ADDITIONAL SPECIFICATIONS
Pressure Drop
Pressure Drop (Line Loss) within the boiler is less
than the pipe rating of the pipe within the boiler, so
there is no appreciable pressure drop.
Explanation of GPM Flow
e following are given as examples of gallons per
minute water Gow required to deliver hot water in
order to provide heating of a given number of
degrees and at a certain BTU level:
•
500K BTU’s at 20 degrees temperature
di:erential requires 50 gallons per minute.
•
250K BTU’s at 20 degrees temperature
di:erential requires 25 gallons per minute
•
1M BTU’s at 20 degrees temperature
di:erential requires 100 gallons per minute.
Wood Gun E Series Specifications
E100
E140
E180
E250
BTU/Hour Max
150,000
200,000
230,000
350,000
BTU 8 Hour Avg
Output*
100,000
140,000
180,000
250,000
Water Capacity
60 gallons
80 gallons
90 gallons
140 gallons
Fire Box Capacity
6.5 ft
3
10 ft
3
14 ft
3
22 ft
3
Fire Box Length
28''
32''
32''
48''
Standard Door
Opening
14'' x 14''
14'' x 14''
14'' x 14''
14'' x 14''
Height
58''
64''
66''
74''
Width (cyclone
removed)
26''
26''
31''
31''
Depth
44''
48''
48''
66'
Flue Size
6''
6''
6''
8''
Weight (w/o gas/oil)
1,400 lbs
1,650 lbs
2,100 lbs
3,000 lbs
Typical Heating
Capacity**
3,000 ft
2
4,000 ft
2
5,000 ft
2
9,000 ft
2
*Based on loading rebox with seasoned rewood **Subject to building design/construction
- 47 -
Summary of Contents for wood gun E100 SF
Page 2: ......
Page 24: ...Photo Smoke flap installed 19 ...
Page 46: ...Steel Center Brick 8 Inch 41 ...
Page 49: ...Appendix A Boiler Specification Diagram 44 ...
Page 50: ... 45 ...
Page 51: ... 46 ...
Page 53: ...Appendix B Wiring Diagrams 48 ...
Page 54: ... 49 ...
Page 55: ... 50 ...
Page 56: ... 51 ...
Page 57: ... 52 ...
Page 58: ... 53 ...
Page 59: ... 54 ...
Page 60: ... 55 ...
Page 61: ...Appendix C Exploded Parts Drawings 56 ...
Page 63: ... 58 ...
Page 68: ...Appendix F Boiler Piping and Ducting Examples 63 ...