alre JDS-211 Manual For Connection And Operation Download Page 11

E32.0.A3.6C-01                    Manual for connection and operation of the JDS-211                        page 11 of 16

AL.Hi

 

Maximum alarm-value

possible settings: AL.Lo .. max. display range

AL.Lo

 

Minimum alarm-value

possible settings: min. display range .. AL.Hi

A.dEL

 

Delay of the alarm-function 

in sec

possible settings: 0 .. 9999

Example: You want to have a temperature alarm-monitoring of a greenhouse. The alarm should start when

the temperature rises above 50°C or falls below 15°C.

   

Therefore your settings will be 50°C for the maximum alarm-value “AL.HI“ and 15°C for the mini-
mum alarm-value “AL.Lo“.
=> The alarm will be starting after the temperature rises above 50°C and stays above 50°C for
the entered delay time or after it had been falling below 15°C and stays below 15°C for the en-
tered delay time.
Please note that the alarm-outputs are inverted! This means, that the output will be active when
there is no alarm!

When pressing button 1, the display shows “

1.SP

 “ again. Now you have finished the configuration. Press

now button 4 to exit the menu.

6.3. Manual adjustment of the manipulating variable (manual control)

This chapter describes how to adjust manually the manipulating variable. This allows to adjust the power
supplied to the process by hand.
The manually adjusted manipulating variable is active till the menu is closed. Then the automatic regulation
will be activated again.

-   The menu for the manual adjustment of the manipulating variable is called by pressing button 4 for >2

seconds.

-

  The device displays “

1.Set

“.   

-

 

1.SEt

 

manipulating variable 

 in %

possible settings: 0,0. ... 100,0

-

 

Depending on the configurated type of control the manual adjustment of the manipulating variable is different:

-

 

PID-control:

By means of 

button 2 

 or

 button 3 

 you 

choose

 your desired 

manipulating variable.

The manipulating variable is immediately active and will persist till the menu is closed or it is changed
again.

-

 

3point-motorised valve control:

By means of 

button 2 

 or

 button 3 

 you 

choose

 your desired 

manipulating variable 

and validate it by

button 1

.

The controller calculates the needed the activation of the actuator to get the desired manipulating vari-
able and actuates the motor accordingly.

Please note: If the minimum change of manipulating variable is not reached, there will be no activation.

-

Press button 4 to exit the manual adjustment of the manipulating variable.

7. Serial interface

The serial interface allows the device to communicate with a host computer. Data polling and data transfer is
done in master/slave mode, so the device will only send data on demand. Every device has a unique ID-
number that makes exact identification of each device possible. With the help of a software (like EbxKonfig –
freeware version available via internet at alre.de) you are able to reassign an address to the device.

Additional accessories needed for the interface mode:

- Level converter: interface of device 

"

 PC:

i.e. EBW1

- Software for communication with the device

EBS9M:

9-channel-software for displaying a measured value.

EASYCONTROL: universal multi-channel software for real-time-recording and displaying measure-values

of a device in ACCESS®-database-format.

Summary of Contents for JDS-211

Page 1: ...connection and operation of the JDS 211 page 1 of 16 Manual for connection and operation of JDS 211 item number G800040900 as of version 2 3 Fa ALRE IT Regeltechnik GmbH Richard Tauber Damm 10 D 12277...

Page 2: ...ntroller with alarm 7 5 1 2 Min Max Alarm getrennt oder gemeinsam 8 5 2 Offset and slope adjustment Menu calling and adjustment 8 6 Operation 9 6 1 Min max value memory 9 6 2 Switching points and alar...

Page 3: ...The device must be switched off and must be marked against using again in case of obvious malfunc tions of the device which are e g visible damage no prescripted working of the device storing the dev...

Page 4: ...suggest to connect the device s switching outputs after You have configured the device properly Hint By calling a configuration menu for the offset and slope adjustment the measurement and regulation...

Page 5: ...hould be connected as 3 wire system too If a 2 wire system is essential the potential deviation can be compensated by the offset adjustment chapter 5 2 Pt100 temperature probe 3 wire Pt100 temperature...

Page 6: ...ting the adjustment will be cancelled the changing discarded and it will be changed to the parameter view If you don t press any button for more than 60 sec in the menu the menu will be automatically...

Page 7: ...t C 3point motorised valve control cooling only at 2P 1 SP set point value possible settings min max display range 1 Pb Proportional band possible settings 1 9999 position of the dot depends on displa...

Page 8: ...e settings min display range AL Hi A dEL alarm delay in sec possible settings 0 9999 When pressing button 1 the display shows outP again Now you have finished the configuration Press now button 4 to e...

Page 9: ...tching points and alarm boundaries will be called Depending on the configuration you have made in the output configuration menu you will get different display values Please follow the specific chapter...

Page 10: ...in sec possible settings 0 1 320 0 AL Hi Maximum alarm value possible settings AL Lo max display range AL Lo Minimum alarm value possible settings min display range AL Hi A dEL Delay of the alarm fun...

Page 11: ...nds The device displays 1 Set 1 SEt manipulating variable in possible settings 0 0 100 0 Depending on the configurated type of control the manual adjustment of the manipulating variable is different P...

Page 12: ...that the valid display range 9999 digit of the device has been exceeded Err 4 Values below display range Indicates that display value is below the valid display range of the device 1999 digit Err 7 S...

Page 13: ...dard or the corresponding designation on the label on the housing Nominal temp 25 C Operating ambient 20 to 50 C Relative humidity 0 to 80 RH non condensing Storage temp 30 to 70 C Housing Dimensions...

Page 14: ...rvene weakly The control gets inert 1 Int Integral time I action Integral time in sec of the PID control algorithms The higher the set value the weaker the effect The control tends to swinging if inte...

Page 15: ...nt and derivative time 1 dEr are switched off The device works as P controller Start the control and wait until the temperature gets constant This temperature although much below the set point has to...

Page 16: ...gence between actual and set point temperature but on temperature changes If the temperature falls very quickly there will be a big heating power due to the D action If the actual temperature approach...

Reviews: