E32.0.A3.6C-01 Manual for connection and operation of the JDS-211 page 8 of 16
“
2.
Err
“
Preferred state
in case of error ( only at “
3P
“)
possible settings:
„On“
output in case of error active (relay on)
„
Off“
output in case of error inactive (relay off)
“
AL.Hi
“
Maximum alarm-value
(only at“
2P.AL
“ )
possible settings: AL.Lo .. max. display range
“
AL.Lo
“
Minimum alarm-value
(only at“
2P.AL
“)
possible settings: min. display range .. AL.Hi
“
A.dEL
“
Delay of the alarm-function in sec
(only at “
2P.AL
“)
possible settings: 0 .. 9999
When pressing button 1, the display shows “
outP
“ again. Now you have finished the output configuration.
Press now button 4 to exit the menu.
5.1.2. Min-/Max-Alarm (individual or common)
This chapter describes how to adjust the device‘s alarm boundaries for min-/max-alarm-monitoring.
This instruction demands that you selected “
AL.F1
“ or “
AL.F2
“ as your desired output function like it is ex-
plained in chapter 5.1.
By means of
button 1
you
validate
the set parameter or go to the
next parameter
.
By means of
button 2
or
button 3
you
choose
your desired
value
.
By means of
button 4
you
exit
the output configuration menu.
Please note that the alarm-outputs are inverted! This means, that the output will be active when there is no alarm!
“
AL.Hi
“
maximum alarm-value
possible settings: AL.Lo ... max. display range
“
AL.Lo
“
minimum alarm-value
possible settings: min. display range ... AL.Hi
“
A.dEL
“
alarm delay
in sec
possible settings: 0 .. 9999
When pressing button 1, the display shows “
outP
“ again. Now you have finished the configuration. Press
now button 4 to exit the menu.
5.2. Offset- and slope-adjustment: Menu calling and adjustment
- Turn on the device and wait after it finished its built-in segment test.
- At the same time press the pushbutton on the rear side (button 5) and button 3 for >2 seconds. The
device displays “
OFFS
“ (offset).
- Use button 2 or button 3 for setting the desired zero point offset-value.
The input of the offset will be in digit or °C.
The value that had been set will be subtracted from the measured value..
(for further information see “scale”)
- Press button 1 to validate your selection. The display shows “
OFFS
“ again.
- When pressing button 1 again, the device will be displaying “
SCAL
“. (scale = slope)
- Use button 2 or button 3 to select the desired slope-adjustment.
The slope adjustment will be entered in %. The displayed value is calculated depending on the input sig-
nal according to the following formula.
Displayed value = (measured value – zero point offset) * (1 + slope adjustment [% / 100])
Example:
The setting is 2.00 => the slope has risen 2.00% => slope = 102%.
When measuring a value of 1000 (without slope-adjustment) the device would display 102 (with slope
adjustment of 102%)
- Press button 1 to validate the selection of the slope-adjustment. The display shows “
SCAL
“ again.
- When pressing button 1 again, the display shows “
OFFS
“ again.
Now you have finished the offset- and slope-adjustment.