ALTER PM 740 T Technical Note Download Page 7

    

PM 740 T  

page    6  

of 21

                                                                                                                                      File: PM740T_r3eng -  Settembre 2004   -    Manuale per: PM 740 T

PM 740 

PM 740 

    

PM 740 T 

File: PM740T_r3eng -  Settembre 2004 - Manuale per: PM 740 T                                                                                                                                

         

page     7  

of  21 

Fuse replacement

To replace the fuses on the rear panel proceed as follow:

 

- switch-off the main breaker on front panel or wha   

 

tever device is provided to remove main line from the  

 

equipment;

 

- unscrew the fuseholder cap;

 

- replace the fuse with a new one with the same  

 

 

electrical characteristics;

 

- also inspect the fuseholder: if it’s oxidised or it has    

 

burn marks then replace it;

 

- install the fuseholder cap and screw tight.

 

- fuse values are given below in Fuse Specs page 5

Equipment installation

The PM740 cannot operate on a bench: it must be installed into 

a proper cabinet such as a commercial 19” standard  enclosure. 

The equipment is intended for industrial use only, not for 

laboratory use, and the user must respect the wiring norms 

and prescriptions as described into next paragraph (“Wiring 

instruction”).

The equipment must not operate cantilevered, it must be safely 

fixed inside a cabinet by means of screws on the front panel 

(which is provided with 4 holes) and supported by means of a 

proper frame on the bottom for, at least, 3/4 of the total depth.

Usually two “L” shaped supports on each side of the equip-

ment, having a dimension of mm 10(h) x 30(l) x 1.5 (thick) are 

suitable for this purpose. 

The rear side of the equipment must be protected by  a fixed 

panel which can be removed only by means of tools or by a 

door with security micro-switch: when the door is opened the 

micro-switch must shut-off  the main line. This safety pre-

cautions must be taken to avoid operation on rear fuses or on 

connectors while the unit is still powered.

Special attention must  be taken on designing the cooling air 

flow whenever several units are stacked in the same cabinet.

Note that each unit has its own fan which supplies approx 150 

m³/h: the outlet of the exhaust air is on the back of the equip-

ment.

When designing a cabinet to house several units we recom-

mend that the following design criteria be adopted:

 

- use a standard 19” wide enclosure with a depth of    

 

800 mm (32”);

 

- allow free intake of the cooling air from the front of  

 

the cabinet and exhaust air from back;

 

- in case of ambient air with high degree of dust and    

 

moisture, install a proper air conditioner; if you cannot  

 

do this, then  you have to use suitable air filters and    

 

instruct the user about their cleaning;

 

- provide a separation between the air intake duct and  

 

the air outlets, in order to avoid air-recycling.

Handling instructions

The equipment weight is 20 kg (44 lbs). Always lift from the 

bottom and use an adequate rugged support to avoid personal 

injury and damage to equipment itself.

In the case of shipping,  package  with the original package or 

use a wooden case and a proper filler: movement of the equip-

ment inside the package must be avoided.

Warning

: use handles only for helping during    installation. 

Never use handles to lift  the rack: the handles will not 

withstand the off-center weight of the rack!

To lift  always lean the rack over a proper supporting base.

Wiring   instructions

The  PM740 must be installed and serviced only by qualified 

personnel acquainted with the regulations covering the applica-

tion. For safety operations the following rules must be adopted:

I)  the equipment must be grounded through connector  #1 

using pin 4 (see the wiring diagram at page 15);

II) connect the ground screw on panel rear (indicated by 

“ground” symbol) directly to the remote microwave generator 

head by a separate yellow/green wire gauge 2.5 mm²;

III) the  main supply, 3 x400V must be provided through con-

nector #1: connect  phases according to schematic at page 15.  

2,5 mm² wire must be used with this connector.

IV) The magnetron head unit must be connected to the main 

unit by connector #2. 1.5 mm² wire must be used with this 

connector. Refer to wiring diagram on page 16;

Summary of Contents for PM 740 T

Page 1: ...PM 740 T SWITCHING POWER GENERATOR WITH PULSED OUTPUT CAPABILITY FOR 2 kW MAGNETRON C W 8 kW PEAK POWER TECHNICAL NOTE Issue September 2004...

