATING/COOLING BUTTON 

=

This button allows manual switching between cooling or heating
mode (provided the unit is not a heating only unit).

When the unit is connected with an external room thermostat,
this button is not operable and the icon 

e

 is shown.

26. DOMESTIC WATER HEATING BUTTON 

v

This button enables or disables heating of the domestic water.

This button is not used when the domestic hot water tank is not
installed.

27. WEATHER DEPENDENT SET POINT BUTTON 

ba

This button enables or disables the weather dependent set point
function which is available in space heating operation only.

If the controller is set in permission level 2 or 3 (refer to 

"Field

settings" on page 11

), the weather dependent set point button

will not be operable.

28. INSPECTION/TEST OPERATION BUTTON 

z

This button is used for installation purposes and changing field
settings. Refer to 

"Field settings" on page 11

.

29. PROGRAMMING BUTTON 

<

This multi-purpose button is used to program the controller. The
function of the button depends on the actual status of the
controller or on previous actions carried out by the operator.

30. SCHEDULE TIMER BUTTON 

r

/

p

The main function of this multi-purpose button is to
enable/disable the schedule timer.

The button is also used to program the controller. The function of
the button depends on the actual status of the controller or on
previous actions carried out by the operator.

If the controller is set in permission level 3 (refer to 

"Field

settings" on page 11

), the schedule timer button will not be

operable.

31. TIME ADJUST BUTTON 

pi

 and 

pj

These multi-purpose buttons are used to adjust the clock, to
toggle between temperatures (water outlet temperature of the
indoor unit, outdoor ambient temperature and domestic hot
water temperature) and in schedule timer programming mode.

32. TEMPERATURE ADJUST BUTTONS 

bi

 and 

bj

These multi-purpose buttons are used to adjust the current set
point in normal operation mode or in schedule timer
programming mode. In weather dependent set point mode the
buttons are used to adjust the shift value. Finally, the buttons are
also used to select the weekday while setting the clock.

33. DOMESTIC HOT WATER TEMPERATURE ADJUST BUTTONS

wbi

 and 

wbj

These buttons are used to adjust the current set point of the
domestic hot water temperature.

The buttons are not used when the domestic hot water tank is
not installed.

34. QUIET MODE BUTTON 

s

This button enables or disables quiet mode.

If the controller is set in permission level 2 or 3 (refer to 

"Field

settings" on page 11

), the quiet mode button will not be

operable.

Setting up the controller

After initial installation, the user can set the clock and day of the
week.

The controller is equipped with a schedule timer that enables the
user to schedule operations. Setting the clock and day of the week is
required to be able to use the schedule timer.

Setting the clock

1

Hold down the 

pr

 button for 5 seconds.

The clock read-out and the day of week indicator start flashing.

2

Use the 

pi

 and 

pj

 buttons to adjust the clock.

Each time the 

pi

  or 

pj

  button is pressed, the time will

increase/decrease by 1 minute. Keeping the 

pi

  or 

pj

button pressed will increase/decrease the time by 10 minutes.

3

Use the 

bi

 or 

bj

 button to adjust the day of the week.

Each time the 

bi

  or 

bj

  button is pressed the next or

previous day is displayed.

4

Press the 

<

 button to confirm the current set time and day of the

week.

To leave this procedure without saving, press the 

pr

 button.

If no button is pressed for 5 minutes the clock and day of the
week will return to their previous setting.

Setting the schedule timer

To  set the schedule timer, refer to chapter 

"Programming and

consulting the schedule timer" on page 7

.

NOTE

Remark that pushing the 

y

 button has no influence

on the domestic water heating. Domestic water
heating is only switched on or off by means of the 

v

button.

NOTE

The clock needs to be set manually. Adjust the setting
when switching from summertime to wintertime and
vice versa.

Summary of Contents for EKHBHE008AA3V3

Page 1: ...OPERATION MANUAL EKHBHE008AA3V3 EKHBXE008AA3V3 Indoor unit for air to water heat pump system and options For installation WITH restricted power supply condition 6 kW ...

Page 2: ...an coil units floor heating low temperature radiators the Daikin domestic hot water tanks and the solar option kit The AD indoor unit range consists of two main versions a heating cooling EKHBX version and a heating only EKHBH version Both versions are delivered with an integrated backup heater The backup heater only serves as a backup in case of malfunctioning of the outdoor unit or when the unit...

Page 3: ...l start up for example Refer to Initial start up at low outdoor ambient temperatures and Re start at low outdoor ambient temperatures in the installation manual During heating operation the water temperature becomes too low and drops ot of the operation range Refer to Checking the water volume and expansion vessel pre pressure in the installation manual to minimize the backup heater operation Malf...

Page 4: ...on will never be displayed If the solar option is installed and active the w icon will be blinking 4 EXTERNAL CONTROL ICON e This icon indicates that an external room thermostat with higher priority is controlling your installation This external room thermostat can start and stop the space heating cooling operation and change the operation mode cooling heating When an external room thermostat with...

Page 5: ...able the schedule timer The button is also used to program the controller The function of the button depends on the actual status of the controller or on previous actions carried out by the operator If the controller is set in permission level 3 refer to Field settings on page 11 the schedule timer button will not be operable 31 TIME ADJUST BUTTON pi and pj These multi purpose buttons are used to ...

Page 6: ...ating should only be set lower than 25 C during commissioning of the installation When set lower than 25 C only the backup heater will operate In order to avoid overheating space heating is not operable when the outdoor ambient temperature rises above a certain temperature as set through field setting 4 02 refer to Field settings on page 11 Temperature range for cooling 5 C to 22 C 3 Switch on the...

Page 7: ...t a scheduled time Five actions can be programmed per mode These actions are repeated daily 3 Booster heating refer to Programming quiet mode booster heating or domestic water heating on page 9 Allow or disallow booster heating at a scheduled time Five actions can be programmed per mode These actions are repeated daily 4 Domestic water heating refer to Programming quiet mode booster heating or dom...

Page 8: ...er If 2 or more actions are programmed for the same day and at the same time only the action with the highest action number will be executed You can always alter add or remove the programmed actions later When programming heating actions time and set point cooling actions are added automatically at the same time but with the predefined default cooling set point Conversely when programming cooling ...

Page 9: ... to select x to switch cooling or heating and the controller off 9 set the temperature by means of the bi and bj buttons a to select automatic temperature calculation only in heating mode 10 Use the pi and pj buttons to set the correct action time 11 Repeat steps 8 to 10 to program the other actions of the selected day When all actions have been programmed make sure that the display shows the high...

Page 10: ...ulting space cooling or space heating is carried out as follows 1 Use the button to select the operation mode cooling or heating you want to consult 2 Press the button The actual mode is blinking 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to consult by means of the pi and pj buttons The selected day is blinking 5 Press the button to c...

Page 11: ...y will show the next day e g 2 if 1 was selected first This indicates that the day has been copied You can return to step 2 by pressing the pr button Deleting one or more programmed actions Deleting one or more programmed actions is done at the same time as storing the programmed actions When all actions for one day have been programmed make sure that the display shows the highest action number yo...

Page 12: ...seconds in normal mode Note that no indication on the user interface is given When level 2 3 is selected the actual permission level either level 2 or level 3 is determined by the field setting 0 00 1 Weather dependent set point heating operation only The weather dependent set point field settings define the parameters for the weather dependent operation of the unit When weather dependent operatio...

Page 13: ...erature Shift value The disinfection function field settings must be configured by the installer according to national and local regulations TDHW Domestic hot water temperature TU User set point temperature as set on the user interface TH High set point temperature 2 03 t Time Space cooling heating always has priority over the disinfection function The disinfection function is only possible when t...

Page 14: ...revents the booster heater from repeatedly turning on and off i e chattering to maintain the domestic hot water set point temperature Note the booster heater will turn back on when the domestic hot water temperature drops 2 C fixed value below the booster heater OFF temperature 7 00 Domestic hot water step length temperature difference above the domestic hot water set point temperature before the ...

Page 15: ...aving water temperature for cooling operation 9 03 Cooling set point lower limit minimum leaving water temperature for cooling operation 9 04 Overshoot setting defines how much the water temperature may rise above the setpoint before the compressor stops This function is only applicable in heating mode C Solar priority mode C 00 For information concerning the EKSOLHW solar kit refer to the install...

Page 16: ...rity temperature 00 Not applicable Do not change the default value 1 01 Not applicable Do not change the default value 0 02 Not applicable Do not change the default value 0 03 Not applicable Do not change the default value 0 04 Not applicable Do not change the default value 10 6 DT for domestic water heating 00 Start 5 1 20 1 C 01 Stop 2 2 10 1 C 7 Domestic hot water step length 00 Domestic hot wa...

Page 17: ... readout 00 Software version Read only 01 EEPROM version Read only 02 Unit model identification Read only 03 Liquid refrigerant temperature Read only C 04 Inlet water temperature Read only C First code Second code Setting name Installer setting at variance with default value Default value Range Step Unit Date Value Date Value ...

Page 18: ...eck if the clock and the day of the week are set correctly correct if necessary DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done in accordance with relevant local and national legislation Do not try to dismantle the system yourself the dismantling of the system treatment of the refrigerant of oil and other parts must be done by a qua...

Page 19: ......

Page 20: ...4PW48442 1B Copyright Daikin ...

Reviews: