6 | 18
4 Terminal Assignment
The electrical connections are made via screw-clamps. The numbering can be found on the front side
of the clamps. The maximum wire cross section is 2,5 mm². The EMC-installation instruction is to be
complied with. Maximum interference immunity is achieved by direct connection of the cable screen
with “clean” and low resistance protective ground (PG). A lengthening of the cable screen makes the
interference immunity considerably worse. The connection of the screen should be done directly with a
cable clamp.
If, however, a connection to a PG is not possible, the cable screen may be connected to clamp 15 of the
amplifier (analogue ground/screen). Anyhow, enough interference immunity is to be ensured.
Clamp
Description
Clamp
Description
1
Supply voltage
9
-SG-Signal Transducer
2
Supply Ground
10
+SG-Signal Transducer
3
Supply Ground
11
+SG-Sense Transducer
4
Analogue Ground
12
+SG-Excitation Transducer
5
Analogue Ground
13
-SG-Sense Transducer
6
Analogue output 2 (Version 4 … 20 mA)
14
-SG-Excitation Transducer
7
Analogue Ground
15
Analogue Ground/Screen
8
Analogue output 1 (0 … +10 V / ± 10 V)
16
Analogue Ground
Terminals “supply ground” and “analogue ground” are isolated galvanically. To unset this isolation
clamp 3 and 4 are to be bridged.
4/6 wire technology:
Factory pre-set
Jumper J1
Jumper J2
* 4-wire technology
ON
ON
6-wire technology
OFF
OFF