Page 2: ...stanza model PM740T xxx PM740T xxxC TM020 xxx0 modello TM020 xxx1 TMA20 xxx0 TMA20 xxx1 Complies with the following norms Soddisfa le seguenti norme EN 61010 1 1994 A2 1996 EN 61010 1993 A2 1995 EN550...

Page 3: ...product or product family EMC emission standard exists it shall take precedence over all aspects of this generic standard The equipment described in this manual has been classified as industrial scien...

Page 4: ...see drawing a main switch 1 abacklitLCDdisplayshowingaselectedworkingparameter 2 i e one of the following the output power the forward microwave power the reflected microwave power as well as any of...

Page 5: ...tage cat II according IEC 664 Intake current 400 V 7 A max Power factor CW 0 74 Efficiency CW 90 Max Output power 2800 W Max anodic mean current 700 mA CW mode Max anodic peak current 3 1 A Pulse mode...

Page 6: ...pecs Size type 10x38 mm ceramic cartridge Speed action quick F Rated current 6 A Rated voltage 500 V For instructions about fuse replacement please refer to related paragraph on the next page Physical...

Page 7: ...150 m h the outlet of the exhaust air is on the back of the equip ment When designing a cabinet to house several units we recom mend that the following design criteria be adopted use a standard 19 wi...

Page 8: ...asy reach of the operator XII the external circuit breaker must be marked as the discon necting device for the PM740 XIII the connector 1 must never be used as a switch off device Failure to comply wi...

Page 9: ...n this state the output power and the filament is immediately shut off The alarm type is indicated on the display The unit will exit the Alarm mode and enter the Reset Wai ting state only when the ala...

Page 10: ...on the next page then read the specific instruction for every parameter INFORMATION 1 3 Magnetron This indicates how many working hours the magnetron has operated it can be reset by the user from the...

Page 11: ...up Information 1 3 Information 2 3 Information 3 3 OK On Pre v OK On Next Unit Setup 2 2 Press Esc Press Esc Press Esc Press Esc Esc OK On Next OK On Pre v Press Esc OK on Host Com OK on Unit Setup OK...

Page 12: ...ee the comunication protocol documentation Max Rev Pwr This parameter allows the user to set a maximim reverse power threshold If the reverse power input voltage exceeds this threshold the unit will g...

Page 13: ...gnal must be OFF II Connect the serial cable to PC serial port and to RS232 serial port on the PM740 III Remove the top cover of the PM740 IV Locate the CPU board installed on the front panel and set...

Page 14: ...PM 740 PM 740 PM 740 T File PM740T_r3eng Settembre 2004 Manuale per PM 740 T page 13 of 21 COMPONENT LAYOUT bottom layer COMPONENT LAYOUT top layer...

Page 15: ...filter FL20AY01 17 4 Capacitor CR951A2K5 18 1 H V Socket Lemo MOERAY 410 Conn 3 1 H V Plug Lemo MOFFA1Y 410 19 1 Interface board M293 800000293 20 1 14 pin Socket AMP CPC MOCPC14 1826411 Conn 2 21 1 1...

Page 16: ...PM 740 PM 740 PM 740 T File PM740T_r3eng Settembre 2004 Manuale per PM 740 T page 15 of 21 Pin out of CONN 1...

Page 17: ...PM 740 T page 16 of 21 File PM740T_r3eng Settembre 2004 Manuale per PM 740 T Pin out of CONN 2 3 4...

Page 18: ...PM 740 PM 740 PM 740 T File PM740T_r3eng Settembre 2004 Manuale per PM 740 T page 17 of 21 Pin out of CONN 5...

Page 19: ...PM 740 T page 18 of 21 File PM740T_r3eng Settembre 2004 Manuale per PM 740 T Pin out of serial port...

Page 20: ...ected usually due by a sudden drop of the main line voltage check the main supply line or HV cable disconnected VOLTAGE ALARM 4 Overvoltage detected The output voltage exceeds the maximum allowed volt...

Page 21: ...Check the threshold or adjust the power setting INT RAM ALARM 12 Internal memory corruption With the unit switched OFF check that the battery is properly located it s a click in battery installed over...

Page 22: ...solator with dummy load several models available ask for quote and type Cable set p n 44 1384 740 Includes high vol tage cable main line cables head cables signals cable and plugs on psu side p n 44 1...

Reviews: