Altherma EKHBH016AA Installation Manual Download Page 20

Installation manual

17

EKHBH/ EKSWW150-300V3/Z2

Indoor unit for air to water heat pump and sanitary warm water tank for air to water heat pump system

4PW36978-1C

S

TART

-

UP

 

AND

 

CONFIGURATION

The indoor unit should be configured by the installer to match the
installation environment (outdoor climate, installed options, etc.) and
user expertise.

DIP switch settings overview

DIP switch SS2 is located on the switch box' PCB (see 

"Switch box

main components" on page 7

) and allows configuration of sanitary

water tank installation, room thermostat connection and pump
operation.

Room thermostat installation configuration

The following table summarizes the required configuration and
thermostat wiring at the terminal block in the switch box. Pump
operation is listed in the third column. The three last columns indicate
whether the following functionality is available on the user interface
(UI) or handled by the thermostat (T):

space heating or cooling on/off (

y

)

heating/cooling changeover (

=

)

heating and cooling schedule timers (

pr

)

Pump operation configuration

Without room thermostat

When no thermostat is connected to the indoor unit, pump operation
will be determined by the leaving water temperature.

To  force continuous pump operation when no room thermostat is
connected do the following:

-

set toggle switch SS2-3 to ON,

-

short-circuit the terminal numbers 23-17-13 on the terminal 
block in the switch box.

With room thermostat

When a thermostat is connected to the indoor unit, the pump will
operate continuously whenever there is heating or cooling demand
requested by the thermostat.

It is important that all  information in this chapter is read
sequentially by the installer and that the system is
configured as applicable.

Switch off the power supply before opening the switch box
service panel and making any changes to the DIP switch
settings.

DIP 
switch 
SS2

Description 

ON

OFF

1

Not applicable for installer 

(Default)

2

Sanitary water tank 
installation 
(see 

"Sanitary water tank 

installation configuration" 
on page 18

)

Installed

Not installed 
(Default)

3

Room thermostat 
connection
(see 

"Room thermostat 

installation configuration" 
on page 17

)

Room thermostat 
connected 

No room 
thermostat 
connected 
(Default)

4

This setting

(a)

 decides the 

operation mode when 
there is a simultaneous 
demand for more space 
heating/cooling and 
sanitary water heating.

(a) only applicable in case DIP switch 2 = ON

Heating/cooling

Sanitary (Default)

When  no room thermostat  is connected to
the indoor unit, toggle switch SS2-3 should be
set to OFF.

When a room thermostat is connected to the
indoor unit, toggle switch SS2-3 should be set
to ON.

On the room thermostat, set the hysteresis appropriately to
prevent the pump from repeatedly turning on and off (i.e.
chattering), and thereby impacting the lifetime of the pump.

NOTE

When a room thermostat is connected to the
indoor unit, the heating and cooling schedule
timers are never available. Other schedule timers
are not affected. For more information on the
schedule timers, refer to the operation manual.

When a room thermostat is connected to the
indoor unit, and the 

=

  button or 

y

  button is

pressed, the centralised control indicator 

e

  will

flash to indicate that the room thermostat has
priority and controls on/off operation and change
over operation.

4

3

2

1

ON

OFF

4

3

2

1

ON

OFF

4

3

2

1

ON

OFF

Thermostat

Configuration

Pump 
operation

y

y

y

y

=

=

=

=

 

p

p

p

pr

r

r

r

No thermostat

• SS2-3 = OFF
• wiring: (non)

determined by 
leaving water 
temperature 

(a)

(a) The pump will stop when space heating/cooling is turned off or when the water 

reaches the desired water temperature as set on the user interface. With space 
heating/cooling turned on, the pump will then run every 5 minutes during 3 
minutes to check the water temperature.

UI

UI

UI

• SS2-3 = ON
• wiring:

on when space 
heating or 
cooling is on 

(

y

)

UI

UI

UI

Heating only 
thermostat

• SS2-3 = ON
• wiring:

on when 
heating 
request by 
room 
thermostat

T

Thermostat with 
heating/cooling 
switch

• SS2-3 = ON
• wiring:

on when 
heating 
request or 
cooling request 
by room 
thermostat

T

T

th =

Thermostat contact

C =

Cooling contact

H =

Heating contact

L, N =

230 V AC

NOTE

To  set the pump speed, refer to 

"Setting the pump

speed" on page 19

.

X2M

H C L N

1

2

3

4

X2M

H C L N

1

2

3

4

X2M

H C

th

L N

1

2

3

4

X2M

H C

H

th

C

L N

1 2 3 4

Summary of Contents for EKHBH016AA

Page 1: ...INSTALLATION MANUAL EKHBH016AA EKHBX016AA EKSWW150V3 EKSWW200V3 EKSWW300V3 EKSWW200Z2 EKSWW300Z2 Indoor unit for air to water heat pump and sanitary warm water tank for air to water heat pump system ...

Page 2: ... 5 6 7 1 2 3 5 4 3 4 5 350 300 35 48 35 668 895 922 39 361 48 142 101 235 235 502 500 23 30 4 7 400 90 200 1 2 3 4 5 3 4 FBSP 1 2 FBSP 0 40 0 H 300 630 220 110 1 2 3 4 5 6 Ø580 3 4 FBSP 3 4 FBSP 3 4 FBSP 1150 1 1 4 FBSP 1 1 4 MBSP 96 30 90 1 2 3 5 4 ...

Page 3: ...ß den Vorschriften der 03 conformément aux stipulations des 04 overeenkomstig de bepalingen van 05 siguiendo las disposiciones de 06 secondo le prescrizioni per 07 Ì ٠ÚËÛË Ùˆv È Ù Íˆv Ùˆv 08 de acordo com o previsto em 09 в соответствии с положениями 10 under iagttagelse af bestemmelserne i 11 enligt villkoren i 12 gitt i henhold til bestemmelsene i 13 noudattaen määräyksiä 14 za dodržení ustan...

Page 4: ...nit is the indoor part of the reversible air to water Daikin ERHQ heat pumps These units are designed for wall mounted indoor installation and used for both heating and cooling applications The units can be combined with Daikin fan coil units floor heating applications low temperature radiators and sanitary water heating applications Heating cooling units and heating only units The indoor unit ran...

Page 5: ...acity 2 Required heating capacity site dependent 3 Additional heating capacity provided by the backup heater 4 Equilibriumtemperature can be set through the user interface refer to Field settings on page 19 TA Ambient outdoor temperature PH Heating capacity NOTE Especially for the United Kingdom For installation of an EKSWWU sanitary water tank refer to the installation manual supplied with the EK...

Page 6: ...ed in series with another heat source e g gas boiler it shall be made sure that the return water temperature to the heat exchanger does not exceed 55 C Daikin shall not be held liable for any damage resulting from not observing this rule 1 Outdoor unit 6 Collector field supply 2 Indoor unit 7 Shut off valve 3 Heat exchanger FHL1 3 Floor heating loop field supply 4 Pump 5 Shut off valve T Room ther...

Page 7: ... be done by the user interface on the indoor unit Sanitary heating Sanitary water heating is as described under Application 2 on page 3 Application 4 Space cooling and heating application without a room thermostat connected to the indoor unit but with a heating only room thermostat controlling the floor heating and a cooling heating thermostat controlling the fan coil units Heating is provided thr...

Page 8: ...internals e g to connect the field wiring the switch box service panel can be removed Thereto loosen the front screws and unhitch the switch box service panel 1 Outdoor unit 14 Motorised 2 way valve for activation of the room thermostat field supply 2 Indoor unit 3 Heat exchanger 4 Pump FCU1 3 Fan coil unit with thermostat field supply 5 Shut off valve 6 Collector field supply FHL1 3 Floor heating...

Page 9: ...r unit 11 Water inlet connection 12 Water outlet connection 13 Drain and fill valves 14 Water filter The water filter removes dirt from the water to prevent damage to the pump or blockage of the evaporator The water filter should be cleaned on a regular base See Maintenance on page 25 15 Expansion vessel drain valve The drain valve of the expansion vessel allows draining the remaining water in the...

Page 10: ...IP switch SS2 The DIP switch SS2 provides 4 toggle switches to configure certain installation parameters See DIP switch settings overview on page 17 11 X13A socket The X13A socket receives the K3M connector only for installations with sanitary water tank 12 X9A socket The X9A socket receives the thermistor connector only for installations with sanitary water tank 13 Pump fuse FU2 in line fuse 14 P...

Page 11: ...ries see Accessories on page 2 are enclosed Bring the unit as close as possible to its final installation position in its original package in order to prevent damage during transport The indoor unit weighs approximately 55 kg and should be lifted by two persons using the two lifting bars provided Requirement Value Maximum allowable refrigerant piping length between outdoor unit and indoor unit 75 ...

Page 12: ...tallation of the unit check the following points The maximum water pressure is 3 bar Two shut off valves are delivered with the unit To facilitate service and maintenance install one at the water inlet and one at the water outlet of the indoor unit Mind position of the shut off valves Orientation of the integrated drain valves is important for servicing See figure 4 Drain taps must be provided at ...

Page 13: ...ections must be made in accordance with the outlook diagram delivered with the unit respecting the water in and outlet If air moisture or dust gets in the water circuit problems may occur Therefore always take into account the following when connecting the water circuit Use clean pipes only Hold the pipe end downwards when removing burrs Cover the pipe end when inserting it through a wall so that ...

Page 14: ...essure relief valve Water quality must be according to EN directive 98 83 EC WARNING A main switch or other means for disconnection having a contact separation in all poles must be incorporated in the fixed wiring in accordance with relevant local and national legislation Switch off the power supply before making any connections All field wiring and components must be installed by a licensed elect...

Page 15: ... all wiring specifications Connection of the indoor unit power supply and communication cable Power circuit and cable requirements Power supply for the indoor unit is to be provided through the outdoor unit Data communication with the outdoor unit is provided through the same cable For all guidelines and specifications regarding field wiring between the indoor unit and the outdoor unit please refe...

Page 16: ...wer supply 230 V AC Maximum running current 100 mA Wiring the 2 way valve 1 Using the appropriate cable connect the valve control cable to the X2M terminal as shown on the wiring diagram 2 Fix the cable s with cable ties to the cable tie mountings to ensure strain relief Wiring the 3 way valve 1 Using the appropriate cable connect the valve control cable to the appropriate terminals as shown on th...

Page 17: ...e water outlet temperature during use Immediately after installation the sanitary water tank must be flushed with fresh water This procedure must be repeated at least once a day the first 5 consecutive days after installation In case of limited consumption of hot water e g at holiday residences or at houses that are occasionally not occupied the sanitary water tank installation must be fitted with...

Page 18: ...el make sure the wall is sturdy In both cases make sure the tank is mounted level 3 Apply thermal paste to the thermistor and insert the thermistor as deep as possible in the thermistor socket Fix using the nut provided Connecting the water circuits 1 Connect the water inlet and water outlet 2 Connect the hot and cold water supply tubes 3 Connect the pressure relief valve field supply opening pres...

Page 19: ...e PCB 6 Connect the prewired earth wires of the terminal block X3M and X4M to the earthing screw 7 Connect the booster heater power supply and thermal protection cable field supply to terminal X4M earth 1 2 and X2M 13 14 8 Connect the booster heater power supply cable to the terminal block X3M 9 Fix the cables to the cable tie mountings with cable ties to ensure strain relief 10 Set DIP switch SS2...

Page 20: ...talled Not installed Default 3 Room thermostat connection see Room thermostat installation configuration on page 17 Room thermostat connected No room thermostat connected Default 4 This setting a decides the operation mode when there is a simultaneous demand for more space heating cooling and sanitary water heating a only applicable in case DIP switch 2 ON Heating cooling Sanitary Default When no ...

Page 21: ...box on loose connections or damaged electrical components 6 Fixation Check that the unit is properly fixed to avoid abnormal noises and vibrations when starting up the unit 7 Damaged equipment Check the inside of the unit on damaged components or squeezed pipes 8 Refrigerant leak Check the inside of the unit on refrigerant leakage If there is a refrigerant leak call your local Daikin dealer 9 Powe...

Page 22: ...o exit FIELD SET MODE Detailed description 0 User permission level If required certain user interface buttons can be made unavailable for the user Three permission levels are defined see the table below Switching between level 1 and level 2 3 is done by simultaneously pressing buttons pfi and pfj immediately followed by simultaneously pressing buttons s and ba and keeping all 4 buttons pressed for...

Page 23: ...heating off temperature 4 02 Space heating off temperature outdoor temperature above which space heating is turned off to avoid overheating 5 Equilibrium temperature and space heating priority temperature Equilibrium temperature The equilibrium temperature field settings apply to operation of the optional backup heater When the equilibrium temperature function is enabled operation of the backup he...

Page 24: ...ry water tank When the sanitary water is heated and the sanitary water set point temperate as set by the user has been reached the booster heater will continue to heat the sanitary water to a temperature a few degrees above the set point temperature i e the booster heater OFF temperature These extra degrees are specified by the sanitary water step length field setting Correct setting prevents the ...

Page 25: ...mum leaving water temperature for heating operation 9 02 Cooling set point upper limit maximum leaving water temperature for cooling operation 9 03 Cooling set point lower limit minimum leaving water temperature for cooling operation A Quiet mode This field setting allows to select the desired quiet mode Two quiet modes are available quiet mode A and quiet mode B In quiet mode A priority is given ...

Page 26: ...atus 1 ON 0 1 01 Priority 0 OFF 0 1 02 Space heating off temperature 35 14 35 1 C 5 Equilibrium temperature and space heating priority temperature 00 Equilibrium temperature status 1 ON 0 1 01 Equilibrium temperature 0 15 20 1 C 02 Space heating priority status 0 OFF 0 1 03 Space heating priority temperatures 0 15 20 1 C 04 Set point correction for sanitary water temperature 10 0 20 1 C 6 DT for s...

Page 27: ...d as follows when no action is performed the user interface will return to normal mode after 10 seconds or by pressing the z button once To test the heating operation push the h c button so the h icon is displayed To start the test run operation press the y button To test the cooling operation push the h c button so the c icon is displayed To start the test run operation press the y button To test...

Page 28: ... unit and look for obvious defects such as loose connections or defective wiring Before contacting your local Daikin dealer read this chapter carefully it will save you time and money When a safety device was activated stop the unit and find out why the safety device was activated before resetting it Under no circumstances safety devices may be bridged or changed to a value other than the factory ...

Page 29: ... reset button Check whether booster heater and backup heater are configured to operate simultaneously field setting 4 02 see Field settings on page 19 Check whether or not the thermal fuse of the backup heater is blown refer to Main components Backup heater thermal fuse on page 6 for location of the reset button The backup heater equilibrium temperature has not been configured correctly Raise the ...

Page 30: ...e refer to Technical specifications on page 28 Contact your local Daikin dealer E7 Fan lock failure fan is locked Check if the fan is not obstructed by dirt If the fan is not obstructed contact your local Daikin dealer E9 Malfunction of electronic expansion valve Contact your local Daikin dealer EC Sanitary water temperature too high 89 C Check that the contactor of the electric booster heater is ...

Page 31: ...ry water by heat pump 20 35 C 20 35 C a MBSP Male British Standard Pipe b At 1 m in front of the unit free field condition Heating cooling models EKHBX Heating only models EKHBH Standard unit power supply via outdoor unit Power supply 230 V 50 Hz 1P Nominal running current See outdoor unit installation manual Backup heater Power supply See Connection of the backup heater power supply on page 12 Ma...

Page 32: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW36978 1C Copyright Daikin ...

Reviews: