Altherma EKHBH016AA Installation Manual Download Page 23

EKHBH/ EKSWW150-300V3/Z2

Indoor unit for air to water heat pump and sanitary warm water tank for air to water heat pump system

4PW36978-1C

Installation manual

20

[1-02] Set point at low ambient temperature (Lo_Ti): the
target outgoing water temperature when the outdoor
temperature equals or drops below the low ambient
temperature (Lo_A). 
Note that the Lo_Ti value should be higher than Hi_Ti, as for
colder outdoor temperatures (i.e. Lo_A) warmer water is
required.

[1-03] Set point at high ambient temperature (Hi_Ti): the
target outgoing water temperature when the outdoor
temperature equals or rises above the high ambient
temperature (Hi_A). 
Note that the Hi_Ti value should be lower than Lo_Ti, as for
warmer outdoor temperatures (i.e. Hi_A) less warm water
suffices.

[2] Disinfection function

Applies only to installations with a sanitary water tank.

The disinfection function disinfects the sanitary water tank by
periodically heating the sanitary water to a specific temperature.

[2-00] Operation interval: day(s) of the week at which the
sanitary water should be heated.

[2-01] Status: defines whether the disinfection function is
turned on (1) or off (0).

[2-02] Start time: time of the day at which the sanitary water
should be heated.

[2-03] Set point: high water temperature to be reached.

[2-04] Interval: time period defining how long the set point
temperature should be maintained.

[3] Auto restart

When power returns after a power supply failure, the auto restart
function reapplies the user interface settings at the time of the power
supply failure.

Note that with the function disabled the schedule timer will not be
activated when power returns to the unit after a power supply failure.
Press the 

pr

 button to enable the schedule timer again.

[3-00] Status: defines whether the auto restart function is
turned ON (0) or OFF (1).

[4] Backup heater operation and space heating off temperature

Backup heater operation 

— 

Applies only to units with optional

backup heater installed.
The operation of the backup heater can altogether be enabled or
disabled, or it can be disabled depending on operation of the booster
heater.

[4-00] Status: defines whether backup heater operation is
enabled (1) or disabled (0).

[4-01] Priority: defines whether backup heater and booster
heater can operate simultaneously (0), or if the booster
heater operation has priority over the backup heater
operation (1).

Space heating off temperature

[4-02] Space heating off temperature: outdoor temperature
above which space heating is turned off, to avoid
overheating.

[5] Equilibrium temperature and space heating priority
temperature

Equilibrium temperature  — The 'equilibrium temperature' field
settings apply to operation of the optional backup heater. When the
equilibrium temperature function is enabled, operation of the backup
heater is restricted to low outdoor temperatures, i.e. when the
outdoor temperature equals or drops below the specified equilibrium
temperature. When the function is disabled, operation of the backup
heater is possible at all outdoor temperatures. Enabling this function
reduces the working time of the backup heater.

[5-00] Equilibrium temperature status: specifies whether the
equilibrium temperature function is enabled (1) or
disabled (0).

[5-01] Equilibrium temperature: outdoor temperature below
which operation of the backup heater is allowed.

Space heating priority temperature  (applies only to installations
with a sanitary water tank) — The 'space heating priority
temperature' field settings apply to operation of the 3-way valve and
the booster heater in the sanitary water tank.
When the space heating priority function is enabled, it is assured that
the full capacity of the heat pump is used for space heating only
when the outdoor temperature equals or drops below the specified
space heating priority temperature, i.e. low outdoor temperature. In
this case the sanitary water will only be heated by the booster heater.

[5-02] Space heating priority status: specifies whether space
heating priority is enabled (1) or disabled (0).

T

t

Target water temperature

T

A

Ambient (outdoor) temperature

= Shift value

The disinfection function field settings must be configured
by the installer according to national and local regulations.

T

SWW

Sanitary water temperature

T

U

User set point temperature (as set on the user interface)

T

H

High set point temperature [2-03]

t

Time

Lo_Ti

Lo_A

Hi_A

T

A

T

t

+ 05

00

– 05

Hi_Ti

Shift value

00.00

22.00

24.00

01.00

23.00

t

T

SWW

T

H

T

U

[2-02]

[2-03]

[2-04]

NOTE

It is therefore recommended to leave the auto restart
function enabled.

NOTE

When the priority field setting is set to ON (1),
space heating performance of the system
might be decreased at low outdoor
temperatures, since in case of sanitary water
heating demand the backup heater will not be
available for space heating (space heating will
still be provided by the heat pump).

When the priority field setting is set to OFF (0),
make sure that electrical power consumption
does not exceed supply limits.

Summary of Contents for EKHBH016AA

Page 1: ...INSTALLATION MANUAL EKHBH016AA EKHBX016AA EKSWW150V3 EKSWW200V3 EKSWW300V3 EKSWW200Z2 EKSWW300Z2 Indoor unit for air to water heat pump and sanitary warm water tank for air to water heat pump system ...

Page 2: ... 5 6 7 1 2 3 5 4 3 4 5 350 300 35 48 35 668 895 922 39 361 48 142 101 235 235 502 500 23 30 4 7 400 90 200 1 2 3 4 5 3 4 FBSP 1 2 FBSP 0 40 0 H 300 630 220 110 1 2 3 4 5 6 Ø580 3 4 FBSP 3 4 FBSP 3 4 FBSP 1150 1 1 4 FBSP 1 1 4 MBSP 96 30 90 1 2 3 5 4 ...

Page 3: ...ß den Vorschriften der 03 conformément aux stipulations des 04 overeenkomstig de bepalingen van 05 siguiendo las disposiciones de 06 secondo le prescrizioni per 07 Ì ٠ÚËÛË Ùˆv È Ù Íˆv Ùˆv 08 de acordo com o previsto em 09 в соответствии с положениями 10 under iagttagelse af bestemmelserne i 11 enligt villkoren i 12 gitt i henhold til bestemmelsene i 13 noudattaen määräyksiä 14 za dodržení ustan...

Page 4: ...nit is the indoor part of the reversible air to water Daikin ERHQ heat pumps These units are designed for wall mounted indoor installation and used for both heating and cooling applications The units can be combined with Daikin fan coil units floor heating applications low temperature radiators and sanitary water heating applications Heating cooling units and heating only units The indoor unit ran...

Page 5: ...acity 2 Required heating capacity site dependent 3 Additional heating capacity provided by the backup heater 4 Equilibriumtemperature can be set through the user interface refer to Field settings on page 19 TA Ambient outdoor temperature PH Heating capacity NOTE Especially for the United Kingdom For installation of an EKSWWU sanitary water tank refer to the installation manual supplied with the EK...

Page 6: ...ed in series with another heat source e g gas boiler it shall be made sure that the return water temperature to the heat exchanger does not exceed 55 C Daikin shall not be held liable for any damage resulting from not observing this rule 1 Outdoor unit 6 Collector field supply 2 Indoor unit 7 Shut off valve 3 Heat exchanger FHL1 3 Floor heating loop field supply 4 Pump 5 Shut off valve T Room ther...

Page 7: ... be done by the user interface on the indoor unit Sanitary heating Sanitary water heating is as described under Application 2 on page 3 Application 4 Space cooling and heating application without a room thermostat connected to the indoor unit but with a heating only room thermostat controlling the floor heating and a cooling heating thermostat controlling the fan coil units Heating is provided thr...

Page 8: ...internals e g to connect the field wiring the switch box service panel can be removed Thereto loosen the front screws and unhitch the switch box service panel 1 Outdoor unit 14 Motorised 2 way valve for activation of the room thermostat field supply 2 Indoor unit 3 Heat exchanger 4 Pump FCU1 3 Fan coil unit with thermostat field supply 5 Shut off valve 6 Collector field supply FHL1 3 Floor heating...

Page 9: ...r unit 11 Water inlet connection 12 Water outlet connection 13 Drain and fill valves 14 Water filter The water filter removes dirt from the water to prevent damage to the pump or blockage of the evaporator The water filter should be cleaned on a regular base See Maintenance on page 25 15 Expansion vessel drain valve The drain valve of the expansion vessel allows draining the remaining water in the...

Page 10: ...IP switch SS2 The DIP switch SS2 provides 4 toggle switches to configure certain installation parameters See DIP switch settings overview on page 17 11 X13A socket The X13A socket receives the K3M connector only for installations with sanitary water tank 12 X9A socket The X9A socket receives the thermistor connector only for installations with sanitary water tank 13 Pump fuse FU2 in line fuse 14 P...

Page 11: ...ries see Accessories on page 2 are enclosed Bring the unit as close as possible to its final installation position in its original package in order to prevent damage during transport The indoor unit weighs approximately 55 kg and should be lifted by two persons using the two lifting bars provided Requirement Value Maximum allowable refrigerant piping length between outdoor unit and indoor unit 75 ...

Page 12: ...tallation of the unit check the following points The maximum water pressure is 3 bar Two shut off valves are delivered with the unit To facilitate service and maintenance install one at the water inlet and one at the water outlet of the indoor unit Mind position of the shut off valves Orientation of the integrated drain valves is important for servicing See figure 4 Drain taps must be provided at ...

Page 13: ...ections must be made in accordance with the outlook diagram delivered with the unit respecting the water in and outlet If air moisture or dust gets in the water circuit problems may occur Therefore always take into account the following when connecting the water circuit Use clean pipes only Hold the pipe end downwards when removing burrs Cover the pipe end when inserting it through a wall so that ...

Page 14: ...essure relief valve Water quality must be according to EN directive 98 83 EC WARNING A main switch or other means for disconnection having a contact separation in all poles must be incorporated in the fixed wiring in accordance with relevant local and national legislation Switch off the power supply before making any connections All field wiring and components must be installed by a licensed elect...

Page 15: ... all wiring specifications Connection of the indoor unit power supply and communication cable Power circuit and cable requirements Power supply for the indoor unit is to be provided through the outdoor unit Data communication with the outdoor unit is provided through the same cable For all guidelines and specifications regarding field wiring between the indoor unit and the outdoor unit please refe...

Page 16: ...wer supply 230 V AC Maximum running current 100 mA Wiring the 2 way valve 1 Using the appropriate cable connect the valve control cable to the X2M terminal as shown on the wiring diagram 2 Fix the cable s with cable ties to the cable tie mountings to ensure strain relief Wiring the 3 way valve 1 Using the appropriate cable connect the valve control cable to the appropriate terminals as shown on th...

Page 17: ...e water outlet temperature during use Immediately after installation the sanitary water tank must be flushed with fresh water This procedure must be repeated at least once a day the first 5 consecutive days after installation In case of limited consumption of hot water e g at holiday residences or at houses that are occasionally not occupied the sanitary water tank installation must be fitted with...

Page 18: ...el make sure the wall is sturdy In both cases make sure the tank is mounted level 3 Apply thermal paste to the thermistor and insert the thermistor as deep as possible in the thermistor socket Fix using the nut provided Connecting the water circuits 1 Connect the water inlet and water outlet 2 Connect the hot and cold water supply tubes 3 Connect the pressure relief valve field supply opening pres...

Page 19: ...e PCB 6 Connect the prewired earth wires of the terminal block X3M and X4M to the earthing screw 7 Connect the booster heater power supply and thermal protection cable field supply to terminal X4M earth 1 2 and X2M 13 14 8 Connect the booster heater power supply cable to the terminal block X3M 9 Fix the cables to the cable tie mountings with cable ties to ensure strain relief 10 Set DIP switch SS2...

Page 20: ...talled Not installed Default 3 Room thermostat connection see Room thermostat installation configuration on page 17 Room thermostat connected No room thermostat connected Default 4 This setting a decides the operation mode when there is a simultaneous demand for more space heating cooling and sanitary water heating a only applicable in case DIP switch 2 ON Heating cooling Sanitary Default When no ...

Page 21: ...box on loose connections or damaged electrical components 6 Fixation Check that the unit is properly fixed to avoid abnormal noises and vibrations when starting up the unit 7 Damaged equipment Check the inside of the unit on damaged components or squeezed pipes 8 Refrigerant leak Check the inside of the unit on refrigerant leakage If there is a refrigerant leak call your local Daikin dealer 9 Powe...

Page 22: ...o exit FIELD SET MODE Detailed description 0 User permission level If required certain user interface buttons can be made unavailable for the user Three permission levels are defined see the table below Switching between level 1 and level 2 3 is done by simultaneously pressing buttons pfi and pfj immediately followed by simultaneously pressing buttons s and ba and keeping all 4 buttons pressed for...

Page 23: ...heating off temperature 4 02 Space heating off temperature outdoor temperature above which space heating is turned off to avoid overheating 5 Equilibrium temperature and space heating priority temperature Equilibrium temperature The equilibrium temperature field settings apply to operation of the optional backup heater When the equilibrium temperature function is enabled operation of the backup he...

Page 24: ...ry water tank When the sanitary water is heated and the sanitary water set point temperate as set by the user has been reached the booster heater will continue to heat the sanitary water to a temperature a few degrees above the set point temperature i e the booster heater OFF temperature These extra degrees are specified by the sanitary water step length field setting Correct setting prevents the ...

Page 25: ...mum leaving water temperature for heating operation 9 02 Cooling set point upper limit maximum leaving water temperature for cooling operation 9 03 Cooling set point lower limit minimum leaving water temperature for cooling operation A Quiet mode This field setting allows to select the desired quiet mode Two quiet modes are available quiet mode A and quiet mode B In quiet mode A priority is given ...

Page 26: ...atus 1 ON 0 1 01 Priority 0 OFF 0 1 02 Space heating off temperature 35 14 35 1 C 5 Equilibrium temperature and space heating priority temperature 00 Equilibrium temperature status 1 ON 0 1 01 Equilibrium temperature 0 15 20 1 C 02 Space heating priority status 0 OFF 0 1 03 Space heating priority temperatures 0 15 20 1 C 04 Set point correction for sanitary water temperature 10 0 20 1 C 6 DT for s...

Page 27: ...d as follows when no action is performed the user interface will return to normal mode after 10 seconds or by pressing the z button once To test the heating operation push the h c button so the h icon is displayed To start the test run operation press the y button To test the cooling operation push the h c button so the c icon is displayed To start the test run operation press the y button To test...

Page 28: ... unit and look for obvious defects such as loose connections or defective wiring Before contacting your local Daikin dealer read this chapter carefully it will save you time and money When a safety device was activated stop the unit and find out why the safety device was activated before resetting it Under no circumstances safety devices may be bridged or changed to a value other than the factory ...

Page 29: ... reset button Check whether booster heater and backup heater are configured to operate simultaneously field setting 4 02 see Field settings on page 19 Check whether or not the thermal fuse of the backup heater is blown refer to Main components Backup heater thermal fuse on page 6 for location of the reset button The backup heater equilibrium temperature has not been configured correctly Raise the ...

Page 30: ...e refer to Technical specifications on page 28 Contact your local Daikin dealer E7 Fan lock failure fan is locked Check if the fan is not obstructed by dirt If the fan is not obstructed contact your local Daikin dealer E9 Malfunction of electronic expansion valve Contact your local Daikin dealer EC Sanitary water temperature too high 89 C Check that the contactor of the electric booster heater is ...

Page 31: ...ry water by heat pump 20 35 C 20 35 C a MBSP Male British Standard Pipe b At 1 m in front of the unit free field condition Heating cooling models EKHBX Heating only models EKHBH Standard unit power supply via outdoor unit Power supply 230 V 50 Hz 1P Nominal running current See outdoor unit installation manual Backup heater Power supply See Connection of the backup heater power supply on page 12 Ma...

Page 32: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW36978 1C Copyright Daikin ...

Reviews: